| | ** DENIED 3RD REVIEW *** |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON |
| | PLANS AND REVISIONS TO PLANS WHICH INFORMATION IS ONLY |
| | NOW BEING SUBMITTED. DUE TO CHANGES AND INFORMATION |
| | WHICH WAS NOT ON PREVIOUS PLANS OR REVIEW, THESE ITEMS |
| | COULD NOT HAVE COMMENTED ON AS SOME ITEMS AND |
| | INFORMATION IS NEW TO PLANS AND/OR DESIGN. THESE ITEMS |
| | WILL BE CLEARLY NOTED. |
| | |
| | **PLEASE SEE THERE IS ONE NEW COMMENT BASED ON |
| | INFORMATION RECENTLY CONFIRMED FROM THE FLORIDA |
| | BUILDING COMMISSION. |
| | |
| | |
| | 1) NOTE: PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13 |
| | HAS NOT YET BEEN ACHIEVED. |
| | PLEASE SEE THE FOLLOWING ITEMS: |
| | A) PLEASE KNOW AS OF RECENT INFORMATION CONFIRMED WITH |
| | THE FLORIDA BUILDING COMMISSION, METHOD A ON THE ENERGY |
| | CALCULATIONS MAY NOT BE USED AS THIS TENANT SPACE IS |
| | NOT A BUILDING BY THE DEFINITIONS AS SET FORTH IN FBC |
| | CHAPTER 13 AS WELL AS THE FBC DEFINITIONS. THIS DATE OF |
| | CONFORMATION WAS 9/24/07. |
| | PLEASE KNOW AS THE *BUILDING* ALREADY CONTAINS AIR |
| | CONDITIONING AND AS LONG AS MEETING THE REQUIREMENTS |
| | FOR MECHANICAL MAKE UP AIR ETC, THE ENERGY CALCULATIONS |
| | ARE NOT NEEDED FOR ELECTRICAL. PLEASE KNOW HOWEVER THAT |
| | THE LIGHTING PERFORMANCE CALCULATIONS ARE STILL NEEDED |
| | AND MAY BE SET UP IN A TABLE FORM USING THE SAME |
| | INFORMATION ON PLANS AS LONG AT THE LIGHTING LEVELS |
| | MEET 13-415.2, 13-415.2.C.1, OR 13-415.2.B. PLEASE |
| | REMEMBER TO SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. |
| | PLEASE SEE ANY EXTERIOR LIGHTING WILL BE BASED ON |
| | 13-415.2.ABC.1.3. |
| | ** PLEASE CALL TO GO OVER. |
| | |
| | B) PLEASE SEE THE LIGHTING METHOD OF CONTROLS PER |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 IS STILL IN QUESTION. |
| | PLEASE SEE THERE ARE STANDARD SWITCHES SHOWN ON PLANS |
| | BETWEEN MENS RESTROOM AND KITCHEN AREA. HOW DO THESE |
| | OPERATE AND FALL INTO THE REQUIREMENTS OF CHAPTER 13? |
| | |
| | 2) NOTE: PLEASE KNOW THE FIRE SPRINKLER PLANS , SHOP |
| | DRAWINGS AND SUBMITTALS WILL BE UNDER SEPARATE FIRE |
| | ALARM AND FIRE SPRINKLER PERMITS. **THIS IS NOTED FOR |
| | INFORMATION ONLY. |
| | |
| | 3) NOTE: PLEASE SEE THE SERVICE RISER HAS NOW BEEN |
| | SUBSTANTIALLY REVISED WHICH NOW INDICATES A EXISTING |
| | 600AMP TENANT MAIN. THIS IS UNCLEAR HOW THIS IS |
| | POSSIBLE AS STATED ON PREVIOUS REVIEW. THIS SITE WILL |
| | BE INSPECTED WITHIN THE FIRST WEEK OF OCTOBER AS THE |
| | PREVIOUS SPACE ONLY HAD ONE TENANT MAIN FOR TWO FLOOR |
| | AND NOW PLANS FOR THIS SPACE AND NEW TENANT SPACE ABOVE |
| | BOTH INDICATE ONE EXISTING 400AMP MAIN AND ONE EXISTING |
| | 600AMP MAIN.??? |
| | PLEASE SEE THE RISER MENTIONS THIS IS BEING TAPPED FROM |
| | AN EXISTING WIRE-WAY WHICH IS FED FROM AN EXISTING |
| | SERVICE MAIN #2, YET THE LOAD CALCULATIONS WHICH WAS |
| | REQUESTED ON PREVIOUS REVIEW INDICATE THIS TENANT MAIN |
| | FOR PANERA BREAD BEING FIGURED FOR *EXISTING SERVICE |
| | MAIN #3*. ?? |
| | THIS IS TWO DIFFERENT SERVICE MAINS. RISER SHOWS |
| | *SERVICE MAIN #2* AND LOAD CALCULATIONS SHOW *SERVICE |
| | MAIN #3*.PLEASE UNDERSTAND AND SEE HOW THIS IS |
| | COMPLETELY CONFUSING AND UNCLEAR WHERE SERVICE IS BEING |
| | FED. |
| | PLEASE SEE THE LOAD SHOWN ON MDP FOR KVA (222.79) IS |
| | NOT THAT OF THE LOAD BEING SHOWN ON THE LOAD |
| | CALCULATIONS ON THE SAME SHEET FOR SERVICE MAIN. |
| | (221.40) |
| | NO FURTHER REVIEWS ON EITHER BUILD OUT WILL BE DONE |
| | UNTIL FIELD MEETING AND INSPECTION IS DONE. THIS HAS |
| | BEEN REQUESTED ON 9/26 WITH CITY PLACE AND WILL NEED TO |
| | TAKE PLACE AS SOON AS POSSIBLE TO GET SOME CLARITY ON |
| | ACTUAL INSTALLATION. IT IS SUGGESTED THE ENGINEERING |
| | FIRM OBTAINS THE ACTUAL INFORMATION ON SERVICE(S) AS |
| | SHOWN. |
| | 215.5, 230, 220, 240 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | PLEASE KNOW AS THE SERVICE MAINS, IDENTIFICATION ETC |
| | CAN NOT YET BE CONFIRMED THE LOAD CALCULATIONS AS |
| | PREVIOUSLY REQUESTED IN NOTE #9, CAN NOT BE CONFIRMED |
| | AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #13 WHICH |
| | REQUESTED THE MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | PROPOSED DISTRIBUTION CENTER. THESE WERE NOW SUBMITTED, |
| | HOWEVER ONLY THE SHEETS CONTAINS A NOTE WHICH MENTIONS |
| | THIS IS A UL LISTED SYSTEM. NO SUBMITTALS WHICH ARE |
| | ACTUAL SPEC/CUT SHEETS FOR EQUIPMENT WERE SUBMITTED |
| | WHICH SHOW AND INDICATE THE LISTING(S) FROM A NRTL. |
| | (NATIONALLY RECOGNIZED TESTING LABORATORY). **PLEASE |
| | SEE THE SHEETS SUBMITTED DO NOT CORRELATE WITH PLANS, |
| | IN FACT THESE ARE COMPLETELYDIFFERENT FOR OVER |
| | CURRENT PROTECTION SIZES, ETC. |
| | * FOR EXAMPLE, PLEASE SEE SPECS/CUT SHEETS SHOW THIS AS |
| | BEING AN 800AMP MLO (MAIN LUG ONLY) PIECE OF EQUIPMENT, |
| | YET THE RISER DIAGRAM CLEARLY SHOWS THIS AS BEING AN |
| | 600AMP MCB (MAIN CIRCUIT BREAKER) PANEL-BOARD. THIS |
| | ALSO SHOWS COMPLETELY DIFFERENT SUB-PANELS WHICH FOR |
| | INSTANCE A PANEL *M* WHICH IS SHOWN AS 400AMP MLO. |
