Plan Review Notes
Plan Review Notes For Permit 07030491
Permit Number 07030491
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-20 18:31:26** UNSAT **
  
 * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE MISSING LICENSE NUMBER FOR THE
 LANDSCAPE FIRM AS LISTED ON THE TITLE BLOCKS FOR *L*
 SHEETS. THIS IS ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE 481.219, FAC 61G1-16.004
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 2) NOTE: PLEASE SEE THE MISSING LICENSE NUMBER FOR THE
 SURVEY FIRM AS REQUIRED PER FS 472.021. 61G17
 ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 PLEASE ALSO SEE THAT THE SIGNATURE MUST BE ORIGINAL AS
 REQUIRED PER FS 472.025
 PLEASE SEE THE PLANS EVEN CONTAIN THE STATEMENT THIS IS
 REQUIRED, HOWEVER PLANS CONTAIN A RAISED SEAL OVER A
 *PHOTO-COPIED SIGNATURE*.
 THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS. PLEASE SEE THAT THERE ARE SEVERAL LOCATIONS
 WHICH CODES FROM OLDER ADOPTED CODES ARE STATED ON
 PLANS. PLEASE ALSO SEE THAT THE PLANS ALSO CONTAIN
 STATEMENTS IN DIFFERENT LOCATIONS FOR THE *STANDARD
 BUILDING *.
 PLEASE KNOW THAT THE STANDARD BUILDING CODE WAS NO
 LONGER IN AFFECT AS OF MARCH 1ST, 2002 WHEN THE STATE
 OF FLORIDA ADOPTED THE 2001 FBC.
 PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE FOLLOWING
 CODE(S) WERE ADOPTED. PLEASE LIST THE FOLLOWING AT A
 MINIMUM FOR THIS REVIEWER.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** THESE ARE REQUIRED FOR THIS REVIEWER AT A MINIMUM
 AND OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 4) NOTE: ALL SIGNS, FIRE ALARM, FIRE SPRINKLER,
 BURGLAR/SECURITY PERMITS WILL BE UNDER SEPARATE PERMITS
 WITH SEPARATE PLANS AND PERMIT FEES.
  
 5) NOTE: PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR
 AND MATERIALS EVEN IF ANY EQUIPMENT OR MATERIALS ARE
 OWNER SUPPLIED.PLEASE SEE THE TOTAL VALUE IS TO
 INCLUDE ALL LIGHTING, EQUIPMENT, LOW VOLTAGE ETC. THIS
 WILL BE VERIFIED FOR BASE BUILDING AND BASE PME FROM
 THE TABLES AS SET-FORTH IN THE FBC.
 FBC ADMIN SECTION 108.3
  
 6) NOTE: PLEASE SEE THAT PLANS E0.1 AND E0.1A INDICATE
 TWO DIFFERENT TYPES OF SITE LIGHTING POLES EVEN FOR THE
 SAME SYMBOL. EACH OF THESE SHEETS ARE DONE BY A
 DIFFERENT DESIGNER. PLEASE CORRELATE.
 PLEASE SEE ONE SHEET WHICH MENTIONS WIND LOAD RATINGS
 TO BE 150MPH AND BELOW. IT CAN BE UNDERSTOOD IF THIS
 STATEMENT SAID 150 OR ABOVE, HOWEVER HOW COULD THIS BE
 BELOW?
 PLEASE SEE THE NEXT LEVEL DOWN STATES 120MPH AND BELOW
 AND SO ON. PLEASE KNOW THAT ALL LIGHTING SHALL MEET
 THIS AREA FOR WIND LOADSAT 140MPH.
 PLEASE SUBMIT THE ENGINEERING ON POLES WITH LIGHTING
 FIXTURES WHICH INDICATES THE EFFECTIVE PROJECTED AREA
 OF FIXTURES ETC. THE ACTUAL CALCULATIONS WILL BE
 REVIEWED BY THE BUILDING REVIEWER ONCE SUBMITTED.
 PLEASE SEE THAT THE SITE PLANS INDICATE LIGHTING POLES
 LOCATED OFF SITE AND NOT ON THIS PROPERTY/LEGAL
 ADDRESS. PLEASE KNOW THAT THESE WILL BE REQUIRED UNDER
 A SEPARATE PERMIT AND MAY NOT BE INCLUDED ON THESE
 PLANS.
  
