| 2007-05-08 18:17:05 | *****DENIED***** |
| | |
| | |
| | 01.THE ENTIRE NUMERERICAL ADDRESS INCLUDING THE SUITE |
| | NUMBER SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN SHEET. |
| | |
| | 02.ON SHEET G-CS, UNDER APPLICABLE CODES AND |
| | REGULATIONS, ADD LIFE SAFETY CODE - NFPA 1012003 |
| | EDITION. |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY |
| | AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 05.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | SOUTH ROSEMARY AVENUE, DISPLAY THE SUITE NUMBER.AS |
| | PER WEST PALM BEACH CODE, TENANT SPACE NUMBERS SHALL BE |
| | NO LESS THA 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| | |
| | 06.ANY DOOR IN A MEANS OF EGRESS FROM AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PROVIDED WITH PANIC HARDWARE OF FIRE EXIT HARDWARE. |
| | |
| | 07.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| | THE TRAVEL DISTANCE TO REACH AN EXIT.THE LOCATION OF |
| | EXIT LIGHTS, EMERGENCY LIGHTS AND FIRE EXTINGUISHERS |
| | MAY ALSO BE INCLUDED. |
| | |
| | 08.COMMERCIAL COOKING EQUIPMENT SHALL BE IN |
| | ACCORDANCE WITH NFPA 96.SEPARATE PLANS AND PERMIT |
| | WILL BE REQUIRED FOR THE HOOD INSTALLATION AS WELL AS |
| | THE HOOD SUPPRESSION SYSTEM. |
| | |
| | 09.PROVIDE INTERIOR FINISH CLASSIFICATION FOR THE |
| | WALLS AND CEILINGS.INTERIOR WALL AND CEILING FINISH |
| | MATERIALS SHALL BE CLASS A OR CLASS B IN EXITS AND EXIT |
| | ACCESS CORRIDORS, AND CLASS A, CLASS B, OR CLASS C IN |
| | ALL OTHER AREAS. |
| | |
| | 10.ALTHOUGH SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED FOR THE FIRE SPRINKLER SYSTEM REMODEL, PROVIDE |
| | A LAYOUT OF THIS SYSTEM UNDER THIS PERMIT. |
| | |
| | 11.ALTHOUGH SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED FO THE FIRE ALARM SYSTEM REMODEL, PROVIDE A |
| | LAYOUT OF THE SYSTEM UNDER THIS PERMIT. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |