2007-04-16 15:20:52-----------------DENIED-------------------
  
 FBC 2004 W/2006 REVISIONS
 FBC CH 1 AS REVISED BY THE CITY OF WEST PALM BEACH
  
 1. MPE-1.1: MECHANICAL EQUIPMENT AND SUPPORTS EXPOSED
 TO WIND SHALL BE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBC CH 16. PROVIDE WIND LOAD
 CALCULATIONS AND CONNECTION DETAILS CERTIFIED BY A
 STATE LICENSED STRUCTURAL ENGINEER. PRE-ENGINEERED
 EQUIPMENT STANDS ARE STRUCTURAL ELEMENTS AS DEFINED IN
 FAC 9B-72. AS SUCH, PRODUCT APPROVAL IS REQUIRED.
  
 2 MPE-1.1: WHERE EQUIPMENT IS LOCATED WITHIN 10' OF A
 ROOF EDGE, A GUARD SHALL BE PROVIDED PER FBC,M 304.10.
 GUARDS SHALL MEET THE LOADING REQUIREMENTS OF FBC
 1618.4.6.
  
 3. PLEASE SHOW LOCATION OF OUTSIDE AIR DUCTS AND VOLUME
 DAMPERS FEEDING AHU'S 1,2,3. FBC 106.1.1
  
 4. M-3.1: KITCHEN AIR BALANCE SCHEDULE: AHU-3 SHOWS
 1300 CFM SUPPLY, BUT FLOOR PLAN SHOWS 1150 CFM SUPPLY.
 THERE IS ALSSO 300 CFM SUPPLY BEING EXHAUSTED IN
 BATHROOMS. THIS LEAVES A NET 850 CFM SUPPLY WITH 1100
 CFM RETURN. THIS WILL NOT ALLOW THE INDUCTION OF 200
 CFM OUTSIDE AIR AS STATED ON SCHEDULE. PLEASE SHOW HOW
 PROPER AIR BALANCE IS TO BE ACHIEVED. FBC 10601.2.
  
 5. M-3.1 EXHAUST FAN CURB DETAIL: PLEASE SEE PREVIOUS
 COMMENT REGARDING WIND LOADS FOR OUTDOOR EQUIPMENT.
  
 6. M-3.1 EXHAUST FAN CURB DETAIL: WHAT IS THE REASON
 FOR THE GREASE RETENTION SYSTEM ON ROOF? IF THERE IS
 THE EXPECTATION OF THE ACCUMULATION OF GREASE OR
 GREASE-LADEN VAPOR, A TYPE I HOOD IS REQUIRED OVER
 COOKING EQUIPMENT PER FBC,M 507.2 AND NFPA 96.
  
 7. M-3.1 EXHAUST FAN SCHEDULE: WHERE IS EF 3 LOCATED?
 IT IS NOT SHOWN ON PLANS. EF SCHEDULE SHOWS EF 3 AT 550
 CFM BUT RESTAURANT AIR BALANCE SCHEDULE SHOWS EF 3 AT
 400 CFM. PLEASE CLARIFY PER FBC 106.1.1 AND FBC
 106.1.2.
  
 8 M-4.1 KITCHEN HOOD EXHAUST NOTES: THIS INFORMATION IS
 IN CONFLICT WITH DUCT DETAIL ON M-4.2 FROM CAPTIVEAIR.
 PLEASE CLARIFY BY RESOLVING THIS CONFLICT. THIS IS
 ANOTHER INDICATION THET THERE IS AN EXPECTATION OF
 GREASE-LADEN VAPORS FROM THE COOKING EQUIPMENT. PLEASE
 PROVIDE MANUFACTURER'S SUBMITTAL/ INSTALLATION
 INSTRUCTIONS SHOWING LISTING AND TYPE OF EXHAUST
 REQUIRED. FBC 106.1.1
  
 9. M-4.2 MUA UNIT DETAIL SHOWS 250,000 BTU GAS HEATER,
 BUT THIS IS NOT SHOWN ON GAS RISER DIAGRAM. PLEASE
 COORDINATE DRAWINGS.
  
 10. PLEASE SHOW COMPLIANCE WITH FBC CH 13-409.1.ABC.3.2
 THRU .3.4 (ENERGY CODE) REGARDING VENTILATION SYSTEM
 CONTROLS.
  
 11. PLEASE SHOW ALL GAS APPLIANCE VENT TERMINATION
 LOCATIONS.
  
 NOTE: SEPARATE PERMIT REQUIRED FOR WALK-IN
 COOLER/FREEZER.
  