 7) NOTE: PLEASE SEE THE ADDRESS FOR THIS PROJECT IS
 9921 OKEECHOBEE BLVD. PLEASE INCLUDE THIS INFORMATION
 AS REQUIRED ON TITLE BLOCKS.
 FAC 61G1-16.004, FAC 61G15-23.002
  
 8) NOTE: PLEASE SEE THAT A VOLTAGE DROP SUMMARY WAS
 SUBMITTED FOR PANELS AND SOME ITEMS HOWEVER NOT
 SUBMITTED FOR SITE LIGHTING AND OTHER WORST CASE
 SCENARIOS PER FBC 13-413.1ABC.1
  
 9) NOTE: PLEASE SEE THE LOCATION OF THE MAIN SERVICE
 MEANS OF DISCONNECT IS NOT APPROVED AT THIS TIME PER
 THIS AHJ.
 PLEASE SEE THAT THE LOCATION SHALL BE READILY
 ACCESSIBLE AT THE NEAREST POINT OF ENTRANCE INTO THE
 BUILDING IF THE MAIN IS GOING TO BE LOCATED INSIDE THE
 BUILDING. AS SHOWN ON PLANS, THIS MAIN IS ONLY OBTAINED
 IN THE CASE OF AN EMERGENCY BY FIRE DEPARTMENT
 PERSONNEL BY TRAVERSING THROUGH AT LEAST FOUR LOCKED
 DOORS AND A SUBSTANTIAL NOT RATED PATH OF TRAVEL INTO
 THE BUILDING.
 PLEASE KNOW THAT THIS HAS BEEN GONE OVER WITH THE FIRE
 MARSHAL CHIEF AND LOCATION IS ALSO NOT ACCEPTED. **
 PLEASE CALL TO GO OVER OTHER LOCALS IF NEED BE. (LOCATE
 MAIN OUTSIDE, DOOR FROM OUTSIDE INTO THE MAIN
 ELECTRICAL FIRE RATED (1HR MINIMUM) ROOM? ETC) 230.70,
 230.71, 90.4 NEC.
 FBC ADMIN SECTION 104.6
  
 10) NOTE: PLEASE SEE PLANS APPEAR TO INDICATE SOME SORT
 OF *OUTLET* TAPPED FROM THE WATER HEATER SHOWN ON
 PLANS? PLEASE CLARIFY THIS.
 FBC 106.1.2.
  
 11) NOTE: PLEASE KNOW THAT ANY (LOCK ON/LOCK OFF
 DEVICES WHICH ARE BEING INSTALLED ONLY IN THE ATTEMPT
 TO BE USED AS THE DISCONNECTING MEANS OF EQUIPMENT OR
 APPLIANCES SHALL HAVE THE DEVICE PERMANENTLY AFFIXED TO
 BREAKER SO THAT THE DEVICE CAN NOT BE READILY REMOVED
 UNLESS THE BREAKER IS REMOVED.
 PLEASE KNOW IF NONE OF THE DEVICES AS NOTED ON PLANS
 ARE FOR THIS PURPOSE AND ONLY BEING USED FOR LOCKING ON
 THE CIRCUITS THEN PLEASE STATE DEVICE(S).
 PLEASE KNOW THAT A NOTE WILL BE REQUIRED ON PLANS IN
 ADDITION TO THE *LOCK-OFF* NOTE WHICH STATES THAT THE
 DEVICE MUST BE AN INTEGRAL PART OF THE BREAKER OR WORDS
 TO THAT AFFECT.
 110.3, 90.4.
  
 12) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE
 SOME LOCATIONS WHICH DO NOT INDICATE ANY LIGHTING
 CONTROLS UNDER AN AUTOMATED MEANS. PLEASE SEE THAT
 THESE DEVICES NEED TO BE SHOWN AS SOME OF THE DEVICES
 SHOWN SEEM TO BE NORMAL CONTROL SWITCHES AND SOME AREAS
 DO NOT SEEM TO INDICATE OCCUPANCY TYPE DEVICES. PLEASE
 SEE THE COOLER, FREEZER, DRIVE THRU SWITCH, TOWER
 SWITCH, PHOTO-LAB ETC. PLEASE VERIFY ALL LOCATIONS.
 PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES, AND TIMES
 FOR ALL DEVICES. THE PLANS DO CONTAIN SOME NOTES WHICH
 STATE 2HRS HOWEVER NOT FOR ALL.
 PLEASE SEE OUTSIDE LIGHTING IS REQUIRED TO BE ON AN
 ASTRONOMICAL TIME CLOCK WITH CONTROLS TO SHUT LIGHTING
 OFF WHEN SUFFICIENT DAY LIGHT IS PRESENT.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE
 THE LIGHTING FIXTURE LEGEND DOES NOT CORRELATE WITH THE
 ENERGY CALCULATIONS SUBMITTED. PLEASE ALSO SEE THE
 TOTAL WATTAGE AND MAXIMUM LIGHTING POWER DENSITIES AS
 SHOWN CAN NOT BE VERIFIED. PLEASE SEE THAT THE LIGHTING
 ENERGY CALCULATIONS DO NOT INDICATE THE EXTERNAL AND
 EXTERIOR LIGHTING AS SHOWN ON PLANS.
 PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED
 INDICATES *MANUAL ON/OFF* FOR ALL LIGHTING? PLEASE SEE
 THAT THIS IS NOT POSSIBLE WHEN THE LIGHTING IS
 AUTOMATED.
 PLEASE SEE THE SHEET #3 NEEDS TO CONTAIN THE
 INFORMATION AS NEEDED FOR PRINTED INFORMATION FOR THE
 DESIGNER OF RECORD, SIGNED, DATED AND SEAL.PLEASE BE
 SURE ALL TO SEE 13-103.1.1.1
  
 13) NOTE: PLEASE SEE SOME OF THE DEVICES AS NOTED FOR
 OCCUPANCY DEVICES ARE ONLY 180 DEGREE DEVICES, WHICH
 WHEN AN OCCUPANT IS LOCATED IN SOME AREAS ON THE PLANS
 THIS DEVICE AND THE DIRECTION AS NOTED WOULD NOT PICK
 UP ON THE OCCUPANT AND THERE FORE TURNING LIGHTING OFF
 AND MAY CREATE A HAZARD.
 PLEASE SEE SOME REDLINED AREAS ON PLANS WHICH ARE OF
 CONCERN. IF THESE DEVICES ARE COMBO DEVICES WHICH
 PROVIDE ULTRASONIC SENSING THEN THIS MAY NOT BE AN
 ISSUE. PLEASE VERIFY ALL LOCATIONS AND TYPES OF DEVICES
 FOR FULL COVERAGE.
 LS 101 7.8, 7.9
  
 14) NOTE: PLEASE SEE MISSING SHOW WINDOW/DISPLAY WINDOW
 AREAS WHICH WILL REQUIRE RECEPTACLES LOCATED ABOVE THE
 WINDOW AREAS AND PORTIONS THEREOF.PLEASE SEE THE
 LOADS FOR THE SHOW WINDOWS SHALL COMPLY WITH 220.43A
 FOR FEEDER CALCULATIONS. THE CALCULATION OF 200
 VOLT-AMPERES FOR EACH LINEAR FOOT OF A SHOW WINDOW IS
 REQUIRED TO DETERMINE THE FEEDER LOAD. SEE THE
 COMMENTARY FOLLOWING 220.14(G) FOR LOAD CALCULATIONS
 FOR BRANCH CIRCUITS IN SHOW WINDOWS.
 AS NO LOAD CALCULATIONS WERE SUBMITTED, REVIEW OF THIS
 FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 15) NOTE: PLEASE SEE MISSING SIGN CIRCUIT ON PLANS AND
 PANEL SCHEDULE FOR THE MINIMUM LOADS AS INDICATED IN
 THE NEC. THIS CIRCUIT IS TO BE LOCATED AT A MINIMUM AT
 THE LOCATION OF THE FRONT ENTRANCE AS REQUIRED PER
 600.5.
  
 16) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE PLEASE
 SUBMIT A SIGNED, DATED AND SEALED NOTARIZED LETTER. FS
 471.025
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 PLEASE ALSO BE SURE THE LETTER IS ORIGINAL AND IS
 PROPERLY NOTARIZED PER FS 117.05.
  
 17) NOTE: PLEASE SEE THAT PLANS MENTIONS FIRE ALARM
 SYSTEM AND SECURITY ALARM SYSTEM.
 PLEASE KNOW BASED ON THIS BUILDING AND IT BEING
 SPRINKLED AND FIRE ALARM PROTECTED, PLEASE SEE FIRE
 REVIEW COMMENTS WHICH WILL REQUIRED FIRE SPRINKLER
 LAYOUT AND PLEASE SHOW FA DEVICES ON BASED BUILDING
 PLANS. PLEASE KNOW THAT EVEN THOUGH ANY FIRE ALARM AND
 FIRE SPRINKLER WORK WILL BE DONE UNDER A SEPARATE
 PERMIT, THE BASE PLANS ARE REQUIRED TO SHOW
 PROTECTION.
 PLEASE BE SURE ALL DEVICES AS REQUIRED IN FBC
 11-4.28.1, .2 AND .3(4) AS SHOWN WITH MINIMUM LEVELS
 FOR ADA COMPLIANCE.
 FBC 106.1.2, 106.3.5.1.2
  
 18) NOTE: PLEASE SEE AS NOTED ABOVE FOR CODES; PLEASE
 SEE THAT THE LOAD CALCULATIONS INDICATE SECTIONS OF THE
 CODE WHICH ARE FROM PREVIOUS CODES NO LONGER IN
 EFFECT.
 220.11, 220.13.
  
 19) NOTE: PLEASE CLARIFY AND SHOW THE BRANCH CIRCUITS
 CONDUCTOR SIZES FOR ALL. CAN BE DONE IN A TYPICAL
 DIAGRAM IF THIS IS INDEED THAT CASE, HOWEVER PLEASE SEE
 AREAS WITH VOLTAGE DROP WHICH MAY BE AFFECTED TO SHOW A
 LARGER CONDUCTOR ON A BRANCH CIRCUIT WITH SMALLER OCP.
 240.4, 310.16
  
 20) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE UPS SYSTEM EQUIPMENT.
 110.3, 90.7
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-20 07:02:062007-03-20 07:02:06
 REVIEW IN PROGRESS
2007-03-19 20:08:582007-03-19 20:08:58
 IN ELEC FOR REVIEW, NOTES TO FOLLOW ONCE REVIEW IS
 COMPLETE.