Plan Review Notes
Plan Review Notes For Permit 07030523
Permit Number 07030523
Review Stop P
Sequence Number 2
Notes
Date Text
2007-07-14 16:49:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 *******FROM PREVIOUS REVIEW*******
  
 1. OK
 2. OK
  
 3. SHT G-ADA SHOW THE FOLLOWING ACCESSIBILITY
 REQUIREMENTS:
 A. 11-4.16.5 FLUSH CONTROLS __W/C
 B. 11-4.19.5 FAUCETS __LAVS
 ****RESPONSE NOTED, BUT THE CUT SHEETS WERE NOT
 LOCATED, THE REQUIREMENT FOR THE FLUSH CONTROLS IS THAT
 THE CONTROLS SHALL BE ON THE WIDE SIDE OF THE TOILET.
 THE REQUIREMENT FOR THE FAUCETS IS THAT THEY BE LEVER
 TYPE, PUSH TYPE, ELECTRONIC ETC. THESE REQUIREMENTS
 SHALL BE SHOWN ON THE PLANS AS CUT SHEETS CAN BE LOST
 ON THE JOB.
  
 4. SHT EQ-2.1, THE 2 PAGE "WORKSHEETS" FROM DBPR HOTEL
 AND RESTURANT DIVISION PLAN REVIEW SHALL BE ATTACHED TO
 EACH SHEET STAMPED BY THE FOOD SERVICE ON EACH SET OF
 PLANS. SECTION 102.2.1.
 ****RESPONSE NOTED, BUT WORKSHEETS HAVE NOT BEEN
 ATTACHED TO STAMPED SHEET. -MINIMUM TWO STAMPED
 SHEETS REQUIRED FOR PLAN REVIEW. (ONLY ONE SHEET
 STAMPED BY DBPR FOUND)
  
 5. ALL MEP SHEETS. THE ORIGINAL SIGNATURE OF THE
 ENGINEER IS REQUIRED WHEN THE SEAL IS AFFIXED. THE
 STAMPED SIGNATURE IS NOT APPROVED. FAC
 61G15-23.002(1)(2) & FS 471.025.
 ****RESPONSE NOTED, BUT THE SIGNATURE IS SO MUCH
 DIFFERENT THAT A SIGNED, SEALED, DATED, NOTORIZED
 LETTER SHALL BE SUBMITTED INDICATING THE LEGAL
 SIGNATURE OF THE PROFESSIONAL ENGINEER AS WELL AS A
 PICTURE I.D. WITH THE ENGINEERS SIGNATURE FOR OUR
 FILES.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT P-3.2 THE HOT & COLD WATER SUPPLIES TO FIXTURE
 13A ARE REVERSED. HOT IS SHOWN ON THE RIGHT AND COLD IS
 SHOWN ON THE LEFT. PLEASE CORRECT. SECTION 607.4.--
 ****ALL OF THE COMMENTS HAVE BEEN ADDRESSED EXCEPT THE
 ABOVE PORTION.
  
 15. SHT P-3.2 THE FOLLOWING GAS REQUIREMENTS SHALL BE
 SUBMITTED:
  
 A. OK
  
 B. TYPE OF GAS, (LP OR NATURAL).
 ****RESPONSE NOTED, BUT INFORMATION IS REQUIRED ON THE
 PLANS.
  
 C. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES. MATERIAL IS INDICATED AS
 EITHER THREADED OR WELDED ON SHT P-3.1. IF THE PIPING
 WILL BE WELDED, THE WELDING CERTIFICATION AND WELDING
 PROCEDURE WILL BE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
 ****RESPONSE NOTED, BUT NOT ADDRESSED. THE NOTE STILL
 INDICATES IT CAN BE THREADED OR WELDED PIPE. UNTILL THE
 PIPE TYPE IS IDENTIFIED AS EITHER SCREW PIPE OR WELD
 PIPE THE PERMIT CAN NOT BE ISSUED.
  
 D. OK
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE
 DOUBLE RACK OVEN IS NOT CLEAR AND LEGIBLE ON SHEET #3
 AND UL LISTING DOES NOT INDICATE WHAT IT WAS LISTED
 FOR. PLEASE SUBMIT A COPY OF THE UL LISTING FOR THIS
 PRODUCT.
  
 G. N/A
 H. N/A
 16. OK
 17. OK
  
 18. SHT P-4.1 THE 10 GALLON HOT WATER STORAGE TANK
 REQUIRES A RELIEF VALVE PER SECTION 504.4 AND SHALL BE
 INSTALLED PER 504.4.1. THE RELIEF LINE SHALL DISCHARGE
 PER SECTION 504.6.1. SUBMIT A DETAIL INDICATING
 COMPLIANCE. IF THE STORAGE TANK IS INSTALLED ABOVE THE
 GROUND FLOOR SPACE, IT SHALL BE INSTALLED IN A PAN AND
 SHALL HAVE A PAN DRAIN LINE. SECTIONS 504.7, 504.7.1 &
 504.7.2. PLEASE CLARIFY AND SUBMIT DETAILS IF
 REQUIRED.
 ****RESPONSE NOTED, BUT THE PAN DRAIN CAN NOT DRAIN
 INTO A FLOOR DRAIN, FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. A FLOOR SINK OR A HUB DRAIN
 IS REQUIRED PER SECTIONS 802.3 & 802.3.2.
  
 19. SHT P-4.1 THE WATER HEATER SCHEMATIC SHALL SHOW ALL
 PIPE SIZES FOR THE WATER LINES AND THE GAS LINES.--
 SCHEMATIC SHOWS 2" GAS HEADER, THIS SHALL REFLECT THE
 GAS RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE PIPEING SHOWN ON THE WATER
 HEATER SCHEMATIC IS NOT SHOWN ON SHEETS P2.4 OR P3.2.
 ALSO THE GAS HEADER ON THE RISER DIAGRAM DOES NOT
 REFLECT THE WATER HEATER SCHEMATIC. THE SCHEMATIC SHOWS
 1-1/2" PIPE BEING PIPED IN FROM THE LEFT OF THE HEATERS
 AND THE SCHEMATIC SHOWS THE GAS PIPING IN FROM THE
 RIGHT SIDE AND IS SHOWN AS 2" PIPE. PLEASE CORRELATE
 RISER AND SCHEMATIC AND SHOW ALL PIPE SIZES.
  
 20. OK
  
 21. THE GREASE LINE SHALL DRAIN TO A GREASE
 INTERCEPTOR. THE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY
 COMPO AT (561) 822-2272 OR CALVIN WILLIAMS AT (561)
 822-2284. THEIR FAX NUMBER IS (561) 822-2287 OR THEY
 CAN BE REACHED BY E-MAIL [email protected] OR
 [email protected]. CITY CODE 90-124(7). ****RESPONSE
 NOTED, WAITING FOR WRITTEN NOTICE FROM R. COMPO.
  
 ********NEW COMMENT********
  
 1B. ALL SHEETS SHALL BE STAMPED FOR APPROVAL BY CITY
 PLACE MANAGEMENT PRIOR TO RESUBMITTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  