2007-06-25 18:09:38*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS RESPONSE TO
 THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 03.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, DUST,
 AND DEBRIS SHALL BE REMOVED FROM THE SITE AT THE END OF
 EACH SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE
 OPERATION.
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION ON A2.1,
 DISPLAY THE NUMERICAL ADDREESS ON THE BUILDING TO BE
 VISIBLE FROM OKEECHOBEE BOULEVARD.PLEASE NOTE THAT
 THE ADDRESS IS TO VISIBLE EVEN IF SECURITY AND/OR
 HURRICANE SHUTTERS ARE INSTALLED.
  
 05.INTERIOR WALL AND CEILING FINISH MATERIAL SHALL BE
 CLASS A OR CLASS B.BE SPECIFIC
  
 06.INTERIOR FLOOR FINISHSHALL BE CLASS I OR CLASS II.
 BE SPECIFIC
  
 07.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 08.PROVIDE TRAVEL DISTANCE TO EXITS AS IN ACCORDANCE
 7.6.1 OF NFPA 101 I.E. LIFE SAFETY PLAN.
  
 09.ADDITIONAL EXIT SIGNS MAY BE REQUIRED WHEN RACKS,
 SHELVES, AND OTHER EQUIPMENT OBSCURE VISIBILITY OF THE
 NOW PROPOSED EXIT MARKINGS.
  
 10.CHECKOUT STANDS OR ASSOCIATED RAILINGS OR BARRIERS
 SHALL NOT OBSTRUCT EXITS, REQURED AISLES, OR APPROACHES
 THERETO.
  
 11.AISLES LEADING TO EACH EXIT SHALL BE REQUIRED AND
 THE AGGREGATE WIDTH SHALL NOT BE LESS THAN THE REQUIRED
 WIDTH OF THE EXIT.OTHER AISLES SHALL NOT BE LESS THAN
 36" IN CLEAR WIDTH.
  
 12.WILL THIS STRUCTURE HAVE A FIRE ALARM SYSTEM?IF
 SO, PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM.
  
 13.IT IS INDICATED THAT THE STRUCTURE IS TO BE 100%
 SPRINKLERED.PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW