2007-05-15 16:23:37BUILDING PLAN REVIEW
 PERMIT: 07030523
 ADD: 700 S ROSEMARY# 142
 CONT: PEMBERTON BUILDERS
 TEL: (561)718-8624
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4) SHEET G-SP1 DESIGN STRESS REFERENECS THE 2003 IBC
 PLEASE CORRECT TO THE 2004 FBC W /2006 REVISIONS
  
 5)THE PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA
 FOR THE NEW WINDOWS AND DOORS,
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF. POSITIVE AND NEGATIVE
 ZONE 4 & 5.
  
 6 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT WINDOWS
 B) MULLIONS
 C) GLAZED SWING DOORS (EXTERIOR)
 D) EXTERIOR METAL SWING DOORS
 E) PRE ENGINEERED A/C STANDS
 F) EFIS SYSTEMS
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) SHEET G-SP2HEADING 815-C INSTALLATIONINDICATES
 A WIND PRESSURE OF 26PSF PLEASE SEE TABLE
 1609.6.2.1(1)ALSO SEE MULTIPLIERS THE SHOPPING CENTER
 AND PARKING GARAGE ARE CONSIDERED ONE 5 STORY
 BUILDING!!!! SEE TABLE 1609.6.2.1(4) FOR MULTIPLIERS.
  
 11)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 12)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 13) THE MEP SHEETS THE ENGINEERS SIGNATURE IS A STAMP
 NOT AN ORIGINAL SIGNATURE,
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 14)PLEASE PROVIDE INFORMATION ON THE FREEZER AND
 WALK-IN COOLERS:
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND SELF-IGNITION
 TEMPERATURES OF NOT LESS THAN 600?F AND 800?F (316?C
 AND 427?C), RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
  
 2603.4.1.3 WALK-IN COOLERS.
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE
 FLOOR AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 )
 AND THE FOAM PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 15) FOR THE BUILDING AREA INCREASES WERE TAKEN, PLEASE
 PROVIDE FIRE SPRINKLER PLANS FOR THE BUILD OUT AND
 COOLER/ FREEZER.
  
 16)SHEET A2.3 DOESN'T INDICATE COMPLIANCE WITH:
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 11-5.3 ACCESS AISLES.
 ALL ACCESSIBLE FIXED TABLES SHALL BE ACCESSIBLE BY
 MEANS OF AN ACCESS AISLE AT LEAST 36 INCHES (915 MM)
 CLEAR BETWEEN PARALLEL EDGES OF TABLES OR BETWEEN A
 WALL AND THE TABLE EDGES.
  
 11-5.4 DINING AREAS.
 IN NEW CONSTRUCTION, ALL DINING AREAS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, LOGGIAS, AND OUTDOOR SEATING
 AREAS, SHALL BE ACCESSIBLE. IN ALTERATIONS,
 ACCESSIBILITY TO RAISED OR SUNKEN DINING AREAS, OR TO
 ALL PARTS OF OUTDOOR SEATING AREAS IS NOT REQUIRED
 PROVIDED THAT THE SAME SERVICES AND DECOR ARE PROVIDED
 IN AN ACCESSIBLE SPACE USABLE BY THE GENERAL PUBLIC AND
 ARE NOT RESTRICTED TO USE BY PEOPLE WITH DISABILITIES.
  
 EXCEPTION: NOTHING IN THIS SECTION SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW OCCUPIABLE
 GRADE LEVEL, REGARDLESS OF WHETHER THE CODE REQUIRES AN
 ELEVATOR TO BE INSTALLED IN SUCH BUILDINGS, STRUCTURES
 OR FACILITIES EXCEPT: (1) ELEVATOR PITS, ELEVATOR
 PENTHOUSES, MECHANICAL ROOMS, PIPING OR EQUIPMENT
 CATWALKS, AND AUTOMOBILE LUBRICATION AND MAINTENANCE
 PITS AND PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS
 ROOMS, ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. THEREFORE, FACILITIES SUBJECT TO THE ADA MAY BE
 REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS OTHERWISE
 EXEMPT UNDER SECTION 11-4.1.3 (5), OF THE CODE.
  
 11-5.5 FOOD SERVICE LINES.
 FOOD SERVICE LINES SHALL HAVE A MINIMUM CLEAR WIDTH OF
 36 INCHES (915 MM), WITH A PREFERRED CLEAR WIDTH OF 42
 INCHES (1065 MM) TO ALLOW PASSAGE AROUND A PERSON USING
 A WHEELCHAIR. TRAY SLIDES SHALL BE MOUNTED NO HIGHER
 THAN 34 INCHES (865 MM) ABOVE THE FLOOR (SEE FIGURE
 11-53 ). IF SELF-SERVICE SHELVES ARE PROVIDED, AT LEAST
 50 PERCENT OF EACH TYPE MUST BE WITHIN REACH RANGES
 SPECIFIED IN SECTIONS 11-4.2.5 AND 11-4.2.6 .
  
 17)MPE 1.1 REFRIGARATION STAND SUPPORT INDICATES THAT
 THE STAND WILL BE 24" TALL BUT THE DETAIL INDICATES
 THAT THE BASE PLATE TO CUT THROUGH THE ROOF INSULATION,
 CORIDGATED ROOF DECK AND BEAR DIRECTLY ON THE BAR JOIST
 AT THIS POINT YOU WILL NOT HAVE THE 24" CLEAR HEIGTH
 REQUIRED SEE TABLE 1509.7.
 THE SECOND ISSUE WITH THIS TYPE OF INSTALLATION IS HOW
 WILL THE ROOF SYSTEM BE RESEALED?
  
 18) CHANGE OF USE; 13-101.4.1.1 PREVIOUSLY
 UNCONDITIONED EXISTING BUILDINGS WHICH WERE PERMITTED
 PRIOR TO MARCH 15, 1979 TO WHICH HEATING OR COOLING
 SYSTEMS ARE ADDED SHALL MEET THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN METHODS B OR C OF SUBCHAPTER
 13-4 FOR COMMERCIAL APPLICATIONS
  
 19) AWNINGS AND SIGNS REQUIRE A SEPERATE PERMIT.
  
 20) 3105.1.1.2A FIXED FABRIC AWNING OR FABRIC-COVERED
 FRAME SHALL NOT EXTEND OVER PUBLIC PROPERTY MORE THAN
 TWO-THIRDS THE DISTANCE FROM THE PROPERTY LINE TO THE
 NEAREST CURB LINE IN FRONT OF THE BUILDING SITE AS
 MEASURED FROM THE EXTERIOR FACE OF THE BUILDING NOR
 SHALL ANY PORTION BE CLOSER THAN 18 INCHES (457 MM) TO
 THE CURB LINE.
 EXCEPTIONS:
 1.IF INSTALLED OVER 14 FEET (4267 MM) IN HEIGHT,
 IT MAY OCCUPY THE ENTIRE WIDTH OF THE SIDEWALK.
 2.UNLESS OTHERWISE REGULATED BY LOCAL ZONING
 REQUIREMENTS.
 3105.3.1
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 BE FLAME RESISTANT IN ACCORDANCE WITH NFPA 701.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90
 MPH
 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN
 LIFE OF 0.77.
 3.EXPOSURE CATEGORY B FOR OR C AS DEFINED IN
 CHAPTER 16 .
  
 3105.4.2.2
 THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE
 COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1.MINIMUM WIND VELOCITY AS REQUIRED IN CHAPTER 16
 .
 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN
 LIFE OF 0.77.
 3.EXPOSURE CATEGORY B OR C AS DEFINED IN CHAPTER
 16 .
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 PLAN EXAMINER II BUILDING
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  