| 2007-03-25 14:16:34 | |
| | |
| | ****** UNSAT ***** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SEE THAT THERE COMMENTS MADE TO SHEETS OTHER |
| | THAN ELECTRICAL BY THIS REVIEWER WHICH WILL BE REQUIRED |
| | TO BE MET WHETHER OR NOT COMMENTS ARE MADE FORM OTHER |
| | TRADES. |
| | |
| | ** IMPORTANT** |
| | ONLY ONE SET OF PLANS WILL BE RETURNED. |
| | DUE TO MANY OF THE COMMENTS BELOW AND THE TYPE OF |
| | COMMENTS, TWO OF THE THREE SETS OF PLANS SUBMITTED ARE |
| | BEING RETAINED BY THIS OFFICE. |
| | |
| | 1) NOTE: PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR |
| | PERMIT AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT |
| | UNDER THE NEW CODES. |
| | PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE |
| | ARCHITECTURAL SHEETS ALONG WITH ELECTRICAL SHEETS. |
| | PLEASE SEE SHEETS OF PLANS CONTAIN CODES WHICH ARE NOT |
| | ADOPTED BY THE STATE OF FLORIDA. PLEASE SEE CODES FROM |
| | IBC, SBCCI ETC |
| | PLANS INDICATE A 2003 NFPA-70 (NEC) ? PLEASE KNOW THERE |
| | IS A 2002 AND THEN THE NEW CODE IS THE 2005. PLEASE SEE |
| | THAT ALL AREAS OF PLANS WHICH REFERENCE THE 2002 NEC |
| | SHALL ONLY STATE THE 2005. THIS WILL AFFECT MANY AREAS |
| | OF PLANS. SEE OTHER COMMENTS WITH RESPECT TO THESE. |
| | PLEASE ALSO BE SURE THE TRADES REFLECT THE CODES |
| | RELEVANT TO THEIR DESIGNS ON RESPECTIVE SHEETS. 2004 |
| | FBC W/ 2006 REVISIONS (ALL TRADES). |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** PLEASE SEE NOTES ON G-SL INDICATE FEDERAL |
| | REQUIREMENTS FOR ADA. PLEASE KNOW THAT THE STATE OF |
| | FLORIDA CONTAINS ITS OWN ADA CODE AS REQUIRED IN |
| | CHAPTER 11 OF THE 2004 FBC W/2006 REVISIONS. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WITH |
| | RESPECT TO OTHER CODES REQUIRED ON PLANS. |
| | |
| | 2) NOTE: PLEASE SEE THE SHEETS FROM THE ENGINEERING |
| | FIRM ARE MISSING TITLE BLOCK INFORMATION AS REQUIRED |
| | PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND |
| | FLORIDA STATUTES 471.023. |
| | A SEARCH WITH THE DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION DID NOT FIND ANY RELEVANT |
| | LICENSE INFORMATION ATTACHED TO ENGINEER.. |
| | PLEASE ALSO KNOW IF THE ENGINEER IS EMPLOYED BY THE |
| | SAID COMPANY AND COMPANY IS OFFERING ENGINEERING |
| | SERVICES, THEN A CERTIFICATE OF AUTHORIZATION NUMBER IS |
| | REQUIRED FOR SAID FIRM. |
| | PLEASE SEE FS 471.023. |
| | |
| | 3) NOTE: PLEASE SEEMEP SHEETS DO NOT CONTAIN ORIGINAL |
| | SIGNATURES WHICHARE REQUIRED PER FS 471.025 AND FAC |
| | 61G15-23.002. THESE CONTAIN A RAISED SEAL HOWEVER THESE |
| | ARE NOT ORIGINAL SIGNATURES. *ALL THREE SETS CONTAIN |
| | THE SAME*THE STATE OF FLORIDA REQUIRES AN ORIGINAL |
| | SIGNATURE. PLEASE SEE SECTION EXTRACTED FORM THE |
| | FLORIDA STATUTES. |
| | * ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, |
| | OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND |
| | BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS |
| | PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE |
| | SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH |
| | SAID SEAL. SUCH SIGNATURE, DATE, AND SEAL SHALL BE |
| | EVIDENCE OF THE AUTHENTICITY OF THAT TO WHICH THEY ARE |
| | AFFIXED.* |
| | |
| | **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 4) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS ARE |
| | MISSING THE PRINTED NAME OF THE ARCHITECT ON TITLE |
| | BLOCKS AS REQUIRED PER FAC61G1-16.004. |
| | * THIS IS REQUIRED WHETHER OR COMMENT IS MADE BY OTHER |
| | TRADE(S). |
| | |
| | 5) NOTE: PLEASE INCLUDE THE SUITE/UNIT NUMBER ON TITLE |
| | BLOCKS. |
| | FAC 61G15-23.002, 61G1-16.004 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF |
| | MATERIALS, EQUIPMENT, ETC IS OWNER SUPPLIED AS STATED |
| | ON PLANS. |
| | VALUE IS LOW AT THIS TIME. PLEASE ADJUST. |
| | PLEASE KNOW A VALUE MAY BE ADJUSTED BY THIS OFFICE |
| | USING ADOPTED DOCUMENTS INTO THE FBC. |
| | FBC 108.3 |
| | |
| | 7) NOTE: PLEASE SEE THE 2004 FBC W/ 2006 REVISIONS FOR |
| | CHAPTER 13. AT THIS TIME THERE ARE SEVERAL ITEMS |
| | MISSING FOR REVIEW. |
| | PLEASE SEE NO SCHEDULING OF SYSTEM WAS SUBMITTED. |
| | PLEASE SEE NO INFORMATION ON A SYSTEM WAS SUBMITTED. |
| | PLEASE SEE NO OVER RIDE DEVICES AT THE POINTS OF |
| | EGRESS/INGRESS INTO SPACE FROM ENTRANCE WIN WHICH THE |
| | OCCUPANT CAN SEE THE LIGHTING WHICH IS BEING |
| | CONTROLLED. |
| | PLEASE SEE NO TIMES ON ANY OVER RIDE DEVICES AND TYPES |
| | OF DEVICES. |
| | PLEASE SEE MISSING ENERGY CALCULATIONS. |
| | PLEASE SEE MISSING LIGHTING PERFORMANCE CALCULATIONS. |
| | PLEASE SEE MISSING CERTIFICATIONS PER DESIGNER(S) OF |
| | RECORD. |
| | PLEASE SEE REQUIRED CALCULATION METHODS FOR TRACK |
| | LIGHTING. 13-415.2.ABC.1.2 |
| | |
| | PLEASE SEE 13-103.1, 13-415.1ABC.1, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3, 13-415.1.AB.1.1, 13-415.1.A, .B AND .C, |
| | 13-415.2 AND TABLES UNDER THE NEW 2006 REVISIONS. ETC. |
| | |
| | 8) NOTE: PLEASE SEE PLANS NOTES FOR GFI PROTECTION |
| | WHERE CODES ARE ADOPTED HOWEVER PLEASE ACTUALLY SHOW |
| | WHERE THE PROTECTION WILL BE. PLEASE INDICATE BY THE |
| | DEVICES OR BREAKERS. QUOTING THE CODE LIEU OF SHOWING |
| | SPECIFIC DETAIL IS NOT PERMITTED. |
| | |
| | 9) NOTE: PLEASE INDICATE INTERLOCKS/SHUNT-DEVICES FOR |
| | ANY LIGHTING ETC WHICH ARE FED TO HOOD. |
| | NFPA-96 |
| | |
| | 10) NOTE: PLEASE INDICATE TRANSFORMER GROUNDING. THE |
| | SIZE CONNECTIONS ETC RE REQUIRED TO BE SHOWN, NOT ONLY |
| | QUOTED CODE. |
| | 250.20,250.30,250.66 |
| | |
| | 11) NOTE: PLEASE CLARIFY HOW THE FEEDERS ON THE LINE |
| | SIDE OF THE TRANSFORMER CAN CONTAIN A NEUTRAL WHEN THIS |
| | IS GOING TO BE A SEPARATELY DERIVED SYSTEM? PLEASE SEE |
| | FEEDER NUMERICAL DESIGNATIONS OF#39 WHICH CONTAINS A |
| | NEUTRAL. |
| | |
| | 12) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON LEGEND |
| | ONLY. PLEASE INCLUDE ON LAYOUT OF PLANS AND DEVICES. |
| | PLEASE KNOW EVEN THOUGH FIRE SPRINKLER AND FIRE ALARM |
| | WORK WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT THE |
| | BASE FIRE ALARM DEVICES ALONG WITH FIRE PROTECTION WILL |
| | BE REQUIRED IN BASE PLANS. THIS WILL BE NOTED BY THE |
| | FIRE AND BUILDING REVIEWER(S) ALSO. |
| | |
| | 13) NOTE: PLEASE SEE MISSING SIGN CIRCUIT ON PLANS AND |
| | PANEL SCHEDULE PER 600.5. |
| | |
| | 14) NOTE: PLEASE VERIFY SERVICE AS SHOWN AS THE RISER |
| | MENTIONS THE METER IS BEING DONE BY THE LANDLORD?? THIS |
| | SCOPE OF WORK HAS NOT BEEN DONE/OR APPLIED FOR. PLEASE |
| | SEE THE RISER SEEMS TO SHOW THE NEW TENANT MAIN AS NEMA |
| | 3R WHICH LENDS TO THIS BEING LOCATED OUTSIDE? PLEASE |
| | KNOW THAT THIS BUILDING CONTAINS AN INDOOR ELECTRICAL |
| | ROOM WHERE ALL TENANT MAIN DISCONNECTS ARE LOCATED. |
