| Plan Review Notes For Permit 07030491 |
| Permit Number |
07030491 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-10-12 13:20:09 | *****DENIED***** | | | | | | *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 04.ON THE APPROPIATE EXTERIOR ELEVATION ON A2.1, | | | DISPLAY THE NUMERICAL ADDREESS ON THE BUILDING TO BE | | | VISIBLE FROM OKEECHOBEE BOULEVARD. SHOW ACTUAL | | | ADDRESS NUMBER ON APPROPIATE EXTERIOR ELEVATION | | | | | | 05.INTERIOR WALL AND CEILING FINISH MATERIAL SHALL BE | | | CLASS A OR CLASS B.PLEASE BE ADVISED THAT THE | | | RESPONSE ON SHEET A3.1 REFERS TO NFPA 2001.THIS | | | SHOULD BE NFPA 2003 | | | | | | 12. THIS STRUCTURE WILL HAVE A FIRE ALARM SYSTEM. | | | PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM SIGNED, | | | SEALED, AND DATED. | | | | | | 13.IT IS INDICATED THAT THE STRUCTURE IS TO BE 100% | | | SPRINKLERED.PROVIDE A LAYOUT OF THE FIRE SPRINKLER | | | SYSTEM SIGNED, SEALED, AND DATED. | | | | | | *NEW COMMENT | | | | | | AA.ON SHEET LS.1 UNDER CODE REQUIREMENTS,AMEND NOTE | | | TO REFLECT FLORIDA FIRE PREVENTION CODE 2004 EDITION | | | AND NFPA 101 - 2003 EDITION. | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM | | | WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|