Plan Review Notes
Plan Review Notes For Permit 07030523
Permit Number 07030523
Review Stop P
Sequence Number 4
Notes
Date Text
2007-12-03 17:24:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
 **FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT EQ-2.1, THE 2 PAGE "WORKSHEETS" FROM DBPR HOTEL
 AND RESTURANT DIVISION PLAN REVIEW SHALL BE ATTACHED TO
 EACH SHEET STAMPED BY THE FOOD SERVICE ON EACH SET OF
 PLANS. SECTION 102.2.1.
 ****RESPONSE NOTED, BUT WORKSHEETS HAVE NOT BEEN
 ATTACHED TO STAMPED SHEET. -MINIMUM TWO STAMPED
 SHEETS REQUIRED FOR PLAN REVIEW. (ONLY ONE SHEET
 STAMPED BY DBPR FOUND)
 ******RESPONSE NOTED, BUT THE TWO PAGE "SPECIFICATION
 WORKSHEETS" HAVE NOT BEEN ATTACHET TO THE SHEET
 REVIEWED AND STAMPED BY DBPR AS REQUIRED. PLEASE ATTACH
 WORKSHEETS.
 **RESPONSE NOTED, BUT SHT G-CS IS ON THE FRONT OF THE
 SET AND IS NOT STAMPED BY DBPR. EQ-2.1 IS NOW A NEW
 SHEET SIGNED, SEALED & DATED AFTER THE LAST PLUMBING
 PLAN REVIEW. THE TWO PAGE "SPECIFICATION WORKSHEETS"
 ARE NOT ATTACHED. PLEASE COMPLY WITH THE ORIGINAL
 COMMENT.
  
 5. ALL MEP SHEETS. THE ORIGINAL SIGNATURE OF THE
 ENGINEER IS REQUIRED WHEN THE SEAL IS AFFIXED. THE
 STAMPED SIGNATURE IS NOT APPROVED. FAC
 61G15-23.002(1)(2) & FS 471.025.
 ****RESPONSE NOTED, BUT THE SIGNATURE IS SO MUCH
 DIFFERENT THAT A SIGNED, SEALED, DATED, NOTORIZED
 LETTER SHALL BE SUBMITTED INDICATING THE LEGAL
 SIGNATURE OF THE PROFESSIONAL ENGINEER AS WELL AS A
 PICTURE I.D. WITH THE ENGINEERS SIGNATURE FOR OUR
 FILES.
 ******RESPONSE NOTED, BUT THE LETTER IS NOT SEALED AS
 REQUESTED. PLEASE SEAL THE LETTER INDICATING THE LEGAL
 SIGNATURE.
 **RESPONSE NOTED, BUT NO NEW LETTER WAS FOUND.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 15. SHT P-3.2 THE FOLLOWING GAS REQUIREMENTS SHALL BE
 SUBMITTED:
  
 A. OK
 B. OK
  
 C. OK
 D. OK
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE
 DOUBLE RACK OVEN IS NOT CLEAR AND LEGIBLE ON SHEET #3
 AND UL LISTING DOES NOT INDICATE WHAT IT WAS LISTED
 FOR. PLEASE SUBMIT A COPY OF THE UL LISTING FOR THIS
 PRODUCT.
 ******RESPONSE NOTED, BUT NEW MANUF SHEETS HAVE NOT
 BEEN SUBMITTED, NOR HAS THE UL LISTING INFORMATION.
 PLEASE SUBMIT REQUIRED INFORMATION.
 **RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE OVEN DO
 NOT REFLECT THE BTU'S INDICATED ON THE RISER DIAGRAM.
 THE MANUF. SPECIFICATION SHEETS FOR THE WATER HEATERS
 ARE NOT IN THE PACKAGE OF REQUIRED INFORMATION. PLEASE
 SUBMIT ALL MANUF. SPECIFICATION SHEETS AND MAKE SURE
 THEY REFLECT THE BTU LOAD INDICATED ON THE RISER
 DIAGRAM. INDICATE THE MODEL NUMBER ON THE SPECIFICATION
 SHEETS SUBMITTED.
  
 G. N/A
 H. N/A
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 ********NEW COMMENT********
  
 1B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]