Plan Review Notes
Plan Review Notes For Permit 07030491
Permit Number 07030491
Review Stop P
Sequence Number 3
Notes
Date Text
2007-10-12 08:48:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SUBMIT A STORM RISER DIAGRAM FOR THE ROOF DRAINS
 PIPING FOR ROOF DRAINS AT COL. LINE 3 & COL. LINE 4.
 SHOW ALL PIPE SIZES AND INDICATE SQUARE FOOTAGE BEING
 DRAINED. SECTION 106.3.5.1.3(7)(13).
  
 2. SEE PROVISO'S FROM REVIEW DATED 7-11-7. PLEASE SHOW
 COMPLIANCE FOR ALL ITEMS IN PROVISO.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]