2007-12-04 12:37:47** DENIED 4THREVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS ARE IN NEED OF ADDRESSING.
 PLEASE SEE 13-415.2.ABC.1, ONLY LIGHTING WHICH IS
 INTEGRAL FOR SIGNAGE IS EXEMPT.
 PLEASE PROVIDE INFORMATION ON THESE TYPES OF SIGNS AS
 THE LIGHTING T1A AND IT3 IS TRACK LIGHTING. HOW CAN THE
 TRACK LIGHTING BE INTEGRAL?
 PLEASE ALSO SEE OTHER TRACK LIGHTING ON FIXTURE LEGEND
 WHERE FIXTURE WATTAGE IS SHOWN AS N/A. HOW IS THIS
 POSSIBLE WHEN PLANS INDICATE THESE FIXTURES BEING
 INSTALLED?
 PLEASE SEE FIXTURE T1-2 FOR EXAMPLE.
 PLEASE SEE 13-415.2, BASED ON THE MISSING CALCULATIONS,
 THE TOTAL LOOKS LIKE IT WOULD EXCEED THE MAXIMUM
 ALLOWANCES AS SET-FORTH IN THE FLORIDA ENERGY
 CODE/FLORIDA BUILDING CODE.
  
 2) NOTE: PLEASE KNOW A PERMANENT LADDER FOR ACCESS TO
 TRANSFORMER WILL BE REQUIRED. THIS WAS GONE OVER IN
 MEETING WITH OTHER TENANT WHICH IS SHARING THE SPACE
 ABOVE THE ELEVATOR MACHINE ROOM.
 PLEASE VERIFY WITH OTHER TENANT/LANDLORD WHOM IS GOING
 TO HAVE ON PLANS AND INSTALL.
 THIS ITEM CAN BE RED-LINED/NOTED ON PLANS AND DOES NOT
 NEED TO BE ADDRESSED AT THIS TIME UNLESS THE SCOPE OF
 WORK FOR LADDER WILL BE DONE UNDER THIS PERMIT.
 ** NOTED FOR INFORMATION.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  