Plan Review Notes
Plan Review Notes For Permit 07030523
Permit Number 07030523
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-27 19:04:35 
  
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARESEVERAL COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE
 SEE THERE ARE SOME NEW COMMENTS BASED ON PLANS AND
 REVISIONS TO PLANS WHICH INFORMATION IS ONLY NOW BEING
 SUBMITTED. MOST OF THE COMMENTS ARE FROM THE PREVIOUS
 REVIEW AND WILL BE INDICATED AS SUCH.
  
  
 1) NOTE: PLEASE SEE THE PREVIOUS NOTES FROM MULTIPLE
 REVIEWERS WHICH INDICATED *IMPORTANT*.ONE OF THESE
 NOTES WAS TO *COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS* AND ONLY INSERT THE NEW REVISED SHEETS INTO
 THE COMPLETED SETS FOR REVIEW AND STAMPING. THIS WAS
 NOT DONE AND ALL OF OLD SHEETS WERE LEFT IN SETS. THESE
 WERE NOT MARKED/LABELED AS VOID OR ANY INDICATION THEY
 WERE NOT CURRENT. PLANS WERE REVIEWED BASED ON REVISION
 DATES. ANY SHEETS WHICH WERE NOT REVISED AND LEFT FROM
 PREVIOUS REVIEW MAY HAVE COMMENTS.
 PLEASE KNOW THIS WILL NOT BE DONE BY THIS OFFICE AND
 OLD PLANS/SHEETS MUST BE REMOVED.
 CALLED ELITE EXPEDITORS AS LISTED ON RE-SUB COVER SHEET
 FOR CONTACT AND INFORMED JENNIFER MELANSON THIS NEEDED
 TO BE DONE. AS PLANS ARE COMING BACK TO ADDRESS CODE
 COMMENTS THIS WILL BE REQUIRED TO BE DONE BEFORE
 RE-SUBMITTAL. IF PLANS ARE SUBMITTED WITHOUT THIS DONE,
 PROCESSING FOR REVIEW WILL NOT BE DONE AND PLANS WILL
 BE PLACED OUT-FRONT FOR PICK UP.
 ** PLEASE ALSO KNOW THAT ONLY TWO COMPLETE SETS ARE
 NEEDED FOR THE SCOPE OF WORK. PLEASE KNOW THIS OFFICE
 WILL STAMP UP TO THREE, HOWEVER PLEASE SEE 12 SETS OF
 ENERGY CALCULATIONS WERE SUBMITTED AND ONLY THREE WILL
 BE STAMPED ONCE CODE COMPLIANT.
 FBC 106.3.1
  
 2) NOTE: PLEASE SEE PLANS MUST CONTAIN THE
 PRE-APPROVED/REVIEWED STAMP AND SIGNATURE ON ALL PLANS
 FROM CITY PLACE MANAGEMENT/LANDLORD BEFORE THEY ARE
 STAMPED BY THE CITY OF WEST PALM BEACH FOR PERMIT
 ISSUANCE. THE PREVIOUS PLANS WERE STAMPED HOWEVER THE
 NEW SHEETS WERE NOT.
 FBC 106.1
  
 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL
 SHEETS ARE STILL MISSING THE PRINTED LICENSE NUMBER FOR
 THE ARCHITECT OF RECORD.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THE ARCHITECTURAL SHEETS ARE MISSING THE
 PRINTED NAME OF THE ARCHITECT ON TITLE BLOCKS AS
 REQUIRED PER FAC61G1-16.004.
 * THIS IS REQUIRED WHETHER OR COMMENT IS MADE BY OTHER
 TRADE(S).
  
 4) NOTE:PLEASE SEE THE PROJECT WAS SUBMITTED BACK
 WITH THE SAME VALUE ON PERMIT APPLICATION AND NO
 CHANGES WERE MADE. THE APPLIED VALUE MUST INCLUDE ALL
 LABOR, MATERIALS, PERMANENTLY INSTALLED EQUIPMENT,
 DESIGN/ENGINEERING/ARCHITECTURAL FEES ETC EVEN IF ANY
 OF THESE ITEMS ARE OWNER SUPPLIED. PLEASE KNOW A VALUE
 WILL BE ASSESSED USING ADOPTED GUIDES PER THE FBC IF AN
 APPROPRIATE VALUE IS NOT ADJUSTED ON APPLICATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF
 MATERIALS, EQUIPMENT, ETC IS OWNER SUPPLIED AS STATED
 ON PLANS.
 VALUE IS LOW AT THIS TIME. PLEASE ADJUST.
 PLEASE KNOW A VALUE MAY BE ADJUSTED BY THIS OFFICE
 USING ADOPTED DOCUMENTS INTO THE FBC.
 FBC 108.3
  
 5) NOTE: PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13
 HAS NOT YET BEEN ACHIEVED. PLEASE SEE EH FOLLOWING
 ITEMS:
 A) PLEASE SEE THE ENERGY CALCULATIONS ARE NOT CORRECT.
  
 B)PLEASE SEE THE NUMBER OF LUMINAIRES NEED TO
 COORDINATE WITH PLANS.
 C) PLEASE SEE THE WATTAGE OF LUMINAIRES NEED TO
 CORRELATE WITH PLANS.
 D) PLEASE SEE THE METHOD OF CONTROLS NEEDS TO CORRELATE
 WITH PLANS.
 E) PLEASE SEE THE OWNER AGENT IS NOT SIGNED ON SHEET 2
 AS REQUIRED.
 F) PLEASE SEE NO TIME OF DAY SCHEDULING WAS SUBMITTED
 AS PREVIOUSLY REQUESTED.
 F) PLEASE SEE NO LOCATION FOR ALL OVER RIDE DEVICES
 WERE SHOWN ON PLANS. THE ONLYOVER RIDE DEVICE AS
 NOTED IS LOCATED AT THE LIGHTING CONTROL PANEL WHICH
 DOES NOT MEET THE CODE.
 H) PLEASE SEE ALL SEPARATE SPACES CONTAINING FLOOR TO
 CEILING HEIGHT PARTITIONS REQUIRES DEVICES: NONE WERE
 SHOWN ON PLANS.
 I) PLEASE SEE MISSING SEPARATE CONTROLS FOR
 DISPLAY/ACCENT LIGHTING.
 J) PLEASE SEE NOT EXTERIOR LIGHTING WAS FIGURED INTO
 THE CALCULATIONS. (PLEASE SEE NOTE #8)
 **PLEASE KNOW AS THIS WAS THE FIRST TIME ANY
 DESIGN/INFORMATION FOR CHAPTER 13 WAS SUBMITTED PLEASE
 ADDRESS THESE COMMENTS AND SEE THE PREVIOUS NOTE BELOW
 FOR ALL CODE SECTIONS AND SEE ALL OF CHAPTER 13 AS
 THERE ARE TOO MANY TO BE STATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE 2004 FBC W/ 2006 REVISIONS FOR CHAPTER
 13. AT THIS TIME THERE ARE SEVERAL ITEMS MISSING FOR
 REVIEW.
 PLEASE SEE NO SCHEDULING OF SYSTEM WAS SUBMITTED.
 PLEASE SEE NO INFORMATION ON A SYSTEM WAS SUBMITTED.
 PLEASE SEE NO OVER RIDE DEVICES AT THE POINTS OF
 EGRESS/INGRESS INTO SPACE FROM ENTRANCE WIN WHICH THE
 OCCUPANT CAN SEE THE LIGHTING WHICH IS BEING
 CONTROLLED.
 PLEASE SEE NO TIMES ON ANY OVER RIDE DEVICES AND TYPES
 OF DEVICES.
 PLEASE SEE MISSING ENERGY CALCULATIONS.
 PLEASE SEE MISSING LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SEE MISSING CERTIFICATIONS PER DESIGNER(S) OF
 RECORD.
 PLEASE SEE REQUIRED CALCULATION METHODS FOR TRACK
 LIGHTING. 13-415.2.ABC.1.2
  
 PLEASE SEE 13-103.1, 13-415.1ABC.1, 13-415.1.ABC.1.1,
 .1.2 AND .1.3, 13-415.1.AB.1.1, 13-415.1.A, .B AND .C,
 13-415.2 AND TABLES UNDER THE NEW 2006 REVISIONS. ETC.
  
 6) NOTE: PLEASE SEE THE CD LEVELS SHOWN ON PLANS FOR
 MINIMUM ADA COMPLIANCE DOES NOT MEET THE FBC AS
 PREVIOUSLY STATED IN NOTES.
 PLEASE SEE THE FBC WHICH CONTAINS MORE RESTRICTIVE
 REQUIREMENTS THANNFPA.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE
 THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA
 REQUIRED AREAS. DEVICES ARE BEING SHOWN ON LEGEND ONLY.
 PLEASE INCLUDE ON LAYOUT OF PLANS AND DEVICES. PLEASE
 KNOW EVEN THOUGH FIRE SPRINKLER AND FIRE ALARM WORK
 WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT THE BASE
 FIRE ALARM DEVICES ALONG WITH FIRE PROTECTION WILL BE
 REQUIRED IN BASE PLANS. THIS WILL BE NOTED BY THE FIRE
 AND BUILDING REVIEWER(S) ALSO.
  
 7) NOTE:PLEASE SEE THE RESPONSE MENTIONS THE SIGN
 CIRCUIT WAS REMOVED FROM PANEL? WHY WAS THIS DONE?
 PLEASE SEE THE MINIMUM OF ONE CIRCUIT IS REQUIRED AT
 THE ENTRANCE LOCATION WHETHER OR NOT A SIGN INSTALLED
 AND IS TO BE FROM THE TENANT SPACE PANEL. THE EXISTING
 SIGNS LOCATED AT CITY PLACE ARE FROM EACH TENANT AND
 ONLY THE COMMON AREA SIGNS FOR CITY PLACE NOT THE
 TENANT ARE FROM THE HOUSE PANEL. 600.5
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SIGN CIRCUIT ON PLANS AND PANEL
 SCHEDULE PER 600.5.
  
 8) NOTE: PLEASE SEE ANY EXTERIOR LIGHTING FOR COMMON
 AREA WALLS ETC ARE FROM CITY PLACE HOUSE. PLEASE SEE
 THE EXTERIOR LIGHTING SHOWN ON THESE PLANS IF UNDER THE
 LANDLORDS PANEL AND AREA WILL BE REQUIRED UNDER
 SEPARATE PERMITS AND PLANS. PLEASE OBTAIN COORDINATION
 FROM THE CITY PLACE MANAGEMENT AND LANDLORD FOR THIS.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO THE ENERGY
 CALCULATIONS AS THERE WERE NO EXTERIOR LIGHTING FIGURED
 INTO THE CALCULATIONS.
  
 9) NOTE: PLEASE SEE PLANS NOW MENTIONS AND SHOWS AN
 EXISTING 400AMP SERVICE WAS ALREADY PRESENT FOR THIS
 SPACE, HOWEVER THE EXISTING 400AMP SERVICE WAS FOR A
 MUCH LARGER SPACE WHICH IS NOW SPLIT UP TO MORE THAN
 ONE TENANT. PLANS WHICH HAVE ALREADY BEEN SUBMITTED BY
 THE NEW TENANT FOR UPSTAIRS HAS ALREADY INDICATED THE
 *EXISTING 400AMP SERVICE* IS BEING USED FOR THEIR
 SPACE? PLEASE KNOW THE COORDINATION BETWEEN THE TWO
 TENANTS AND THE LANDLORD IS IMPERATIVE FOR THIS. THE
 LOAD CALCULATIONS FOR THE EXISTING 1200AMP SERVICE FOR
 EACH OF THE NEW TENANTS INCLUDING THE LOAD FOR EACH OF
 THE NEW TENANTS WILL BE REQUIRED ON EACH SET OF RECORD
 PLANS.
 THIS INFORMATION IS A MUST AND A COMPLETE BREAKDOWN OF
 THE EXISTING AND NEW WILL BE NEEDED. AN ONSITE MEETING
 MAY ALSO BE ARRANGED TO GO OVER THIS.
 215.5,230,220,240, ETC NEC. THERE ARE TOO MANY SECTIONS
 OF CODE WHICH APPLY SPECIFICALLY TO THIS.
 FBC 106.3.5.1.2
  
