Plan Review Notes
Plan Review Notes For Permit 07030491
Permit Number 07030491
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-22 14:16:15*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE STILL SOME NOTES FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:SAME NOTE FROM PREVIOUS REVIEW. THE RESPONSE
 LETTER FROM ARCHITECT MENTIONS THIS WILL BE ADDRESSED
 BY THE CONTRACTOR HOWEVER THIS IS NOT THE
 RESPONSIBILITY OF THE CONTRACTOR. IT IS THE
 RESPONSIBILITY OF THE DESIGNER OR FIRM AS NOTED.
 PLEASE ALSO SEE SOME *L* SHEETS IN SETS WHICH ARE NOTE
 SIGNED, DATED OR SEALED.
 PLEASE SEE MISSING LICENSE NUMBER FOR THE LANDSCAPE
 FIRM AS LISTED ON THE TITLE BLOCKS FOR *L* SHEETS. THIS
 IS ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE SEE 481.219, FAC 61G1-16.004
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 2) NOTE:SAME NOTE AS PREVIOUS REVIEW. THE RESPONSE
 LETTER FROM ARCHITECT MENTIONS THIS WILL BE ADDRESSED
 BY THE CONTRACTOR HOWEVER THIS IS NOT THE
 RESPONSIBILITY OF THE CONTRACTOR. IT IS THE
 RESPONSIBILITY OF THE DESIGNER OR FIRM AS NOTED PLEASE
 SEE THE MISSING LICENSE NUMBER FOR THE SURVEY FIRM AS
 REQUIRED PER FS 472.021. 61G17
 ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3) NOTE:PLEASE SEE THIS COMMENT REMAINS AS THE PLANS
 NOW INDICATE A 2005 NFPA-72 WHICH IS NOT YET ADOPTED BY
 THE STATE OF FLORIDA. PLEASE SEE THE PREVIOUS REVIEW
 NOTES BELOW WHICH GIVE THE CODES TO BE ON PLANS. PLEASE
 SEE THERE ARE STILL LOCATIONS ON PLANS ON SHEETS WHICH
 WERE NOTE CHANGED OUT WHICH REFLECT THE *STANDARD
 BUILDING CODE*.
 ** PREVIOUS REVIEW NOTE*
 PLEASE SEE THAT ALL OF THE CODES WHICH PLANS ARE UNDER
 DESIGN AND RECORD SHALL BE STATED ON PLANS AS FOLLOWS.
 PLEASE SEE THAT THERE ARE SEVERAL LOCATIONS WHICH CODES
 FROM OLDER ADOPTED CODES ARE STATED ON PLANS. PLEASE
 ALSO SEE THAT THE PLANS ALSO CONTAIN STATEMENTS IN
 DIFFERENT LOCATIONS FOR THE *STANDARD BUILDING *.
 PLEASE KNOW THAT THE STANDARD BUILDING CODE WAS NO
 LONGER IN AFFECT AS OF MARCH 1ST, 2002 WHEN THE STATE
 OF FLORIDA ADOPTED THE 2001 FBC.
 PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE FOLLOWING
 CODE(S) WERE ADOPTED. PLEASE LIST THE FOLLOWING AT A
 MINIMUM FOR THIS REVIEWER.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** THESE ARE REQUIRED FOR THIS REVIEWER AT A MINIMUM
 AND OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE ADDRESS FOR THIS PROJECT IS
 9921 OKEECHOBEE BLVD. PLEASE INCLUDE THIS INFORMATION
 AS REQUIRED ON TITLE BLOCKS. PLEASE SEE NUMEROUS SHEETS
 FROM PREVIOUS REVIEW NOT ONLY FOR ELECTRICAL BUT FOR
 OTHER TRADE SHEETS AS WELL DO NOT SHOW THE ADDRESS. THE
 LOCATION AS NOTED TO THE NEAREST MAIN INTERSECTION IS
 NOT ACCEPTABLE.
 THIS IS TO BE CORRECTED ON ALL SHEETS EVEN IF COMMENT
 IS NOT MADE BY OTHER TRADE(S). PLEASE KNOW THAT SHEETS
 WHICH MAY ALREADY CONTAIN STAMPS FROM REVIEWERS MAY
 HAVE THE CORRECT ADDRESS PLACED ON SHEETS BY PERMANENT
 MEANS. (PRINTED, STAMPED ETC)
 FAC 61G1-16.004, FAC 61G15-23.002
  
 5) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR
 CHAPTER 13. PLEASE SEE RESPONSE MENTIONS TO SEE TIMES
 FOR OVER RIDE DEVICES ON SHEETS AND 4.1 YET THESE TIMES
 FOR OCCUPANCY TYPE DEVICE COULD NOT BE LOCATED ON
 PLANS.
 PLEASE SEE THE ENERGY CALCULATION AS SUBMITTED STILL DO
 NOT CORRELATE WITH THE FIXTURE LEGEND AND FIXTURE NOTES
 ON THE SAME SHEET AS FIXTURE LEGEND. PLEASE SEE THE
 NUMBER OF FIXTURE, TYPES AND WATTAGES NEED TO
 COORDINATE WITH THE ENERGY CALCULATIONS.
 KEYED NOTE #4 ON LIGHTING SHEETS MENTIONS TO SEE NOTE
 #111 ON E4.1, HOWEVER THE NOTE ON E4.1 DOES NOT
 ELABORATE ON DEVICE TIMES?
 LIGHTING CASES?
 13-415.1.ABC1.1, .1.2, .1.3.
 ** PLEASE SEE THAT THE OWNER AGENT IS NOT SIGNED ON
 ENERGY CALCULATIONS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE
 SOME LOCATIONS WHICH DO NOT INDICATE ANY LIGHTING
 CONTROLS UNDER AN AUTOMATED MEANS. PLEASE SEE THAT
 THESE DEVICES NEED TO BE SHOWN AS SOME OF THE DEVICES
 SHOWN SEEM TO BE NORMAL CONTROL SWITCHES AND SOME AREAS
 DO NOT SEEM TO INDICATE OCCUPANCY TYPE DEVICES. PLEASE
 SEE THE COOLER, FREEZER, DRIVE THRU SWITCH, TOWER
 SWITCH, PHOTO-LAB ETC. PLEASE VERIFY ALL LOCATIONS.
 PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES, AND TIMES
 FOR ALL DEVICES. THE PLANS DO CONTAIN SOME NOTES WHICH
 STATE 2HRS HOWEVER NOT FOR ALL.
 PLEASE SEE OUTSIDE LIGHTING IS REQUIRED TO BE ON AN
 ASTRONOMICAL TIME CLOCK WITH CONTROLS TO SHUT LIGHTING
 OFF WHEN SUFFICIENT DAY LIGHT IS PRESENT.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE
 THE LIGHTING FIXTURE LEGEND DOES NOT CORRELATE WITH THE
 ENERGY CALCULATIONS SUBMITTED. PLEASE ALSO SEE THE
 TOTAL WATTAGE AND MAXIMUM LIGHTING POWER DENSITIES AS
 SHOWN CAN NOT BE VERIFIED. PLEASE SEE THAT THE LIGHTING
 ENERGY CALCULATIONS DO NOT INDICATE THE EXTERNAL AND
 EXTERIOR LIGHTING AS SHOWN ON PLANS.
 PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED
 INDICATES *MANUAL ON/OFF* FOR ALL LIGHTING? PLEASE SEE
 THAT THIS IS NOT POSSIBLE WHEN THE LIGHTING IS
 AUTOMATED.
 PLEASE SEE THE SHEET #3 NEEDS TO CONTAIN THE
 INFORMATION AS NEEDED FOR PRINTED INFORMATION FOR THE
 DESIGNER OF RECORD, SIGNED, DATED AND SEAL.PLEASE BE
 SURE ALL TO SEE 13-103.1.1.1
  
 6) NOTE:PLEASE SEE THE RESPONSE TO THIS COMMENT
 MENTIONS TO SEE SHEETS E1.1 AND E2.1A HOWEVER PLEASE
 CLARIFY AND SHOW AS NOTED ON PREVIOUS REVIEW WHERE
 THESE ARE FIGURED INTO THE LOAD CALCULATIONS PER NEC
 SECTIONS AS GIVEN.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SHOW WINDOW/DISPLAY WINDOW AREAS
 WHICH WILL REQUIRE RECEPTACLES LOCATED ABOVE THE WINDOW
 AREAS AND PORTIONS THEREOF.PLEASE SEE THE LOADS FOR
 THE SHOW WINDOWS SHALL COMPLY WITH 220.43A FOR FEEDER
 CALCULATIONS. THE CALCULATION OF 200 VOLT-AMPERES FOR
 EACH LINEAR FOOT OF A SHOW WINDOW IS REQUIRED TO
 DETERMINE THE FEEDER LOAD. SEE THE COMMENTARY FOLLOWING
 220.14(G) FOR LOAD CALCULATIONS FOR BRANCH CIRCUITS IN
 SHOW WINDOWS.
 AS NO LOAD CALCULATIONS WERE SUBMITTED, REVIEW OF THIS
 FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 7) NOTE:PLEASE SEE THE PREVIOUS NOTE REQUESTED A
 SIGNED, DATED, SEALED AND NOTARIZED LETTER FROM THE
 DESIGNER O RECORD FOR SIGNATURE. PLEASE SEE A LETTER
 WAS SUBMITTED HOWEVER PLEASE SEE THIS LETTER IS NOT
 ORIGINAL, AND IT WAS NOT SEALED.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS APPEAR TO BE SIGNED WITH INITIALS, IF
 THIS IS INDEED THE LEGAL SIGNATURE PLEASE SUBMIT A
 SIGNED, DATED AND SEALED NOTARIZED LETTER. FS 471.025
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 PLEASE ALSO BE SURE THE LETTER IS ORIGINAL AND IS
 PROPERLY NOTARIZED PER FS 117.05.
  
 8) NOTE: PLEASE SEE NO INFORMATION WAS SUBMITTED FOR
 THE MINIMUM COMPLIANCE FOR ADA PER FBC AS PREVIOUSLY
 STATED. RESPONSE MENTIONS THIS WILL BE COMPLIED WITH,
 HOWEVER COULD NOT LOCATE THIS AND RESPONSE IS UNCLEAR.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT PLANS MENTIONS FIRE ALARM SYSTEM AND
 SECURITY ALARM SYSTEM.
 PLEASE KNOW BASED ON THIS BUILDING AND IT BEING
 SPRINKLED AND FIRE ALARM PROTECTED, PLEASE SEE FIRE
 REVIEW COMMENTS WHICH WILL REQUIRED FIRE SPRINKLER
 LAYOUT AND PLEASE SHOW FA DEVICES ON BASED BUILDING
 PLANS. PLEASE KNOW THAT EVEN THOUGH ANY FIRE ALARM AND
 FIRE SPRINKLER WORK WILL BE DONE UNDER A SEPARATE
 PERMIT, THE BASE PLANS ARE REQUIRED TO SHOW
 PROTECTION.
 PLEASE BE SURE ALL DEVICES AS REQUIRED IN FBC
 11-4.28.1, .2 AND .3(4) AS SHOWN WITH MINIMUM LEVELS
 FOR ADA COMPLIANCE.
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE UPS SYSTEM EQUIPMENT.
 110.3, 90.7
  
 10) NOTE: PLEASE DO NOT ATTACH ALL OF THE RESPONSES,
 LETTERS REPORTS, PRODUCT APPROVALS, AND OTHER
 SUPPORTING DOCUMENTS DOWN THE LEFT SIDE OF PLANS. THIS
 SHOULD BE ATTACHED, MADE INTO TWO SEPARATE SETS OF
 SUPPORTING DOCUMENTS. (FOLDERS, SPIRAL BOUND, TABBED
 ETC.
 THESE DOCUMENTS WERE REMOVED FROM ONE SET FOR EASE OF
 REVIEW.
 FBC ADMIN SECTION 106.3
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.