| 2007-04-06 17:45:48 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A1.1 ROOM FINISH SCHEDULE. SUBMIT MANUF. |
| | SPECIFICATIONS SHEETS FOR THE FIBERGLASS POLYESTER |
| | PANELS. PLANELS SHALL COMPLY WITH THE REQUIREMENTS TO |
| | BE "SMOOTH, HARD, NONABSORBENT" MATERIALS AS REQUIRED |
| | IN SECTION 1210.2. |
| | |
| | 2. SHT A1.3 ROOF DRAINAGE CALCULATIONS INDICATE 4 6" |
| | ROOF DRAINS AND 3 8"X24" OVERFLOW SCUPPERS. SHT P2.2 |
| | ROOF LEADER RISER SHOWS A 8"X16" PRIMARY SCUPPER AND |
| | 8"X16" OVERFLOW SCUPPERS. PLEASE CORRELATE ROOF |
| | DRAINAGE INFORMATION. TABLE 1106.3 & SECTION 106.1.1. |
| | |
| | 3. SHT A4.2 SHOW COMPLIANCE FOR THE FOLLOWING: |
| | A. 11-4.18.4 FLUSH CONTROLS |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 4. SUBMIT A DETAIL FOR THE EMPLOYEE ROOM SINK. SHOW |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | |
| | 5. SHTS P1.1 & P2.2 ITEM 10. ALL INDIRECT WASTE SHALL |
| | BE DRAINED TO EITHER A FLOOR SINK OR A HUB DRAIN. A |
| | FLOOR DRAIN IS NOT AN APPROVED INDIRECT WASTE RECEPTOR. |
| | SECTIONS 802.3 & 802.3.2. |
| | |
| | 6. SHT P2.1 DETAIL #3 WATER HEATER DETAIL. DIELECTRIC |
| | UNIION ARE NOT APPROVED FOR USE IN THE WATER SYSTEM. |
| | DIELECTRIC COUPLINGS ARE APPROVED. PLEASE CHANGE |
| | REFERENCE. |
| | |
| | 7. SHT P2.1 DETAIL 1 AND SHT P2.2 DOMESTIC WATER RISER |
| | DIAGRAM. THE WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES, IN AN "EFFECTIVE RANGE", NOT IN THE |
| | CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 8. ALL PLUMBING SHEETS. THE SIGNATURE OF THE ENGINEER |
| | SIGNING & SEALING THE DOCUMENTS IS REQUIRED. IT APPEARS |
| | THAT INITIALS ARE USED. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE OF THE ENGINEER OF RECORD, THEN A SIGNED, |
| | SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE |
| | WILL BE SUBMITTED FOR OUR FILES. FAC 61G15-23.002(2) |
| | AND FS 471.025. |
| | |
| | 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO |
| | THE BUILDING. THIS SHALL BE AS CLOSE TO THE METER AS |
| | POSSIBLE AND ON PRIVATE PROPERTY. PLEASE INDICATE ON |
| | THE PLANS. SECTION 608.13.2. |
| | |