| 2007-03-20 18:31:26 | ** UNSAT ** |
| | |
| | * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE SEE MISSING LICENSE NUMBER FOR THE |
| | LANDSCAPE FIRM AS LISTED ON THE TITLE BLOCKS FOR *L* |
| | SHEETS. THIS IS ALSO KNOWN AS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | PLEASE SEE 481.219, FAC 61G1-16.004 |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE THE MISSING LICENSE NUMBER FOR THE |
| | SURVEY FIRM AS REQUIRED PER FS 472.021. 61G17 |
| | ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| | |
| | PLEASE ALSO SEE THAT THE SIGNATURE MUST BE ORIGINAL AS |
| | REQUIRED PER FS 472.025 |
| | PLEASE SEE THE PLANS EVEN CONTAIN THE STATEMENT THIS IS |
| | REQUIRED, HOWEVER PLANS CONTAIN A RAISED SEAL OVER A |
| | *PHOTO-COPIED SIGNATURE*. |
| | THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE |
| | BY OTHER TRADES. |
| | |
| | 3) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS |
| | ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS |
| | FOLLOWS. PLEASE SEE THAT THERE ARE SEVERAL LOCATIONS |
| | WHICH CODES FROM OLDER ADOPTED CODES ARE STATED ON |
| | PLANS. PLEASE ALSO SEE THAT THE PLANS ALSO CONTAIN |
| | STATEMENTS IN DIFFERENT LOCATIONS FOR THE *STANDARD |
| | BUILDING *. |
| | PLEASE KNOW THAT THE STANDARD BUILDING CODE WAS NO |
| | LONGER IN AFFECT AS OF MARCH 1ST, 2002 WHEN THE STATE |
| | OF FLORIDA ADOPTED THE 2001 FBC. |
| | PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE FOLLOWING |
| | CODE(S) WERE ADOPTED. PLEASE LIST THE FOLLOWING AT A |
| | MINIMUM FOR THIS REVIEWER. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** THESE ARE REQUIRED FOR THIS REVIEWER AT A MINIMUM |
| | AND OTHER CODES WILL BE REQUIRED FOR OTHER TRADES. |
| | |
| | 4) NOTE: ALL SIGNS, FIRE ALARM, FIRE SPRINKLER, |
| | BURGLAR/SECURITY PERMITS WILL BE UNDER SEPARATE PERMITS |
| | WITH SEPARATE PLANS AND PERMIT FEES. |
| | |
| | 5) NOTE: PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR |
| | AND MATERIALS EVEN IF ANY EQUIPMENT OR MATERIALS ARE |
| | OWNER SUPPLIED.PLEASE SEE THE TOTAL VALUE IS TO |
| | INCLUDE ALL LIGHTING, EQUIPMENT, LOW VOLTAGE ETC. THIS |
| | WILL BE VERIFIED FOR BASE BUILDING AND BASE PME FROM |
| | THE TABLES AS SET-FORTH IN THE FBC. |
| | FBC ADMIN SECTION 108.3 |
| | |
| | 6) NOTE: PLEASE SEE THAT PLANS E0.1 AND E0.1A INDICATE |
| | TWO DIFFERENT TYPES OF SITE LIGHTING POLES EVEN FOR THE |
| | SAME SYMBOL. EACH OF THESE SHEETS ARE DONE BY A |
| | DIFFERENT DESIGNER. PLEASE CORRELATE. |
| | PLEASE SEE ONE SHEET WHICH MENTIONS WIND LOAD RATINGS |
| | TO BE 150MPH AND BELOW. IT CAN BE UNDERSTOOD IF THIS |
| | STATEMENT SAID 150 OR ABOVE, HOWEVER HOW COULD THIS BE |
| | BELOW? |
| | PLEASE SEE THE NEXT LEVEL DOWN STATES 120MPH AND BELOW |
| | AND SO ON. PLEASE KNOW THAT ALL LIGHTING SHALL MEET |
| | THIS AREA FOR WIND LOADSAT 140MPH. |
| | PLEASE SUBMIT THE ENGINEERING ON POLES WITH LIGHTING |
| | FIXTURES WHICH INDICATES THE EFFECTIVE PROJECTED AREA |
| | OF FIXTURES ETC. THE ACTUAL CALCULATIONS WILL BE |
| | REVIEWED BY THE BUILDING REVIEWER ONCE SUBMITTED. |
| | PLEASE SEE THAT THE SITE PLANS INDICATE LIGHTING POLES |
| | LOCATED OFF SITE AND NOT ON THIS PROPERTY/LEGAL |
| | ADDRESS. PLEASE KNOW THAT THESE WILL BE REQUIRED UNDER |
| | A SEPARATE PERMIT AND MAY NOT BE INCLUDED ON THESE |
| | PLANS. |
| | |
| | 7) NOTE: PLEASE SEE THE ADDRESS FOR THIS PROJECT IS |
| | 9921 OKEECHOBEE BLVD. PLEASE INCLUDE THIS INFORMATION |
| | AS REQUIRED ON TITLE BLOCKS. |
| | FAC 61G1-16.004, FAC 61G15-23.002 |
| | |
| | 8) NOTE: PLEASE SEE THAT A VOLTAGE DROP SUMMARY WAS |
| | SUBMITTED FOR PANELS AND SOME ITEMS HOWEVER NOT |
| | SUBMITTED FOR SITE LIGHTING AND OTHER WORST CASE |
| | SCENARIOS PER FBC 13-413.1ABC.1 |
| | |
| | 9) NOTE: PLEASE SEE THE LOCATION OF THE MAIN SERVICE |
| | MEANS OF DISCONNECT IS NOT APPROVED AT THIS TIME PER |
| | THIS AHJ. |
| | PLEASE SEE THAT THE LOCATION SHALL BE READILY |
| | ACCESSIBLE AT THE NEAREST POINT OF ENTRANCE INTO THE |
| | BUILDING IF THE MAIN IS GOING TO BE LOCATED INSIDE THE |
| | BUILDING. AS SHOWN ON PLANS, THIS MAIN IS ONLY OBTAINED |
| | IN THE CASE OF AN EMERGENCY BY FIRE DEPARTMENT |
| | PERSONNEL BY TRAVERSING THROUGH AT LEAST FOUR LOCKED |
| | DOORS AND A SUBSTANTIAL NOT RATED PATH OF TRAVEL INTO |
| | THE BUILDING. |
| | PLEASE KNOW THAT THIS HAS BEEN GONE OVER WITH THE FIRE |
| | MARSHAL CHIEF AND LOCATION IS ALSO NOT ACCEPTED. ** |
| | PLEASE CALL TO GO OVER OTHER LOCALS IF NEED BE. (LOCATE |
| | MAIN OUTSIDE, DOOR FROM OUTSIDE INTO THE MAIN |
| | ELECTRICAL FIRE RATED (1HR MINIMUM) ROOM? ETC) 230.70, |
| | 230.71, 90.4 NEC. |
| | FBC ADMIN SECTION 104.6 |
| | |
| | 10) NOTE: PLEASE SEE PLANS APPEAR TO INDICATE SOME SORT |
| | OF *OUTLET* TAPPED FROM THE WATER HEATER SHOWN ON |
| | PLANS? PLEASE CLARIFY THIS. |
| | FBC 106.1.2. |
| | |
| | 11) NOTE: PLEASE KNOW THAT ANY (LOCK ON/LOCK OFF |
| | DEVICES WHICH ARE BEING INSTALLED ONLY IN THE ATTEMPT |
| | TO BE USED AS THE DISCONNECTING MEANS OF EQUIPMENT OR |
| | APPLIANCES SHALL HAVE THE DEVICE PERMANENTLY AFFIXED TO |
| | BREAKER SO THAT THE DEVICE CAN NOT BE READILY REMOVED |
| | UNLESS THE BREAKER IS REMOVED. |
| | PLEASE KNOW IF NONE OF THE DEVICES AS NOTED ON PLANS |
| | ARE FOR THIS PURPOSE AND ONLY BEING USED FOR LOCKING ON |
| | THE CIRCUITS THEN PLEASE STATE DEVICE(S). |
| | PLEASE KNOW THAT A NOTE WILL BE REQUIRED ON PLANS IN |
| | ADDITION TO THE *LOCK-OFF* NOTE WHICH STATES THAT THE |
| | DEVICE MUST BE AN INTEGRAL PART OF THE BREAKER OR WORDS |
| | TO THAT AFFECT. |
| | 110.3, 90.4. |
| | |
| | 12) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR |
| | CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE |
| | SOME LOCATIONS WHICH DO NOT INDICATE ANY LIGHTING |
| | CONTROLS UNDER AN AUTOMATED MEANS. PLEASE SEE THAT |
| | THESE DEVICES NEED TO BE SHOWN AS SOME OF THE DEVICES |
| | SHOWN SEEM TO BE NORMAL CONTROL SWITCHES AND SOME AREAS |
| | DO NOT SEEM TO INDICATE OCCUPANCY TYPE DEVICES. PLEASE |
| | SEE THE COOLER, FREEZER, DRIVE THRU SWITCH, TOWER |
| | SWITCH, PHOTO-LAB ETC. PLEASE VERIFY ALL LOCATIONS. |
| | PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES, AND TIMES |
| | FOR ALL DEVICES. THE PLANS DO CONTAIN SOME NOTES WHICH |
| | STATE 2HRS HOWEVER NOT FOR ALL. |
| | PLEASE SEE OUTSIDE LIGHTING IS REQUIRED TO BE ON AN |
| | ASTRONOMICAL TIME CLOCK WITH CONTROLS TO SHUT LIGHTING |
| | OFF WHEN SUFFICIENT DAY LIGHT IS PRESENT. |
| | PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE |
| | THE LIGHTING FIXTURE LEGEND DOES NOT CORRELATE WITH THE |
| | ENERGY CALCULATIONS SUBMITTED. PLEASE ALSO SEE THE |
| | TOTAL WATTAGE AND MAXIMUM LIGHTING POWER DENSITIES AS |
| | SHOWN CAN NOT BE VERIFIED. PLEASE SEE THAT THE LIGHTING |
| | ENERGY CALCULATIONS DO NOT INDICATE THE EXTERNAL AND |
| | EXTERIOR LIGHTING AS SHOWN ON PLANS. |
| | PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED |
| | INDICATES *MANUAL ON/OFF* FOR ALL LIGHTING? PLEASE SEE |
| | THAT THIS IS NOT POSSIBLE WHEN THE LIGHTING IS |
| | AUTOMATED. |
| | PLEASE SEE THE SHEET #3 NEEDS TO CONTAIN THE |
| | INFORMATION AS NEEDED FOR PRINTED INFORMATION FOR THE |
| | DESIGNER OF RECORD, SIGNED, DATED AND SEAL.PLEASE BE |
| | SURE ALL TO SEE 13-103.1.1.1 |
| | |
| | 13) NOTE: PLEASE SEE SOME OF THE DEVICES AS NOTED FOR |
| | OCCUPANCY DEVICES ARE ONLY 180 DEGREE DEVICES, WHICH |
| | WHEN AN OCCUPANT IS LOCATED IN SOME AREAS ON THE PLANS |
| | THIS DEVICE AND THE DIRECTION AS NOTED WOULD NOT PICK |
| | UP ON THE OCCUPANT AND THERE FORE TURNING LIGHTING OFF |
| | AND MAY CREATE A HAZARD. |
| | PLEASE SEE SOME REDLINED AREAS ON PLANS WHICH ARE OF |
| | CONCERN. IF THESE DEVICES ARE COMBO DEVICES WHICH |
| | PROVIDE ULTRASONIC SENSING THEN THIS MAY NOT BE AN |
| | ISSUE. PLEASE VERIFY ALL LOCATIONS AND TYPES OF DEVICES |
| | FOR FULL COVERAGE. |
| | LS 101 7.8, 7.9 |
| | |
| | 14) NOTE: PLEASE SEE MISSING SHOW WINDOW/DISPLAY WINDOW |
| | AREAS WHICH WILL REQUIRE RECEPTACLES LOCATED ABOVE THE |
| | WINDOW AREAS AND PORTIONS THEREOF.PLEASE SEE THE |
| | LOADS FOR THE SHOW WINDOWS SHALL COMPLY WITH 220.43A |
| | FOR FEEDER CALCULATIONS. THE CALCULATION OF 200 |
| | VOLT-AMPERES FOR EACH LINEAR FOOT OF A SHOW WINDOW IS |
| | REQUIRED TO DETERMINE THE FEEDER LOAD. SEE THE |
| | COMMENTARY FOLLOWING 220.14(G) FOR LOAD CALCULATIONS |
| | FOR BRANCH CIRCUITS IN SHOW WINDOWS. |
| | AS NO LOAD CALCULATIONS WERE SUBMITTED, REVIEW OF THIS |
| | FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | |
| | 15) NOTE: PLEASE SEE MISSING SIGN CIRCUIT ON PLANS AND |
| | PANEL SCHEDULE FOR THE MINIMUM LOADS AS INDICATED IN |
| | THE NEC. THIS CIRCUIT IS TO BE LOCATED AT A MINIMUM AT |
| | THE LOCATION OF THE FRONT ENTRANCE AS REQUIRED PER |
| | 600.5. |
| | |
| | 16) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH |
| | INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE PLEASE |
| | SUBMIT A SIGNED, DATED AND SEALED NOTARIZED LETTER. FS |
| | 471.025 |
| | THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY |
| | FUTURE REFERENCE. |
| | PLEASE ALSO BE SURE THE LETTER IS ORIGINAL AND IS |
| | PROPERLY NOTARIZED PER FS 117.05. |
| | |
| | 17) NOTE: PLEASE SEE THAT PLANS MENTIONS FIRE ALARM |
| | SYSTEM AND SECURITY ALARM SYSTEM. |
| | PLEASE KNOW BASED ON THIS BUILDING AND IT BEING |
| | SPRINKLED AND FIRE ALARM PROTECTED, PLEASE SEE FIRE |
| | REVIEW COMMENTS WHICH WILL REQUIRED FIRE SPRINKLER |
| | LAYOUT AND PLEASE SHOW FA DEVICES ON BASED BUILDING |
| | PLANS. PLEASE KNOW THAT EVEN THOUGH ANY FIRE ALARM AND |
| | FIRE SPRINKLER WORK WILL BE DONE UNDER A SEPARATE |
| | PERMIT, THE BASE PLANS ARE REQUIRED TO SHOW |
| | PROTECTION. |
| | PLEASE BE SURE ALL DEVICES AS REQUIRED IN FBC |
| | 11-4.28.1, .2 AND .3(4) AS SHOWN WITH MINIMUM LEVELS |
| | FOR ADA COMPLIANCE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 18) NOTE: PLEASE SEE AS NOTED ABOVE FOR CODES; PLEASE |
| | SEE THAT THE LOAD CALCULATIONS INDICATE SECTIONS OF THE |
| | CODE WHICH ARE FROM PREVIOUS CODES NO LONGER IN |
| | EFFECT. |
| | 220.11, 220.13. |
| | |
| | 19) NOTE: PLEASE CLARIFY AND SHOW THE BRANCH CIRCUITS |
| | CONDUCTOR SIZES FOR ALL. CAN BE DONE IN A TYPICAL |
| | DIAGRAM IF THIS IS INDEED THAT CASE, HOWEVER PLEASE SEE |
| | AREAS WITH VOLTAGE DROP WHICH MAY BE AFFECTED TO SHOW A |
| | LARGER CONDUCTOR ON A BRANCH CIRCUIT WITH SMALLER OCP. |
| | 240.4, 310.16 |
| | |
| | 20) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE UPS SYSTEM EQUIPMENT. |
| | 110.3, 90.7 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |