Plan Review Notes
Plan Review Notes For Permit 07030523
Permit Number 07030523
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-25 14:16:34 
  
 ****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE THAT THERE COMMENTS MADE TO SHEETS OTHER
 THAN ELECTRICAL BY THIS REVIEWER WHICH WILL BE REQUIRED
 TO BE MET WHETHER OR NOT COMMENTS ARE MADE FORM OTHER
 TRADES.
  
 ** IMPORTANT**
 ONLY ONE SET OF PLANS WILL BE RETURNED.
 DUE TO MANY OF THE COMMENTS BELOW AND THE TYPE OF
 COMMENTS, TWO OF THE THREE SETS OF PLANS SUBMITTED ARE
 BEING RETAINED BY THIS OFFICE.
  
 1) NOTE: PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR
 PERMIT AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT
 UNDER THE NEW CODES.
 PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE
 ARCHITECTURAL SHEETS ALONG WITH ELECTRICAL SHEETS.
 PLEASE SEE SHEETS OF PLANS CONTAIN CODES WHICH ARE NOT
 ADOPTED BY THE STATE OF FLORIDA. PLEASE SEE CODES FROM
 IBC, SBCCI ETC
 PLANS INDICATE A 2003 NFPA-70 (NEC) ? PLEASE KNOW THERE
 IS A 2002 AND THEN THE NEW CODE IS THE 2005. PLEASE SEE
 THAT ALL AREAS OF PLANS WHICH REFERENCE THE 2002 NEC
 SHALL ONLY STATE THE 2005. THIS WILL AFFECT MANY AREAS
 OF PLANS. SEE OTHER COMMENTS WITH RESPECT TO THESE.
 PLEASE ALSO BE SURE THE TRADES REFLECT THE CODES
 RELEVANT TO THEIR DESIGNS ON RESPECTIVE SHEETS. 2004
 FBC W/ 2006 REVISIONS (ALL TRADES).
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLEASE SEE NOTES ON G-SL INDICATE FEDERAL
 REQUIREMENTS FOR ADA. PLEASE KNOW THAT THE STATE OF
 FLORIDA CONTAINS ITS OWN ADA CODE AS REQUIRED IN
 CHAPTER 11 OF THE 2004 FBC W/2006 REVISIONS.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WITH
 RESPECT TO OTHER CODES REQUIRED ON PLANS.
  
 2) NOTE: PLEASE SEE THE SHEETS FROM THE ENGINEERING
 FIRM ARE MISSING TITLE BLOCK INFORMATION AS REQUIRED
 PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUTES 471.023.
 A SEARCH WITH THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION DID NOT FIND ANY RELEVANT
 LICENSE INFORMATION ATTACHED TO ENGINEER..
 PLEASE ALSO KNOW IF THE ENGINEER IS EMPLOYED BY THE
 SAID COMPANY AND COMPANY IS OFFERING ENGINEERING
 SERVICES, THEN A CERTIFICATE OF AUTHORIZATION NUMBER IS
 REQUIRED FOR SAID FIRM.
 PLEASE SEE FS 471.023.
  
 3) NOTE: PLEASE SEEMEP SHEETS DO NOT CONTAIN ORIGINAL
 SIGNATURES WHICHARE REQUIRED PER FS 471.025 AND FAC
 61G15-23.002. THESE CONTAIN A RAISED SEAL HOWEVER THESE
 ARE NOT ORIGINAL SIGNATURES. *ALL THREE SETS CONTAIN
 THE SAME*THE STATE OF FLORIDA REQUIRES AN ORIGINAL
 SIGNATURE. PLEASE SEE SECTION EXTRACTED FORM THE
 FLORIDA STATUTES.
 * ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS,
 OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND
 BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL. SUCH SIGNATURE, DATE, AND SEAL SHALL BE
 EVIDENCE OF THE AUTHENTICITY OF THAT TO WHICH THEY ARE
 AFFIXED.*
  
 **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS ARE
 MISSING THE PRINTED NAME OF THE ARCHITECT ON TITLE
 BLOCKS AS REQUIRED PER FAC61G1-16.004.
 * THIS IS REQUIRED WHETHER OR COMMENT IS MADE BY OTHER
 TRADE(S).
  
 5) NOTE: PLEASE INCLUDE THE SUITE/UNIT NUMBER ON TITLE
 BLOCKS.
 FAC 61G15-23.002, 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF
 MATERIALS, EQUIPMENT, ETC IS OWNER SUPPLIED AS STATED
 ON PLANS.
 VALUE IS LOW AT THIS TIME. PLEASE ADJUST.
 PLEASE KNOW A VALUE MAY BE ADJUSTED BY THIS OFFICE
 USING ADOPTED DOCUMENTS INTO THE FBC.
 FBC 108.3
  
 7) NOTE: PLEASE SEE THE 2004 FBC W/ 2006 REVISIONS FOR
 CHAPTER 13. AT THIS TIME THERE ARE SEVERAL ITEMS
 MISSING FOR REVIEW.
 PLEASE SEE NO SCHEDULING OF SYSTEM WAS SUBMITTED.
 PLEASE SEE NO INFORMATION ON A SYSTEM WAS SUBMITTED.
 PLEASE SEE NO OVER RIDE DEVICES AT THE POINTS OF
 EGRESS/INGRESS INTO SPACE FROM ENTRANCE WIN WHICH THE
 OCCUPANT CAN SEE THE LIGHTING WHICH IS BEING
 CONTROLLED.
 PLEASE SEE NO TIMES ON ANY OVER RIDE DEVICES AND TYPES
 OF DEVICES.
 PLEASE SEE MISSING ENERGY CALCULATIONS.
 PLEASE SEE MISSING LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SEE MISSING CERTIFICATIONS PER DESIGNER(S) OF
 RECORD.
 PLEASE SEE REQUIRED CALCULATION METHODS FOR TRACK
 LIGHTING. 13-415.2.ABC.1.2
  
 PLEASE SEE 13-103.1, 13-415.1ABC.1, 13-415.1.ABC.1.1,
 .1.2 AND .1.3, 13-415.1.AB.1.1, 13-415.1.A, .B AND .C,
 13-415.2 AND TABLES UNDER THE NEW 2006 REVISIONS. ETC.
  
 8) NOTE: PLEASE SEE PLANS NOTES FOR GFI PROTECTION
 WHERE CODES ARE ADOPTED HOWEVER PLEASE ACTUALLY SHOW
 WHERE THE PROTECTION WILL BE. PLEASE INDICATE BY THE
 DEVICES OR BREAKERS. QUOTING THE CODE LIEU OF SHOWING
 SPECIFIC DETAIL IS NOT PERMITTED.
  
 9) NOTE: PLEASE INDICATE INTERLOCKS/SHUNT-DEVICES FOR
 ANY LIGHTING ETC WHICH ARE FED TO HOOD.
 NFPA-96
  
 10) NOTE: PLEASE INDICATE TRANSFORMER GROUNDING. THE
 SIZE CONNECTIONS ETC RE REQUIRED TO BE SHOWN, NOT ONLY
 QUOTED CODE.
 250.20,250.30,250.66
  
 11) NOTE: PLEASE CLARIFY HOW THE FEEDERS ON THE LINE
 SIDE OF THE TRANSFORMER CAN CONTAIN A NEUTRAL WHEN THIS
 IS GOING TO BE A SEPARATELY DERIVED SYSTEM? PLEASE SEE
 FEEDER NUMERICAL DESIGNATIONS OF#39 WHICH CONTAINS A
 NEUTRAL.
  
 12) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON LEGEND
 ONLY. PLEASE INCLUDE ON LAYOUT OF PLANS AND DEVICES.
 PLEASE KNOW EVEN THOUGH FIRE SPRINKLER AND FIRE ALARM
 WORK WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT THE
 BASE FIRE ALARM DEVICES ALONG WITH FIRE PROTECTION WILL
 BE REQUIRED IN BASE PLANS. THIS WILL BE NOTED BY THE
 FIRE AND BUILDING REVIEWER(S) ALSO.
  
 13) NOTE: PLEASE SEE MISSING SIGN CIRCUIT ON PLANS AND
 PANEL SCHEDULE PER 600.5.
  
 14) NOTE: PLEASE VERIFY SERVICE AS SHOWN AS THE RISER
 MENTIONS THE METER IS BEING DONE BY THE LANDLORD?? THIS
 SCOPE OF WORK HAS NOT BEEN DONE/OR APPLIED FOR. PLEASE
 SEE THE RISER SEEMS TO SHOW THE NEW TENANT MAIN AS NEMA
 3R WHICH LENDS TO THIS BEING LOCATED OUTSIDE? PLEASE
 KNOW THAT THIS BUILDING CONTAINS AN INDOOR ELECTRICAL
 ROOM WHERE ALL TENANT MAIN DISCONNECTS ARE LOCATED.
 PLEASE PROVIDE A LAYOUT FOR LOCATIONS AND LOADS OF THE
 NEW ON THE EXISTING MAIN WITH THE EXISTING LOADS.
 PLEASE KNOW AT THIS TIME THERE ARE ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SEE NEC 220 IN THE 2005 NEC AS THE CALCULATIONS
 AND LOAD SUMMARY FOR THIS SERVICE AND LOADS WITH
 EXISTING SERVICE NEED TO BE SHOWN PER NEW CODE. PLEASE
 SEE PLANS WHICH CONTAIN CODE SECTIONS FROM THE PREVIOUS
 NEC.
 FBC 106.3.5.1.2
  
 15) NOTE: PLEASE INDICATE A *FLOATING NEUTRAL* IN METER
 AS REQUIRED PER 250.6 AND 250.24. THIS WILL ALLEVIATE
 ANY OBJECTIONABLE CURRENTS.
  
 16) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF
 EMERGENCY LIGHTING AND EXIT LIGHTING.THE PLAN
 MENTIONS 701, 701.11F WHICH IS NOT APPLICABLE.
 FBC 106.1.2
  
 17) NOTE: PLEASE BE SURE ALL EQUIPMENT CONTAINS THE AIC
 RATINGS AS REQUIRED PER 110.9. PLEASE INDICATE FOR THE
 NEW MAIN ON RISER AS SHOWN.
  
 18) NOTE: PLEASE SEE NEC 408.4 AS THE CIRCUITS IN PANEL
 SCHEDULES NEED TO BE SPECIFIC TO THE ROOMS AND AREAS IN
 WHICH THEY FEED. PLEASE THE FOLLOWING TEXT WHICH IS
 BEING EXTRACTED FROM THE NEC HANDBOOK.
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 19) NOTE: PLEASE SUBMIT THE MANUFACTURES SPEC/CUT
 SHEETS ON THE PROPOSED POWER DISTRIBUTION CENTER FOR
 REVIEW. PLEASE BE SURE LISTINGS FROM A NRTL( NATIONALLY
 RECOGNIZED TESTING LABORATORY) IS SHOWN.
 110.3, 90.7.
 FBC 106.1.2.
  
 20) NOTE: PLEASE SEE THE COLOR CODING SHALL BE AS
 FOLLOWS.
 277/480V SYSTEMS, BROWN, PURPLE, YELLOW.
 PLEASE SEE THAT THE NEC HAS *ORANGE* DESIGNATED FOR
 MARKING OF A *HIGH-LEG* IN AN OPEN DELTA SYSTEM WHICH
 IS NOT WHAT IS BEING INSTALLED.
 PLEASE KNOW AS PER LOCAL JURISDICTIONS AND LOCAL WIRING
 AT THE LOCATION OF SAID PROJECT THE COLOR CODING OF THE
 EXISTING SYSTEMS IN THIS BUILDING IS AS NOTED. 90.4
  
 21) NOTE: PLEASE SEE THAT PANEL M AND RISER IS SHOWING
 A FEED TO A PANEL *S* YET THE PLANS SUBMITTED DO NOT
 SHOW ANY PANEL *S*??
 PLEASE SUBMIT THE COMPLETED PLANS SHOWING THIS PANEL.
 FBC 106.3.5.1.2
  
 22) NOTE: PLEASE SEE THE TRANSFORMER WHICH IS BEING
 SHOWN ABOVE OFFICE IS NOT PERMITTED AT THIS LOCATION
 PER 450.13B AND 450.21B.
 PLEASE PROVIDE MORE DETAILS AND INFORMATION ON TYPE OF
 TRANSFORMER. THE LOCATION IS NOT PERMITTED BASED ON
 PLANS SUBMITTED.
 110.3, 90.7
 FBC 106.3.5.1.2
  
 23) NOTE: PLEASE SEE MISSING ROOFTOP ELECTRICAL PLANS,
 A/C PLANS FOR ELECTRICAL DISCONNECTS, NEW OR EXISTING
 GFI REQUIRED FOR EQUIPMENT ETC.
 440.11, 210.63 .
 PLEASE SUBMIT.
 FBC106.1.2
  
 24) NOTE: PLEASE KNOW ANY LOCK OFF/ON DEVICES SHALL BE
 AN INTEGRAL PART OF THE BREAKER, NOT ONE THAT ONLY
 SNAPS INTO PLACE OR CAN BE EASILY REMOVED OR FALL OFF
 WHEN PANEL COVER IS REMOVED.
 110.3, 90.4.
  
 ** PLEASE KNOW AS THERE IS SUBSTANTIAL INFORMATION
 WHICH WAS NOT SUBMITTED A COMPLETE REVIEW FOR CODE
 COMPLIANCE COULD NOT BE DONE AND THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II