| | PANEL *M* ON PLANS/RISER IS 600AMP MCB. |
| | **PLEASE CORRELATE AND COORDINATE ALL PLANS, RISER, |
| | DOCUMENTS AND SPECIFICATIONS. |
| | 110.3, 90.7 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE #15 WHICH GAVE NOTICE |
| | TO THE 150KVA TRANSFORMER WHICH IS BEING SHOWN ABOVE |
| | THE OFFICE WHICH IS STRICTLY PROHIBITED BY THE NEC. THE |
| | PLANS AS SUBMITTED STILL SHOW THIS ABOVE OFFICE WHICH |
| | WILL NOT BE ACCEPTED BY THIS AHJ. |
| | AS THE PLANS INDICATE THIS AS A COMPLETELY CLOSED IN |
| | SPACE WITH CEILING TILES, GRID LIGHTING ETC THIS IS NOT |
| | ONLY A LIFE SAFETY ISSUE HOWEVER A FIRE AND PROPERTY |
| | HAZARD. |
| | PLEASE SEE THE DISCONNECTING MEANS IS REQUIRED TO BE |
| | READILY ACCESSIBLE AND THE LOCATION AS SHOWN DOES NOT |
| | MEET THIS EITHER. |
| | THESE ITEMS WILL BE REVIEWED FOR NUMEROUS NEC CODES. A |
| | NEW LOCATION WILL NEED TO BE FOUND. |
| | FBC 106.3.5.1.2, NEC 450.13B, 450.21, 450.9, 110.26, |
| | 408.7 ETC. |
| | PLEASE ALSO SEE 240.21 AS THE LENGTH OF CONDUCTORS IS |
| | OF CONCERN TO MEET THIS SECTION OF THE NEC. THE |
| | LOCATIONS OF TRANSFORMER AND DISCONNECTING MEANS ON THE |
| | LOAD SIDE WILL NEED TO BE REVIEWED ONCE ADJUSTMENTS ARE |
| | MADE TO PLANS. |
| | THE DETAIL ON A-3.1 AND A-4.4 DOES NOT MATCH WITH PLANS |
| | AS DETAIL ON 4.4 INDICATES THE BOTTOM OF THE OFFICE |
| | CEILING FLUSH WITH THE UNDERSIDE OF THE SLAB, WHICH CAN |
| | NOT BE POSSIBLE WHEN THERE IS A RECESSED LIGHT FIXTURE |
| | WHICH IS SUPPOSE TO BE LOCATED AT THE SAME LOCATION. IT |
| | IS RECOMMENDED THAT PHONE CALLS BE MADE AND POSSIBLE |
| | LOCATIONS BE GONE OVER WITH THIS OFFICE BEFORE |
| | RESUBMITTING PLANS. |
| | |
| | 6) NOTE:PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE |
| | SEE THIS IS ONLY A NOTICE GIVEN AT THIS TIME. ** PLEASE |
| | KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE |
| | AND WILL BE PLACED WITH PREVIOUSLY RETAINED PLANS. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH WILL BE |
| | REQUIRED TO BE REVISED; PLEASE KNOW THAT CODE REVIEW OF |
| | THESE ITEMS CAN NOT BE DONE AT THIS TIME. |
| | COMPLETE REVIEW FOR CODE COMPLIANCE CAN ONLY BE BASED |
| | ON THE PLANS SUBMITTED. |
| | IT IS RECOMMENDED THAT ALL INFORMATION AS MUCH AS |
| | POSSIBLE IS GONE OVER BEFORE PLANS ARE RESUBMITTED. |
| | PLEASE ALSO KNOW THAT ONE COPY OF ELECTRICAL |
| | PLANS/SPECS SUBMITTED MAY BE RETAINED BY THIS OFFICE |
| | DUE TO SOME COMMENTS BEING REPEATED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |