| 2007-12-04 12:37:47 | ** DENIED 4THREVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| | CALCULATIONS ARE IN NEED OF ADDRESSING. |
| | PLEASE SEE 13-415.2.ABC.1, ONLY LIGHTING WHICH IS |
| | INTEGRAL FOR SIGNAGE IS EXEMPT. |
| | PLEASE PROVIDE INFORMATION ON THESE TYPES OF SIGNS AS |
| | THE LIGHTING T1A AND IT3 IS TRACK LIGHTING. HOW CAN THE |
| | TRACK LIGHTING BE INTEGRAL? |
| | PLEASE ALSO SEE OTHER TRACK LIGHTING ON FIXTURE LEGEND |
| | WHERE FIXTURE WATTAGE IS SHOWN AS N/A. HOW IS THIS |
| | POSSIBLE WHEN PLANS INDICATE THESE FIXTURES BEING |
| | INSTALLED? |
| | PLEASE SEE FIXTURE T1-2 FOR EXAMPLE. |
| | PLEASE SEE 13-415.2, BASED ON THE MISSING CALCULATIONS, |
| | THE TOTAL LOOKS LIKE IT WOULD EXCEED THE MAXIMUM |
| | ALLOWANCES AS SET-FORTH IN THE FLORIDA ENERGY |
| | CODE/FLORIDA BUILDING CODE. |
| | |
| | 2) NOTE: PLEASE KNOW A PERMANENT LADDER FOR ACCESS TO |
| | TRANSFORMER WILL BE REQUIRED. THIS WAS GONE OVER IN |
| | MEETING WITH OTHER TENANT WHICH IS SHARING THE SPACE |
| | ABOVE THE ELEVATOR MACHINE ROOM. |
| | PLEASE VERIFY WITH OTHER TENANT/LANDLORD WHOM IS GOING |
| | TO HAVE ON PLANS AND INSTALL. |
| | THIS ITEM CAN BE RED-LINED/NOTED ON PLANS AND DOES NOT |
| | NEED TO BE ADDRESSED AT THIS TIME UNLESS THE SCOPE OF |
| | WORK FOR LADDER WILL BE DONE UNDER THIS PERMIT. |
| | ** NOTED FOR INFORMATION. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |