Plan Review Notes
Plan Review Notes For Permit 07030523
Permit Number 07030523
Review Stop P
Sequence Number 1
Notes
Date Text
2007-04-27 18:56:07DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 1. ALL SHEETS. INDICATE THE TENANT UNIT/SPACE NUMBER IN
 THE TITLE BLOCK ALONG WITH THE ADDRESS. SECTION 106.1.
  
 2. SHT EC-2.1 THE EXISTING FLOOR PLAN SHOWS NO EXISTING
 PLUMBING, BUT SHT A-2.0 INDICATES REMOVAL OF EXISTING
 PLUMBING LINES. PLEASE SHOW WHERE THE PLUMBING LINES
 WILL BE DEMO'D SO THE FIELD INSPECTOR CAN ASSURE THE
 LINES ARE DEMO'D PROPERLY AND NO DEAD ENDS ARE LEFT.
 SECTIONS 106.1.1 & 704.5.
  
 3. SHT G-ADA SHOW THE FOLLOWING ACCESSIBILITY
 REQUIREMENTS:
 A. 11-4.16.5 FLUSH CONTROLS __W/C
 B. 11-4.19.5 FAUCETS __LAVS
  
 4. SHT EQ-2.1, THE 2 PAGE "WORKSHEETS" FROM DBPR HOTEL
 AND RESTURANT DIVISION PLAN REVIEW SHALL BE ATTACHED TO
 EACH SHEET STAMPED BY THE FOOD SERVICE ON EACH SET OF
 PLANS. SECTION 102.2.1.
  
 5. ALL MEP SHEETS. THE ORIGINAL SIGNATURE OF THE
 ENGINEER IS REQUIRED WHEN THE SEAL IS AFFIXED. THE
 STAMPED SIGNATURE IS NOT APPROVED. FAC
 61G15-23.002(1)(2) & FS 471.025.
  
 6. ALL MEP SHEETS. THE CERTIFICATE OF AUTHROIZATION
 NUMBER OF THE ENGINEERING BUSINESS IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET. THE FLORIDA STATE WEBSITE OF
 THE DBPR INDICATES THAT THE STATUS OF THE CA NUMBER IS
 CLOSED. (SEE ATTACHED SHEET FROM WEBSITE). PLEASE
 SECURE A CA NUMBER PRIOR TO RESUBMITTING FOR REVIEW AT
 WPB. FAC 61G15-23.002(2) & FS 471.025.
  
 7. SHT P-2.1 GENERAL PLUMBING NOTE #6 INDICATES THE
 SLEEVE TO BE 1" MINIMUM LARGER THAN THE PIPE PASSING
 THRU THE WALL. PER SECTION 305.5 THE SLEEVES SHALL BE 2
 PIPE SIZES GREATER THAN THE PIPE PASSING THROUGH THE
 WALL. PLEASE CORRECT THE PLUMBING NOTE.
  
 8. SHT P-2.3 THE DISH WASHER, (27A), SHALL CONNECT TO
 THE SANITARY SYSTEM, NOT THE GREASE SYSTEM AS SHOWN.
 MUNICIPAL CODE SECTION 90-124(7)(B). PLEASE CHANGE ON
 THE FLOOR PLAN AND THE RISER DIAGRAM.
  
 9. SHT P-2.4 THE GAS LINE STARTS OUT 1-1/2" THEN
 REDUCES TO 1-1/4"AND THEN IS INDICATED AS 1-1/2" AT
 THE OVEN. PLEASE CLARIFY. TABLE 402.4(2).
  
 10. SHT P-2.4 SHOW THE GAS TO THE WATER HEATERS WITH
 ALL OFFSETS ETC. SECTION 106.1.1.
  
 11. SHT P-2.4 NO COLD WATER DROP NOR HOT WATER RISER
 FOR THE WATER HEATERS ARE INDICATED ON THE WATER
 PIPING. PLEASE CLARIFY. SECTION 106.1.1.
  
 12. SHT P-3.1 THE FLOOR SINK (P-7 FOR THE DISH WASHER,
 (27A), TO BE CONNECTED TO THE SANITARY SYSTEM AND NOT
 THE GREASE SYSTEM. (SEE COMMENT #8).
  
 13. SHT P-3.1 SECTION 15400 PLUMBING NOTES 1.0 STATES
 DESIGN BASED ON INTERNATIONAL PLUMBING CODE. ADOPTED
 CODE IS THE FBC-2004 PLUMBING CODE. PLEASE CHANGE
 REFERENCE. SECTION 106.1.1.
  
