2007-12-05 10:51:41 
  
  
 PASSED/PROVISO'S:
  
 1. ALL LAV FAUCETS SHALL COMPLY WITH 11-4.19.5.
  
 2. THE EMPLOYEE SINK FAUCET SHALL COMPLY WITH SECTION
 11-4.24.7.
  
 3. THE EMPLOYEE SINK SHALL COMPLY WITH SECTION
 11-4.24.4.
  
 4. AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE.
  
 5. SUBMIT A STORM RISER DIAGRAM FOR THE ROOF DRAINS
 PIPING FOR ROOF DRAINS AT COL. LINE 3 & COL. LINE 4.
 SHOW ALL PIPE SIZES AND INDICATE SQUARE FOOTAGE BEING
 DRAINED. SECTION 106.3.5.1.3(7)(13). (SUBMIT PRIOR TO
 FIRST ROUGH INSPECTION OF U/G STORM).
  