 ** PREVIOUS REVIEW NOTE** PLEASE VERIFY SERVICE AS
 SHOWN AS THE RISER MENTIONS THE METER IS BEING DONE BY
 THE LANDLORD?? THIS SCOPE OF WORK HAS NOT BEEN DONE/OR
 APPLIED FOR. PLEASE SEE THE RISER SEEMS TO SHOW THE NEW
 TENANT MAIN AS NEMA 3R WHICH LENDS TO THIS BEING
 LOCATED OUTSIDE? PLEASE KNOW THAT THIS BUILDING
 CONTAINS AN INDOOR ELECTRICAL ROOM WHERE ALL TENANT
 MAIN DISCONNECTS ARE LOCATED. PLEASE PROVIDE A LAYOUT
 FOR LOCATIONS AND LOADS OF THE NEW ON THE EXISTING MAIN
 WITH THE EXISTING LOADS.
 PLEASE KNOW AT THIS TIME THERE ARE ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SEE NEC 220 IN THE 2005 NEC AS THE CALCULATIONS
 AND LOAD SUMMARY FOR THIS SERVICE AND LOADS WITH
 EXISTING SERVICE NEED TO BE SHOWN PER NEW CODE. PLEASE
 SEE PLANS WHICH CONTAIN CODE SECTIONS FROM THE PREVIOUS
 NEC.
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE SEE RESPONSE MENTIONS TO SEE REVISED
 RISER AND THIS WAS ADDRESSED, HOWEVER THE RISER
 INDICATES *IF*?? PLEASE SEE THIS METER IS INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT AND A FLOATING
 NEUTRAL KIT IS REQUIRED. PERHAPS THIS CAN BE VERIFIED
 BY THE DESIGNER/DESIGN TEAM OF RECORD WHEN SITE VISIT
 IS DONE FOR NOTE #9 ABOVE.
 250.6,250.24.
 FBC 106.3.5.1.2
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE INDICATE A *FLOATING NEUTRAL* IN METER AS
 REQUIRED PER 250.6 AND 250.24. THIS WILL ALLEVIATE ANY
 OBJECTIONABLE CURRENTS.
  
 11) NOTE:PLEASE SEE RESPONSE MENTIONS THE SECTIONS OF
 THE NEC WAS ADDED TO PLANS WHICH IS CORRECT HOWEVER
 PLEASE SEE THE CIRCUITING ON PANEL LP TO BE EXACT STILL
 NOTES THE EM/EXT LTS ON A DEDICATED CIRCUIT? THIS DOES
 NOT CORRELATE WITH THE CIRCUITING AS SHOWN ON PLANS.
 PLEASE ADJUST.
 408.4, FBC 106.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY LIGHTING
 AND EXIT LIGHTING.THE PLAN MENTIONS 701, 701.11F
 WHICH IS NOT APPLICABLE.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE RESPONSE MENTIONS THE AIC RATINGS
 ARE STATED ON ALL EQUIPMENT HOWEVER THE RATING OF THE
 NEW FUSED MAIN COULD NOT BE LOCATED ON PLANS. PLEASE
 ALSO VERIFY THE RATINGS WHICH ARE SHOWN ON ALL PANELS
 FOR THE PANEL AND BRANCH BREAKERS. PLEASE SEE THE
 RATINGS FOR THE BRANCH BREAKERS AS STATED SEEM HIGH,
 HOWEVER ARE OK AND DO NOT VIOLATE ANY CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE ALL EQUIPMENT CONTAINS THE AIC RATINGS
 AS REQUIRED PER 110.9. PLEASE INDICATE FOR THE NEW MAIN
 ON RISER AS SHOWN.
  
 13) NOTE: PLEASE SUBMIT THE MANUFACTURES SPEC/CUT
 SHEETS FOR THIS EQUIPMENT. PLEASE SEE THE NOTE FOR
 CHAPTER 13 AS THE RISER AND EQUIPMENT IN RISER MAY
 CHANGE.
 THE NOTE ON PLANS MENTIONS THE LISTING AND OTHER
 INFORMATION ABOUT CONTACT INFORMATION ETC HOWEVER THE
 REQUEST WAS TO SUBMIT THE DOCUMENTS FOR THIS EQUIPMENT
 AT THIS TIME FOR REVIEW.
 110.3,90.7.
 FBC 106.1.2, 106.3.5.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURES SPEC/CUT SHEETS ON THE
 PROPOSED POWER DISTRIBUTION CENTER FOR REVIEW. PLEASE
 BE SURE LISTINGS FROM A NRTL( NATIONALLY RECOGNIZED
 TESTING LABORATORY) IS SHOWN.
 110.3, 90.7.
 FBC 106.1.2.
  
 14) NOTE:THIS NOTE REMAINS AS THE COLOR CODING ADDED
 TO THE NOTES WAS NOT AS STATED ON PREVIOUS REVIEW NOTE>
 THIS IS TO BE BROWN (A) ?PURPLE (B) AND YELLOW (C).
 PLEASE SEE THIS MUST HAVE BEEN A MISPRINT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE COLOR CODING SHALL BE AS FOLLOWS.
 277/480V SYSTEMS, BROWN, PURPLE, YELLOW.
 PLEASE SEE THAT THE NEC HAS *ORANGE* DESIGNATED FOR
 MARKING OF A *HIGH-LEG* IN AN OPEN DELTA SYSTEM WHICH
 IS NOT WHAT IS BEING INSTALLED.
 PLEASE KNOW AS PER LOCAL JURISDICTIONS AND LOCAL WIRING
 AT THE LOCATION OF SAID PROJECT THE COLOR CODING OF THE
 EXISTING SYSTEMS IN THIS BUILDING IS AS NOTED. 90.4
  
 15) NOTE: PLEASE PROVIDE MOTE INFORMATION ON THE
 LOCATION OF THIS VERY LARGE TRANSFORMER. PLEASE SEE THE
 LOCATION DOES NOT SEEM TO GIVE THE WORKING CLEARANCES
 AS REQUIRED PER THE NEC. PLEASE SUBMIT ELEVATION
 DETAILS FOR THIS LOCATION AS THE UNIT SHALL NOT BE
 ENCLOSED, CLOSE TO IGNITABLE MATERIALS, AND MUST MEET
 THE CLEAR SPACE ETC. PLEASE ALSO PROVIDE A STRUCTURAL
 SUPPORT DETAIL FOR MOUNTING OF SAID UNIT. THESE ITEMS
 WILL BE REVIEWED FOR NUMEROUS NEC CODES INCLUDING
 STRUCTURAL INTEGRITY.
 FBC 106.3.5.1.2, NEC 450.13B, 450.21, 450.9, 110.26,
 408.7 ETC.
 PLEASE ALSO SEE 240.21 AS THE LENGTH OF CONDUCTORS IS
 OF CONCERN TO MEET THIS SECTION OF THE NEC. AT THIS
 TIME THE MCB IN THE MDP APPEARS TO BE TOO FAR AWAY
 BASED ON THE LENGTH OF CONDUCTORS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE TRANSFORMER WHICH IS BEING SHOWN ABOVE
 OFFICE IS NOT PERMITTED AT THIS LOCATION PER 450.13B
 AND 450.21B.
 PLEASE PROVIDE MORE DETAILS AND INFORMATION ON TYPE OF
 TRANSFORMER. THE LOCATION IS NOT PERMITTED BASED ON
 PLANS SUBMITTED.
 110.3, 90.7
 FBC 106.3.5.1.2
  
 16) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 SEE THIS IS ONLY A NOTICE GIVEN AT THIS TIME. ** PLEASE
 KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE
 AND WILL BE PLACED WITH PREVIOUSLY RETAINED PLANS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN OR
 SUBMITTED FOR REVIEW, THE COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN ONLY BE BASED ON THE PLANS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-27 16:47:22PLANS WERE REMOVED FROM INCOMING AND WILL BE RETURNED
 ONCE ELECTRICAL REVIEW IS DONE.