Plan Review Notes
Plan Review Notes For Permit 07030491
Permit Number 07030491
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2007-10-12 13:20:09*****DENIED*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION ON A2.1,
 DISPLAY THE NUMERICAL ADDREESS ON THE BUILDING TO BE
 VISIBLE FROM OKEECHOBEE BOULEVARD. SHOW ACTUAL
 ADDRESS NUMBER ON APPROPIATE EXTERIOR ELEVATION
  
 05.INTERIOR WALL AND CEILING FINISH MATERIAL SHALL BE
 CLASS A OR CLASS B.PLEASE BE ADVISED THAT THE
 RESPONSE ON SHEET A3.1 REFERS TO NFPA 2001.THIS
 SHOULD BE NFPA 2003
  
 12. THIS STRUCTURE WILL HAVE A FIRE ALARM SYSTEM.
 PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM SIGNED,
 SEALED, AND DATED.
  
 13.IT IS INDICATED THAT THE STRUCTURE IS TO BE 100%
 SPRINKLERED.PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM SIGNED, SEALED, AND DATED.
  
 *NEW COMMENT
  
 AA.ON SHEET LS.1 UNDER CODE REQUIREMENTS,AMEND NOTE
 TO REFLECT FLORIDA FIRE PREVENTION CODE 2004 EDITION
 AND NFPA 101 - 2003 EDITION.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722