2007-08-02 10:15:49PANERA BREAD 2ND REV
 BUILDING PLAN REVIEW
 PERMIT: 07030523
 ADD: 700 S ROSEMARY# 142
 CONT: PEMBERTON BUILDERS
 TEL: (561)718-8624
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 3)BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTIONMATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 4-5) COMPLIED.
  
 6) 2ND REQUEST, 1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M)
 OF GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE
 MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 THE PRODUCT APPROVAL SIGNED OFF BY ARCHITECT LOUISE K
 CRAVER APPARENTLY MISSED THIS IS A NON-RATED ASSEMBLY.
  
 7) 2ND REQUEST,7)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING,
 ROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 ,
 NOT THE (12) TWELVE COPIES SUBMITTED, OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:A)
 STOREFRONT WINDOWS: YKK SERIES YHS-50 FINOA
 02-0618.08
 12 SETS ONLY 2 ARE REQUIRED, THIS REPORT IS A 1994
 TEST REPORT AND THE FASTENERS TOOK 1 1/3 STEEL
 INCREASES NOT ALLOWED BYTHE 2004 FBC. REQUIRES REVIEW
 BY A FLORIDA PE OR TAKE THE DESIGN PRESSURES LISTED IN
 THE NOA AND DIVIDE BY 1.33 TO COMPLY WITH THE 2004
 FBC.
 PLEASE HIGHLIGHT THE TYPE OF GLAZING TO BE INSTALLED IN
 THESE UNITS. IT APPEARS THAT THERE MAY BE PROBLEMS
 POSSIBLY WITH ZONE 4 AND DIFFERENTLY ZONE 5. PLEASE
 IDENTIFY THESE ZONES.
 SHEET A-2.2 THE WINDOWS NEXT TO THE FRONT ENTRY
 INDICATES ACTUAL CURVED GLAZING, WILL THIS WINDOW BE
 ACTUALLY CURVED? IF SO PROVIDE THE PRODUCT APPROVAL
 WITH TESTING.
 B) MULLIONS- MAY OR MAY NOT BE PART OF THE NOA, A
 SECOND ISSUE IS THE HEIGHT OF THE HORIZONTAL MULLIONS
 ON SHEETS A-5.1 AND A-5.2 IN EITHER CASE ONE OF THE
 WINDOWS ARE
 ILLUSTRATED WRONG EFFECTING THE SQ FT AREA OF THE
 GLAZING.
 THIS SAME AREA OR WINDOWA VERTICAL MULLION APPEARS TO
 BE MISSING.
 C) GLAZED SWING DOORS (EXTERIOR) YKK SERIES 20D NARROW
 STILENOA 03-0801.05
 THE NOA SUBMITTED HAS NO IMPACT TESTING, THIS DOOR IS
 LOCATED IN AN END ZONE (5) , PRESSURES ARE LOW ALSO
 TESTED UNDER THE 1994 CODE. ,THIS REPORT IS A 1994 TEST
 REPORT AND THE FASTENERS TOOK 1 1/3 STEEL INCREASES NOT
 ALLOWED BYTHE 2004 FBC. REQUIRES REVIEW BY A FLORIDA
 PE OR TAKE THE DESIGN PRESSURES LISTED IN THE NOA AND
 DIVIDE BY 1.33 TO COMPLY WITH THE 2004 FBC. SUBMIT ONLY
 (2) SETS OF PRODUCT APPROVALS THAT HAVE LARGE MISSILE
 TESTING. AND MEET THE END ZONE PRESSURES.
 D) EXTERIOR METAL SWING DOORSPRESSURES ARE GOOD FOR
 ZONE 4 ONLY, PLEASE SUBMIT ONLY 2 SETS OFPRODUCT
 APPROVALS.
  
 E) PRE ENGINEERED A/C STANDS PRESSURES ARE GOOD SUBMIT
 ONLY 2 SETS OF PRODUCT APPROVALS
 F) EFIS SYSTEMS PLEASE SUBMIT ONLY 2 PRODUCT
 APPROVALS, HIGHLIGHT WHICH SUBSYSTEM TO BE USED. VERIFY
 PRESSURES.
  
 8) COMPLIED.
  
 9) 2ND REQUEST WPB ADMIN CODE 106.3* PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE RESPONSEINDICATES THE
 NOA?S WERE SIGNED THEY NEED TO BE REVIEWED BY THE
 DESIGNER OF RECORD.
  
 10) 2ND REQUEST,SHEET G-SP2HEADING 815-C
 INSTALLATIONINDICATES A WIND PRESSURE OF 26PSF PLEASE
 SEE TABLE 1609.6.2.1(1)ALSO SEE MULTIPLIERS THE
 SHOPPING CENTER AND PARKING GARAGE ARE CONSIDERED ONE 5
 STORY BUILDING!!!! SEE TABLE 1609.6.2.1(4) FOR
 MULTIPLIERS.,
 PRESSURES SHOULD BE HIGHER AS ON SHEET S3.1.
  
 11-12) COMPLIED.
  
 13) SEMI-COMPLIED, THE OLD VOID SHEETS HAVEN?T BEEN
 REMOVED AS REQUESTED
 UNDER COMMENT # 1.
  
 14) 2ND REQUEST DEALS WITH PROVIDING INFORMATION ON THE
 FREEZER AND WALK-IN COOLERS, RESPONSE INDICATES SHOP
 DRAWINGS WERE SUBMITTED, NOT IN THIS SUBMITTAL:
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND SELF-IGNITION
 TEMPERATURES OF NOT LESS THAN 600?F AND 800?F (316?C
 AND 427?C), RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLED.
  
 2603.4.1.3 WALK-IN COOLERS.
 IN NON-SPRINKLED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE
 FLOOR AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 )
 AND THE FOAM PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 15) SEMI-COMPLIED. PLEASE ONLY SUBMIT (2) SETS OF FIRE
 SPRINKLER PLANS FOR THIS REVIEW. THE FIRE SPRINKLER
 CONTRACTOR WILL NEED TO SUPPLY(2) MORE SETS FOR THEIR
 OWN FIRE SPRINKLER PERMITTO BE FILED AT A LATER DATE.
 THE OTHER ISSUE IS UNTIL THE HEIGHT OF THE COOLERS AND
 FREEZERS ARE KNOWN THE UNKNOWN IS THE FIRE SPRINKLERS
 TO BE LOCATED IN THE COOLERS!
  
 16) COMPLIED.
  
 17) SEMI-COMPLIED, PLEASE REMOVE OLD SHEETS AS PER
 COMMENT # 1.
  
 18-20) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 PLAN EXAMINER II BUILDING
 TEL: (561)805-6715