Plan Review Notes
Plan Review Notes For Permit 07030491
Permit Number 07030491
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-13 15:26:25BUILDING PLAN REVIEW
 PERMIT: 07030491
 ADD: 9921 OKEECHOBEE BLVD
 CONT: ROCKWELL DEVELOPMENT
 TEL: (561)278-3100
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT
 IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS
 IN DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE
 IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT
 THE NECESSARY INVESTIGATION BE
 MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4)106.1.2 * ADDITIONAL INFORMATION REQUIRED, PLANS
 FAIL TO PROVIDE AN INDEX INDICATING
 ON WHICH SHEET ANY CERTAIN DOCUMENT WILL BE FOUND. THIS
 WOULD GREATLY INCREASE PRODUCTIVITY
 IN THE AMOUNT OF TIME IT TAKES TO DO A REVIEW OF YOUR
 PROJECT!!!!
  
 5) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 6) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 7)SHEET A0.1 INDICATES THE PLANS WERE DESINED TO THE
 2004 FBC. PLANAS SUBMITTED AFTER DEC.8, 2006 ARE TO BE
 DESIGNED TO THE 2004FBC WITH THE 2006 AMENDMENTS.
  
 8)SHEET A0.2 SITE PLAN INDICATES WHAT APPEARS TO BE A
 PROPERTY LINE AROUND THE NEW PROPOSED STORE, BUT THERE
 ALSO APPEARS TO BE A SECOND PROPERTY LINE AT THE FRONT
 OF THE STORE? WHAT AREA IS THE LEASABLE AREA OR
 PROPERTY LINE ? IS THERE ONLY 38 PARKING SPACES IN THIS
 PROJECT OR IS THERE 87 PARKING SPACES? IF THERE ARE 87
 PARKING SPACES THEN 11-4.1.2(5)(A)INDICATES THERE
 SHOULD BE (4) SPACES FOR THE PHYSICLLY DISABLED .
  
 9) SURVEY BY CRAIG S. PUSEY IS A RAISED SEAL BUT PHOT
 COPIED SIGNATURE.
  
 10)) SHEET A0.2 ALSO SHOULD SHOW THE ACCESSABLE ROUTE
 TO THE PUBLIC WAY. 11-4.1.2(1) .
  
 11)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS:A)
 EXTERIOR HOLLOW METAL SWING DOORS
 B)OVERHEAD COIL DOORS
 C) AUTOMATIC SLIDING DOORS
 D) ROOF HATCHES
 E) WINDOWS- STOREFRONT
 F) WINDOWS PASS THROUGH
 G) ROOF ASSEMBLIES, BASE SHEETS, TILE AND FASTENER
 TYPES
 H) PRE-MANUFACTURED A/C STANDSSHEET A4.5INDICATES
 SLEEPERS, 1509.7/ TABLE 1509.7.
 I) WOOD TRUSS TIE DOWN ANCHORS
  
 12)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
  
  
 13) PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 14) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 ROOF TILE :
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 __X_ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _2&3__ .
  
 __X_ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _X__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 __X__- PROVIDE TYPE OF RIDGE AND HIP BOARD TO BE USED
 AND TYPE OF ATACHMENT.
 CONCRETE TILE / CLAY TILEATTACHMENTSHALL BE
 FASTENED IN ACCORDANCE WITH 1609 OR IN ACCORDANCE WITH
 FRSA/TRI 07320-04 INSTALLATION MANUAL.
  
 15) SHEET S2.1 TRUSS TIE DOWNANCHORS, THE DESIGNER OF
 RECORD HASN,T GIVEN THE VALUES REQUIRED FOR THE HOLD
 DOWN FASTENERS.PLEASE PROVIDE GRAVITY LOADS, LATERAL
 LOADS & UPLIFT LOADS TO BE RESISTED.THE ANCHORS ARE
 PART OF THE MAIN FORCE RESISTING SYSTEM1609.1.1. PLEASE
 PROVIDE VALUES TO BE RESISTED.T1 & T2 ARE NOT LOCATED
 ON PLAN.
  
 16)FRONT ENTRY HORIZONTAL SLIDING DOORS: 1008.1.3.3
 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1.
 THE DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE
 OF BEING OPERATED MANUALLY IN THE EVENT OF POWER
 FAILURE.
 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD
 FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3.
 THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE
 APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED,
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE
 DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 80 AND SHALL COMPLY WITH SECTION 715 .
 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED
 STANDBY POWER SUPPLY.
 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE
 ELECTRICALLY SUPERVISED.
 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED
 WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE
 OPERATING DEVICE.
 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 17)A2.4 INDICATES THE USE OF HI-RIB LATH ON THE UNDER
 SIDE (HORIZONTAL FRAMING MEMBERS) OF THE CANOPY, PLEASE
 PROVIDE THE NAILING REQUIREMENTS FOR LATH. TABLE
 2511.1/ ASTM
 C-1063. 2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM C-1063.
  
 18)SHEET A2.4 INDICATES THE USE OF EAVE ANDTHE
 MONIER LIFETILE ATTIC VENT, PLEAS PROVIDE THE
 CALCULATIONS AS PER 1203.2, PLEASE ALSO PROVIDE THE
 PRODUCT APPROVAL
 FOR THE LIFETILE ATTIC VENT, RULE 9-B-72.
  
 19)PLEASE PROVIDE THE FIRE SPRINKLER PLANS SHEET A0.1
 PROJECT INFORMATION INDICATES TAKING AREA INCREASES FOR
 A FIRE SPRINKLERED BUILDING, PLEASE PROVIDETHE
 REQUIREDAUTOMATIC SPRINKLER PLANS PER, TABLE 503,
 504.2 & 903.1.1
  
 20)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  