Date Text
2007-09-28 21:32:062007-09-28 21:32:06
  
 ** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 PLANS AND REVISIONS TO PLANS WHICH INFORMATION IS ONLY
 NOW BEING SUBMITTED. DUE TO CHANGES AND INFORMATION
 WHICH WAS NOT ON PREVIOUS PLANS OR REVIEW, THESE ITEMS
 COULD NOT HAVE COMMENTED ON AS SOME ITEMS AND
 INFORMATION IS NEW TO PLANS AND/OR DESIGN. THESE ITEMS
 WILL BE CLEARLY NOTED.
  
 **PLEASE SEE THERE IS ONE NEW COMMENT BASED ON
 INFORMATION RECENTLY CONFIRMED FROM THE FLORIDA
 BUILDING COMMISSION.
  
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13
 HAS NOT YET BEEN ACHIEVED.
 PLEASE SEE THE FOLLOWING ITEMS:
 A) PLEASE KNOW AS OF RECENT INFORMATION CONFIRMED WITH
 THE FLORIDA BUILDING COMMISSION, METHOD A ON THE ENERGY
 CALCULATIONS MAY NOT BE USED AS THIS TENANT SPACE IS
 NOT A BUILDING BY THE DEFINITIONS AS SET FORTH IN FBC
 CHAPTER 13 AS WELL AS THE FBC DEFINITIONS. THIS DATE OF
 CONFORMATION WAS 9/24/07.
 PLEASE KNOW AS THE *BUILDING* ALREADY CONTAINS AIR
 CONDITIONING AND AS LONG AS MEETING THE REQUIREMENTS
 FOR MECHANICAL MAKE UP AIR ETC, THE ENERGY CALCULATIONS
 ARE NOT NEEDED FOR ELECTRICAL. PLEASE KNOW HOWEVER THAT
 THE LIGHTING PERFORMANCE CALCULATIONS ARE STILL NEEDED
 AND MAY BE SET UP IN A TABLE FORM USING THE SAME
 INFORMATION ON PLANS AS LONG AT THE LIGHTING LEVELS
 MEET 13-415.2, 13-415.2.C.1, OR 13-415.2.B. PLEASE
 REMEMBER TO SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING.
 PLEASE SEE ANY EXTERIOR LIGHTING WILL BE BASED ON
 13-415.2.ABC.1.3.
 ** PLEASE CALL TO GO OVER.
  
 B) PLEASE SEE THE LIGHTING METHOD OF CONTROLS PER
 13-415.1.ABC.1.1, .1.2 AND .1.3 IS STILL IN QUESTION.
 PLEASE SEE THERE ARE STANDARD SWITCHES SHOWN ON PLANS
 BETWEEN MENS RESTROOM AND KITCHEN AREA. HOW DO THESE
 OPERATE AND FALL INTO THE REQUIREMENTS OF CHAPTER 13?
  
 2) NOTE: PLEASE KNOW THE FIRE SPRINKLER PLANS , SHOP
 DRAWINGS AND SUBMITTALS WILL BE UNDER SEPARATE FIRE
 ALARM AND FIRE SPRINKLER PERMITS. **THIS IS NOTED FOR
 INFORMATION ONLY.
  
