Notes
Date Text
2007-03-19 19:35:40** UNSAT **
  
 * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE THE MISSING LICENSE INFORMATION AS
 REQUIRED ON TITLE BLOCKS FOR THE ENGINEERING FIRM PER
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA
 STATUTES 471.023
 PLEASE ALSO SEE THE MISSING PRINTED NAME OF THE
 ENGINEER AS STATED ON LICENSE AND STATE WEB SITE.
 PLEASE SEE ATTACHED PRINT OUT FROM THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION WHICH CONTAINS A
 CERTIFICATE OF AUTHORIZATION NUMBER FOR THIS ENGINEER
 HOWEVER IT IS NOT FOR THE FIRM AS LISTED ON PLANS.
 PLEASE ALSO SEE THAT THIS LICENSE FOR SAID FIRM IS
 CURRENTLY IN A *DELINQUENT* STATUS AS OF 2/28/07. THIS
 PRINT OUT WAS DONE ON 3/19/07
 ** PLEASE KNOW THAT PLANS ARE BEING RETAINED BY THIS
 OFFICE AT THIS TIME.
 ** CONFIRMATION WITH THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS AND THE STATE'S LEGAL COUNSEL TO THE BOARD
 WILL BE MADE.
  
 2) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** THESE ARE REQUIRED FOR THIS REVIEWER AT A MINIMUM
 AND OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 3) NOTE: PLEASE SEE ARCHITECTURAL SHEETS DO NOT
 INDICATE ANY CODES, TYPE OF CONSTRUCTION, OCCUPANCY
 ETC? THERE IS NO COVER SHEET WITH INFORMATION WHICH IS
 REQUIRED TO REFLECT MANY OF THESE ITEMS.
 PLEASE CORRELATE THE SUITE/UNIT NUMBER WHICH IS
 MENTIONED ON TITLE BLOCKS AS PERMIT APPLICATION AND OUR
 COMPUTER SYSTEM IN WHICH THE LOCATION WAS APPLIED FOR
 IS SUITE/UNIT #242 AND PLANS CALL FOR UNIT/SUITE #240.
 PLEASE ALSO SEE BUILDING REVIEW COMMENTS FOR THIS AND
 COMMENTS WITH RESPECT TO MISSING PRODUCT DATA NOT
 SUBMITTED FOR NEW STOREFRONT DOORS/WINDOWS ETC.
 FBC 106.1.2, 110.2
  
 4) NOTE: PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR
 AND MATERIALS EVEN IF ANY EQUIPMENT OR MATERIALS ARE
 OWNER SUPPLIED. FBC ADMIN SECTION 108.3
  
 5) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE LOCATIONS WHICH DO NOT INDICATE ANY
 LIGHTING CONTROLS.PLEASE SEE THIS IS LOCATED IN A
 BUILDING GREATER THAN 5K SQ FT.
 PLEASE PROVIDE LOCATIONS AND MORE DETAIL OF THE OVER
 RIDES DEVICES AND HOW THEY ARE BEING PART OF THE
 *SYSTEM* OR IF THERE WILL BE INDIVIDUAL CONTROLS BY WAY
 OF OCCUPANCY SENSING DEVICES ETC.
 PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES, AND TIMES
 FOR ALL DEVICES.
 PLEASE SEE THE LIGHTING NOTE PROVIDED FOR SOME
 COMPLIANCE WITH CHAPTER 13 IS NOT CODE COMPLIANT.
 PLEASE PROVIDE ESTIMATED SCHEDULING IF A SYSTEM IS
 INSTALLED.
 PLEASE SEE THAT THE LOCATIONS FOR ALL OVER RIDES
 DEVICES SHALL BE LOCATED SO THAT THE OCCUPANT CAN
 VISUALLY SEE THE LIGHTING WHICH IS BEING CONTROLLED.
 PLEASE PROVIDE MORE INFORMATION.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING.
 PLEASE SEE 13-415.1.AB.1; PLEASE SEE ENERGY
 CALCULATIONS FOR BUILD OUT OF SPACE WHICH WAS NOT
 SUBMITTED.
 PLEASE SEE13-415.2.ABC.1.2 (3) FOR TRACK LIGHTING AND
 HOW LOAD IS SHOWN.
 PLEASE PROVIDE INFORMATION ON TRANSFORMERS IF LOW
 VOLTAGE AS SHOWN.
 PLEASE SEE NO LIGHTING FIXTURE LEGEND WAS SUBMITTED AND
 NOT INFORMATION FOR MAXIMUM LIGHTING POWER DENSITIES
 WAS SHOWN. PLEASE SEE THE QUOTING OF THE CODE IN LIEU
 OF THE TECHNICAL INFORMATION REQUIRED IN DESIGN IS NOT
 PERMITTED.
 PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT
 INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE
 THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE
 SUBMITTED.
 * PLEASE SEE ALL OF CHAPTER 13.
 PLEASE BE SURE ALL TO SEE 13-103.1.1.1
  
 6) NOTE: PLEASE SEE THE NEW ELECTRICAL SERVICE WHICH IS
 BEING PROPOSED WILL NOT BE PERMITTED PER 230.2E. PLEASE
 SEE THAT THIS BUILDING ALREADY CONTAINS AN ELECTRICAL
 SERVICE AND NEW FEED TO THIS TENANT BUILD OUT SHALL
 ORIGINATE FROM THIS EXISTING SERVICE FOR TENANT SPACE.
 PLEASE ALSO INCLUDE COMPLETE LOAD SUMMARY OF THE
 EXISTING SERVICE WITH NEW ELECTRICAL LOAD BEING ADDED.
 NEC 220.12, 220.14, 220.42, 220.43 A AND B, 220.44
 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 7) NOTE: PLEASE PROVIDE INFORMATION ON THAT SERVICE AND
 THE NEW CONNECTIONS.
 PLEASE KNOW THAT A FLOATING NEUTRAL WILL BE REQUIRED TO
 BE NOTED ON PLANS AS THE EQUIPMENT GROUNDING WILL
 ALREADY BE BONDED AT THIS FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6 AND 250.24
  
