| 2007-07-16 13:03:32 | ---------------DENIED---------------- |
| | |
| | FBC 2004 W/ 2006 REVISIONS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWIN COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | COMMENTS FROM THE PREVIOUS REVIEW, WHICH IS DATED |
| | 4/16/07, FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. THE NOA PROVIDED FOR THE PRE-ENGINEERED A/C STAND |
| | DOES NOT MATCH THE STAND OR INSTALLATION INSTRUCTIONS |
| | SHOWN ON MPE-1.1. PLEASE COORDINATE PLANS WITH THE |
| | COMPONENTS TO BE USED. |
| | |
| | 2. OK |
| | |
| | 3. THE 10X10 EXHAUST DUCT; IS THERE A FIRE DAMPER WHERE |
| | THE DUCT PENETRATES THE ACCESS CORRIDOR WALL? PLEASE |
| | SEE FBC,M 607.5 AND 607.8. |
| | |
| | 4. OK |
| | |
| | 5. WIND LOAD CALCULATIONS WERE PROVIDED. HOWEVER, NO |
| | ATTACHMENT DETAIL FOR CURB TO STRUCTURE OR EQUIPMENT TO |
| | CURB COULD BE LOCATED IN PLANS. ALSO. PLEASE SHOW HOW |
| | SPRING ISOLATION CURB RAILS WILL WORK IN CONJUNCTION |
| | WITH WIND RESISTANT ATTACHMENTS. FBC,M 301.10 AND |
| | 301.13. |
| | |
| | 6. OK |
| | |
| | 7. EF-3 IS STILL SHOWN ON EXHAUST FAN SCHEDULE. WHERE |
| | IS EF-3 LOCATED? IF IT IS NOT BEING USED, PLEASE REMOVE |
| | FROM SCHEDULE. FBC 106.1.1 |
| | |
| | 8. PG M-4.1 KITCHEN HOOD EXHAUST DUCTWORK NOTE 1.0 |
| | STATES "18 GAUGE STAINLESS STEEL" BUT THE DETAIL ON |
| | M-4.2 INDICATES "22 GAUGE G90 GALVANIZED." WHICH IS |
| | CORRECT? ALSO, NOTE 4.0 STATES THAT THE DUCT IS NOT TO |
| | PENETRATE FIRE RATED ASSEMBLIES. WILL THIS DDUCT NEED |
| | TO ENTER A RATED SHAFT TO PASS THROUGH THE 2ND FLOOR TO |
| | THE ROOF? NOTE: SHAFT ENCLOSURES SHALL BE CLOSED AT THE |
| | BOTTOM PER FBC 707.11. |
| | |
| | 9 THROUGH 11: OK |
| | |