 14. SHT P-3.2 THE HOT & COLD WATER SUPPLIES TO FIXTURE
 13A ARE REVERSED. HOT IS SHOWN ON THE RIGHT AND COLD IS
 SHOWN ON THE LEFT. PLEASE CORRECT. SECTION 607.4.--
 THE WATER RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN
 IN THE WOMEN'S TOILET ROOM. THE FLOOR PLAN INDICATES
 W/C P-1 ON THE FLOOR PLAN BUT IS INDICATED AS P-3 ON
 THE RISER DIAGRAM. THE TRAP PRIMER LINE IS SHOWN BY P-1
 ON THE FLOOR PLAN, BUT THE LINE IS SHOWN BY P-3 ON THE
 RISER DIAGRAM. PLEASE CORRELATE THE INFORMATION. --NO
 COLD WATER SUPPLY AND HOT WATER LINES TO THE HEATERS
 ARE INDICATED.--THE STORAGE WATER HEATER REQUIRES A
 FULL OPEN VALVE ON THE SUPPLY LINE.--A VACUUM
 RELIEF VALVE IS REQUIRED ON THE BOTTOM FED WATER
 HEATER. SECTIONS 106.1.1., 606.1(6) & 504.2.
  
 15. SHT P-3.2 THE FOLLOWING GAS REQUIREMENTS SHALL BE
 SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. THIS SHALL BE SHOWN FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES. MATERIAL IS INDICATED AS
 EITHER THREADED OR WELDED ON SHT P-3.1. IS THE PIPING
 WILL BE WELDED, THE WELDING CERTIFICATION AND WELDING
 PROCEDURE WILL BE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - THIS IS INDICATED AS 90
 FEET ON THE PLANS, BUT CAN NOT BE VERIFIED UNTIL ALL
 CUT SECTION MEASURMENTS ARE SUBMITTED. (SEE GAS COMMENT
 A).
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLANS INDICATE
 7"WC. THE PRESSURE WILL BE EITHER 2PSI OR 1/2PSI.
 PLEASE INDICATE ON THE PLANS.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 16. SUBMIT THE MANUF. SPECIFICATIONS FOR THE WATER
 FILTER. THE FILTER SHALL MEET THE REQUIREMENTS OF
 NSF-42. SECTION 611.1
  
 17. SUBMIT THE MANUF. SPECIFICATIONS FOR THE TEMPERING
 VALVE. SECTION 106.1.2.
  
 18. SHT P-4.1 THE 10 GALLON HOT WATER STORAGE TANK
 REQUIRES A RELIEF VALVE PER SECTION 504.4 AND SHALL BE
 INSTALLED PER 504.4.1. THE RELIEF LINE SHALL DISCHARGE
 PER SECTION 504.6.1. SUBMIT A DETAIL INDICATING
 COMPLIANCE. IF THE STORAGE TANK IS INSTALLED ABOVE THE
 GROUND FLOOR SPACE, IT SHALL BE INSTALLED IN A PAN AND
 SHALL HAVE A PAN DRAIN LINE. SECTIONS 504.7, 504.7.1 &
 504.7.2. PLEASE CLARIFY AND SUBMIT DETAILS IF
 REQUIRED.
  
 19. SHT P-4.1 THE WATER HEATER SCHEMATIC SHALL SHOW ALL
 PIPE SIZES FOR THE WATER LINES AND THE GAS LINES.--
 SCHEMATIC SHOWS 2" GAS HEADER, THIS SHALL REFLECT THE
 GAS RISER DIAGRAM.
  
 20. SHT P-4.1 THE 4 POD WATER FILTER DETAIL SHOWS A
 RESIN TANK & A BRINE TANK THAT IS NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE
 INFORMATION. THE SYSTEM ALSO SHOWS A 1" LINE THAT
 STATES "TO DRAIN". PLEASE INDICATE WHERE IT WILL DRAIN
 TO.SECTIONS 106.1.1 802.1.5.
  
 21. THE GREASE LINE SHALL DRAIN TO A GREASE
 INTERCEPTOR. THE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY
 COMPO AT (561) 822-2272 OR CALVIN WILLIAMS AT (561)
 822-2284. THEIR FAX NUMBER IS (561) 822-2287 OR THEY
 CAN BE REACHED BY E-MAIL [email protected] OR
 [email protected]. CITY CODE 90-124(7).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]