 8) NOTE: PLEASE SEE THE LOADS FOR THE SHOW WINDOWS
 SHALL COMPLY WITH 220.43A FOR FEEDER CALCULATIONS. THE
 CALCULATION OF 200 VOLT-AMPERES FOR EACH LINEAR FOOT OF
 A SHOW WINDOW IS REQUIRED TO DETERMINE THE FEEDER LOAD.
 SEE THE COMMENTARY FOLLOWING 220.14(G) FOR LOAD
 CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS.
 AS NO LOAD CALCULATIONS WERE SUBMITTED, REVIEW OF THIS
 FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 9) NOTE: PLEASE SEE MISSING SIGN CIRCUIT ON PLANS. THIS
 CIRCUIT IS BEING SHOWN ON PANEL SCHEDULE HOWEVER NOT ON
 PLANS AT THE LOCATION OF THE FRONT ENTRANCE AS REQUIRED
 PER 600.5.
  
 10) NOTE: PLEASE CORRELATE ALL THE CIRCUITING AS SHOWN
 ON PLANS. PLEASE SEE THE CIRCUITS SEEM TO BE SHOWN
 HOWEVER ALSO INDICATES SOME NOTATIONS AS *S*-# ON EACH
 ONE?? PLEASE SEE THAT THIS DOES NOT SEEM TO CORRELATE
 TO ANY INFORMATION ON PLANS? PLEASE SEE THERE IS NO
 SWITCH LEGEND?
 PLEASE ALSO SEE THAT NOT ALL DEVICES CONTAIN CIRCUITING
 ON PLANS. PLEASE COMPLETE.
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTING. (ONLY SOME NOT SHOWN).
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
 FBC 106.1.2.
 NEC 408.4
  
 11) NOTE: PLEASE SEE MISSING OVER CURRENT PROTECTION ON
 THE SECONDARY SIDE OF THE TRANSFORMER. PLEASE SEE
 408.36 AND 240.21
 ** REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME.
  
 12) NOTE: PLEASE SEE THE RISER AND PLANS ARE MISSING
 ANY CONDUCTORS ON THE SECONDARY SIDE OF THE
 TRANSFORMER?
 PLEASE SEE 240.4, 310.16, 240.21 ETC
 FBC 106.3.5.1.2
  
 13) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS NOTE: *FOR
 DEFINITION OF ELECTRICAL SYMBOLS REFER TO PANEL
 SCHEDULE*??? PLEASE SEE THIS IS VERY CONFUSING AS A
 PANEL SCHEDULE WOULD NOT CONTAIN DEFINITIONS FOR ANY
 ELECTRICAL SYMBOLS AND ALTHOUGH THIS IS STATED ON
 PLANS, THE PANEL SCHEDULE AS SUBMITTED DOES NOT CONTAIN
 ANY SYMBOLS OR DEFINITIONS.
 PLEASE SUBMIT A SYMBOL LEGEND AND CORRELATE DEFINITIONS
 FOR PLANS AND DESIGN.
 FBC 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE PLEASE
 SUBMIT A SIGNED, DATED AND SEALED NOTARIZED LETTER. FS
 471.025
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 PLEASE ALSO BE SURE THE LETTER IS ORIGINAL AND IS
 PROPERLY NOTARIZED PER FS 117.05.
  
 15) NOTE: PLEASE SEE FS 471.02(2).
  
 16) NOTE: PLEASE PROVIDE GROUNDING DETAIL FOR ALL
 TRANSFORMERS PER 250.20, 250.30, 250.66.
 PLEASE SHOW SIZE AND ATTACHMENT LOCATIONS.
  
 17) NOTE: PLEASE SEE THAT PLANS MENTIONS ALARM SYSTEM,
 IS THIS SECURITY ALARM SYSTEM OR FIRE ALARM SYSTEM?
 PLEASE KNOW BASED ON THIS BUILDING AND IT BEING
 SPRINKLED AND FIRE ALARM PROTECTED, PLEASE SEE FIRE
 REVIEW COMMENTS WHICH WILL REQUIRED FIRE SPRINKLER
 LAYOUT AND PLEASE SHOW FA DEVICES ON BASED BUILDING
 PLANS. PLEASE KNOW THAT EVEN THOUGH ANY FIRE ALARM AND
 FIRE SPRINKLER WORK WILL BE DONE UNDER A SEPARATE
 PERMIT, THE BASE PLANS ARE REQUIRED TO SHOW
 PROTECTION.
 PLEASE BE SURE ALL DEVICES AS REQUIRED IN FBC
 11-4.28.1, .2 AND .3(4) AS SHOWN WITH MINIMUM LEVELS
 FOR ADA COMPLIANCE.
 FBC 106.1.2, 106.3.5.1.2
  
 18) NOTE: PLEASE INDICATE ALL AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT. PLEASE SEE THAT ANY PANELS AND
 DISCONNECTS SHALL BE SHOWN.
 110.9 NEC.
 FBC 106.1.2, 106.3.5.1.2
  
  
 ** PLEASE KNOW BASED ON THE PLANS SUBMITTED AND
 INFORMATION NOT YET SUBMITTED FOR REVIEW AND ELECTRICAL
 WHICH WILL BE REQUIRED TO BE CHANGED. PLEASE KNOW THERE
 MAY BE COMMENTS ON THE FOLLOWING REVIEW NOT YET MADE ON
 THIS REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  