 3) NOTE: PLEASE SEE THE SERVICE RISER HAS NOW BEEN
 SUBSTANTIALLY REVISED WHICH NOW INDICATES A EXISTING
 600AMP TENANT MAIN. THIS IS UNCLEAR HOW THIS IS
 POSSIBLE AS STATED ON PREVIOUS REVIEW. THIS SITE WILL
 BE INSPECTED WITHIN THE FIRST WEEK OF OCTOBER AS THE
 PREVIOUS SPACE ONLY HAD ONE TENANT MAIN FOR TWO FLOOR
 AND NOW PLANS FOR THIS SPACE AND NEW TENANT SPACE ABOVE
 BOTH INDICATE ONE EXISTING 400AMP MAIN AND ONE EXISTING
 600AMP MAIN.???
 PLEASE SEE THE RISER MENTIONS THIS IS BEING TAPPED FROM
 AN EXISTING WIRE-WAY WHICH IS FED FROM AN EXISTING
 SERVICE MAIN #2, YET THE LOAD CALCULATIONS WHICH WAS
 REQUESTED ON PREVIOUS REVIEW INDICATE THIS TENANT MAIN
 FOR PANERA BREAD BEING FIGURED FOR *EXISTING SERVICE
 MAIN #3*. ??
 THIS IS TWO DIFFERENT SERVICE MAINS. RISER SHOWS
 *SERVICE MAIN #2* AND LOAD CALCULATIONS SHOW *SERVICE
 MAIN #3*.PLEASE UNDERSTAND AND SEE HOW THIS IS
 COMPLETELY CONFUSING AND UNCLEAR WHERE SERVICE IS BEING
 FED.
 PLEASE SEE THE LOAD SHOWN ON MDP FOR KVA (222.79) IS
 NOT THAT OF THE LOAD BEING SHOWN ON THE LOAD
 CALCULATIONS ON THE SAME SHEET FOR SERVICE MAIN.
 (221.40)
 NO FURTHER REVIEWS ON EITHER BUILD OUT WILL BE DONE
 UNTIL FIELD MEETING AND INSPECTION IS DONE. THIS HAS
 BEEN REQUESTED ON 9/26 WITH CITY PLACE AND WILL NEED TO
 TAKE PLACE AS SOON AS POSSIBLE TO GET SOME CLARITY ON
 ACTUAL INSTALLATION. IT IS SUGGESTED THE ENGINEERING
 FIRM OBTAINS THE ACTUAL INFORMATION ON SERVICE(S) AS
 SHOWN.
 215.5, 230, 220, 240 ETC
 FBC 106.1.2, 106.3.5.1.2
 PLEASE KNOW AS THE SERVICE MAINS, IDENTIFICATION ETC
 CAN NOT YET BE CONFIRMED THE LOAD CALCULATIONS AS
 PREVIOUSLY REQUESTED IN NOTE #9, CAN NOT BE CONFIRMED
 AT THIS TIME.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #13 WHICH
 REQUESTED THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 PROPOSED DISTRIBUTION CENTER. THESE WERE NOW SUBMITTED,
 HOWEVER ONLY THE SHEETS CONTAINS A NOTE WHICH MENTIONS
 THIS IS A UL LISTED SYSTEM. NO SUBMITTALS WHICH ARE
 ACTUAL SPEC/CUT SHEETS FOR EQUIPMENT WERE SUBMITTED
 WHICH SHOW AND INDICATE THE LISTING(S) FROM A NRTL.
 (NATIONALLY RECOGNIZED TESTING LABORATORY). **PLEASE
 SEE THE SHEETS SUBMITTED DO NOT CORRELATE WITH PLANS,
 IN FACT THESE ARE COMPLETELYDIFFERENT FOR OVER
 CURRENT PROTECTION SIZES, ETC.
 * FOR EXAMPLE, PLEASE SEE SPECS/CUT SHEETS SHOW THIS AS
 BEING AN 800AMP MLO (MAIN LUG ONLY) PIECE OF EQUIPMENT,
 YET THE RISER DIAGRAM CLEARLY SHOWS THIS AS BEING AN
 600AMP MCB (MAIN CIRCUIT BREAKER) PANEL-BOARD. THIS
 ALSO SHOWS COMPLETELY DIFFERENT SUB-PANELS WHICH FOR
 INSTANCE A PANEL *M* WHICH IS SHOWN AS 400AMP MLO.
 PANEL *M* ON PLANS/RISER IS 600AMP MCB.
 **PLEASE CORRELATE AND COORDINATE ALL PLANS, RISER,
 DOCUMENTS AND SPECIFICATIONS.
 110.3, 90.7
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #15 WHICH GAVE NOTICE
 TO THE 150KVA TRANSFORMER WHICH IS BEING SHOWN ABOVE
 THE OFFICE WHICH IS STRICTLY PROHIBITED BY THE NEC. THE
 PLANS AS SUBMITTED STILL SHOW THIS ABOVE OFFICE WHICH
 WILL NOT BE ACCEPTED BY THIS AHJ.
 AS THE PLANS INDICATE THIS AS A COMPLETELY CLOSED IN
 SPACE WITH CEILING TILES, GRID LIGHTING ETC THIS IS NOT
 ONLY A LIFE SAFETY ISSUE HOWEVER A FIRE AND PROPERTY
 HAZARD.
 PLEASE SEE THE DISCONNECTING MEANS IS REQUIRED TO BE
 READILY ACCESSIBLE AND THE LOCATION AS SHOWN DOES NOT
 MEET THIS EITHER.
 THESE ITEMS WILL BE REVIEWED FOR NUMEROUS NEC CODES. A
 NEW LOCATION WILL NEED TO BE FOUND.
 FBC 106.3.5.1.2, NEC 450.13B, 450.21, 450.9, 110.26,
 408.7 ETC.
 PLEASE ALSO SEE 240.21 AS THE LENGTH OF CONDUCTORS IS
 OF CONCERN TO MEET THIS SECTION OF THE NEC. THE
 LOCATIONS OF TRANSFORMER AND DISCONNECTING MEANS ON THE
 LOAD SIDE WILL NEED TO BE REVIEWED ONCE ADJUSTMENTS ARE
 MADE TO PLANS.
 THE DETAIL ON A-3.1 AND A-4.4 DOES NOT MATCH WITH PLANS
 AS DETAIL ON 4.4 INDICATES THE BOTTOM OF THE OFFICE
 CEILING FLUSH WITH THE UNDERSIDE OF THE SLAB, WHICH CAN
 NOT BE POSSIBLE WHEN THERE IS A RECESSED LIGHT FIXTURE
 WHICH IS SUPPOSE TO BE LOCATED AT THE SAME LOCATION. IT
 IS RECOMMENDED THAT PHONE CALLS BE MADE AND POSSIBLE
 LOCATIONS BE GONE OVER WITH THIS OFFICE BEFORE
 RESUBMITTING PLANS.
  
 6) NOTE:PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 SEE THIS IS ONLY A NOTICE GIVEN AT THIS TIME. ** PLEASE
 KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE
 AND WILL BE PLACED WITH PREVIOUSLY RETAINED PLANS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH WILL BE
 REQUIRED TO BE REVISED; PLEASE KNOW THAT CODE REVIEW OF
 THESE ITEMS CAN NOT BE DONE AT THIS TIME.
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN ONLY BE BASED
 ON THE PLANS SUBMITTED.
 IT IS RECOMMENDED THAT ALL INFORMATION AS MUCH AS
 POSSIBLE IS GONE OVER BEFORE PLANS ARE RESUBMITTED.
 PLEASE ALSO KNOW THAT ONE COPY OF ELECTRICAL
 PLANS/SPECS SUBMITTED MAY BE RETAINED BY THIS OFFICE
 DUE TO SOME COMMENTS BEING REPEATED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  