| | PLEASE PROVIDE A LAYOUT FOR LOCATIONS AND LOADS OF THE |
| | NEW ON THE EXISTING MAIN WITH THE EXISTING LOADS. |
| | PLEASE KNOW AT THIS TIME THERE ARE ITEMS WHICH CAN NOT |
| | BE REVIEWED FOR CODE COMPLIANCE. |
| | PLEASE SEE NEC 220 IN THE 2005 NEC AS THE CALCULATIONS |
| | AND LOAD SUMMARY FOR THIS SERVICE AND LOADS WITH |
| | EXISTING SERVICE NEED TO BE SHOWN PER NEW CODE. PLEASE |
| | SEE PLANS WHICH CONTAIN CODE SECTIONS FROM THE PREVIOUS |
| | NEC. |
| | FBC 106.3.5.1.2 |
| | |
| | 15) NOTE: PLEASE INDICATE A *FLOATING NEUTRAL* IN METER |
| | AS REQUIRED PER 250.6 AND 250.24. THIS WILL ALLEVIATE |
| | ANY OBJECTIONABLE CURRENTS. |
| | |
| | 16) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF |
| | EMERGENCY LIGHTING AND EXIT LIGHTING.THE PLAN |
| | MENTIONS 701, 701.11F WHICH IS NOT APPLICABLE. |
| | FBC 106.1.2 |
| | |
| | 17) NOTE: PLEASE BE SURE ALL EQUIPMENT CONTAINS THE AIC |
| | RATINGS AS REQUIRED PER 110.9. PLEASE INDICATE FOR THE |
| | NEW MAIN ON RISER AS SHOWN. |
| | |
| | 18) NOTE: PLEASE SEE NEC 408.4 AS THE CIRCUITS IN PANEL |
| | SCHEDULES NEED TO BE SPECIFIC TO THE ROOMS AND AREAS IN |
| | WHICH THEY FEED. PLEASE THE FOLLOWING TEXT WHICH IS |
| | BEING EXTRACTED FROM THE NEC HANDBOOK. |
| | **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO |
| | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 19) NOTE: PLEASE SUBMIT THE MANUFACTURES SPEC/CUT |
| | SHEETS ON THE PROPOSED POWER DISTRIBUTION CENTER FOR |
| | REVIEW. PLEASE BE SURE LISTINGS FROM A NRTL( NATIONALLY |
| | RECOGNIZED TESTING LABORATORY) IS SHOWN. |
| | 110.3, 90.7. |
| | FBC 106.1.2. |
| | |
| | 20) NOTE: PLEASE SEE THE COLOR CODING SHALL BE AS |
| | FOLLOWS. |
| | 277/480V SYSTEMS, BROWN, PURPLE, YELLOW. |
| | PLEASE SEE THAT THE NEC HAS *ORANGE* DESIGNATED FOR |
| | MARKING OF A *HIGH-LEG* IN AN OPEN DELTA SYSTEM WHICH |
| | IS NOT WHAT IS BEING INSTALLED. |
| | PLEASE KNOW AS PER LOCAL JURISDICTIONS AND LOCAL WIRING |
| | AT THE LOCATION OF SAID PROJECT THE COLOR CODING OF THE |
| | EXISTING SYSTEMS IN THIS BUILDING IS AS NOTED. 90.4 |
| | |
| | 21) NOTE: PLEASE SEE THAT PANEL M AND RISER IS SHOWING |
| | A FEED TO A PANEL *S* YET THE PLANS SUBMITTED DO NOT |
| | SHOW ANY PANEL *S*?? |
| | PLEASE SUBMIT THE COMPLETED PLANS SHOWING THIS PANEL. |
| | FBC 106.3.5.1.2 |
| | |
| | 22) NOTE: PLEASE SEE THE TRANSFORMER WHICH IS BEING |
| | SHOWN ABOVE OFFICE IS NOT PERMITTED AT THIS LOCATION |
| | PER 450.13B AND 450.21B. |
| | PLEASE PROVIDE MORE DETAILS AND INFORMATION ON TYPE OF |
| | TRANSFORMER. THE LOCATION IS NOT PERMITTED BASED ON |
| | PLANS SUBMITTED. |
| | 110.3, 90.7 |
| | FBC 106.3.5.1.2 |
| | |
| | 23) NOTE: PLEASE SEE MISSING ROOFTOP ELECTRICAL PLANS, |
| | A/C PLANS FOR ELECTRICAL DISCONNECTS, NEW OR EXISTING |
| | GFI REQUIRED FOR EQUIPMENT ETC. |
| | 440.11, 210.63 . |
| | PLEASE SUBMIT. |
| | FBC106.1.2 |
| | |
| | 24) NOTE: PLEASE KNOW ANY LOCK OFF/ON DEVICES SHALL BE |
| | AN INTEGRAL PART OF THE BREAKER, NOT ONE THAT ONLY |
| | SNAPS INTO PLACE OR CAN BE EASILY REMOVED OR FALL OFF |
| | WHEN PANEL COVER IS REMOVED. |
| | 110.3, 90.4. |
| | |
| | ** PLEASE KNOW AS THERE IS SUBSTANTIAL INFORMATION |
| | WHICH WAS NOT SUBMITTED A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE COULD NOT BE DONE AND THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE NEXT REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |