| Date |
Text |
| 2007-03-19 19:35:40 | ** UNSAT ** |
| | |
| | * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE SEE THE MISSING LICENSE INFORMATION AS |
| | REQUIRED ON TITLE BLOCKS FOR THE ENGINEERING FIRM PER |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA |
| | STATUTES 471.023 |
| | PLEASE ALSO SEE THE MISSING PRINTED NAME OF THE |
| | ENGINEER AS STATED ON LICENSE AND STATE WEB SITE. |
| | PLEASE SEE ATTACHED PRINT OUT FROM THE DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION WHICH CONTAINS A |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR THIS ENGINEER |
| | HOWEVER IT IS NOT FOR THE FIRM AS LISTED ON PLANS. |
| | PLEASE ALSO SEE THAT THIS LICENSE FOR SAID FIRM IS |
| | CURRENTLY IN A *DELINQUENT* STATUS AS OF 2/28/07. THIS |
| | PRINT OUT WAS DONE ON 3/19/07 |
| | ** PLEASE KNOW THAT PLANS ARE BEING RETAINED BY THIS |
| | OFFICE AT THIS TIME. |
| | ** CONFIRMATION WITH THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS AND THE STATE'S LEGAL COUNSEL TO THE BOARD |
| | WILL BE MADE. |
| | |
| | 2) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS |
| | ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS |
| | FOLLOWS. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** THESE ARE REQUIRED FOR THIS REVIEWER AT A MINIMUM |
| | AND OTHER CODES WILL BE REQUIRED FOR OTHER TRADES. |
| | |
| | 3) NOTE: PLEASE SEE ARCHITECTURAL SHEETS DO NOT |
| | INDICATE ANY CODES, TYPE OF CONSTRUCTION, OCCUPANCY |
| | ETC? THERE IS NO COVER SHEET WITH INFORMATION WHICH IS |
| | REQUIRED TO REFLECT MANY OF THESE ITEMS. |
| | PLEASE CORRELATE THE SUITE/UNIT NUMBER WHICH IS |
| | MENTIONED ON TITLE BLOCKS AS PERMIT APPLICATION AND OUR |
| | COMPUTER SYSTEM IN WHICH THE LOCATION WAS APPLIED FOR |
| | IS SUITE/UNIT #242 AND PLANS CALL FOR UNIT/SUITE #240. |
| | PLEASE ALSO SEE BUILDING REVIEW COMMENTS FOR THIS AND |
| | COMMENTS WITH RESPECT TO MISSING PRODUCT DATA NOT |
| | SUBMITTED FOR NEW STOREFRONT DOORS/WINDOWS ETC. |
| | FBC 106.1.2, 110.2 |
| | |
| | 4) NOTE: PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR |
| | AND MATERIALS EVEN IF ANY EQUIPMENT OR MATERIALS ARE |
| | OWNER SUPPLIED. FBC ADMIN SECTION 108.3 |
| | |
| | 5) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR |
| | CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE LOCATIONS WHICH DO NOT INDICATE ANY |
| | LIGHTING CONTROLS.PLEASE SEE THIS IS LOCATED IN A |
| | BUILDING GREATER THAN 5K SQ FT. |
| | PLEASE PROVIDE LOCATIONS AND MORE DETAIL OF THE OVER |
| | RIDES DEVICES AND HOW THEY ARE BEING PART OF THE |
| | *SYSTEM* OR IF THERE WILL BE INDIVIDUAL CONTROLS BY WAY |
| | OF OCCUPANCY SENSING DEVICES ETC. |
| | PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES, AND TIMES |
| | FOR ALL DEVICES. |
| | PLEASE SEE THE LIGHTING NOTE PROVIDED FOR SOME |
| | COMPLIANCE WITH CHAPTER 13 IS NOT CODE COMPLIANT. |
| | PLEASE PROVIDE ESTIMATED SCHEDULING IF A SYSTEM IS |
| | INSTALLED. |
| | PLEASE SEE THAT THE LOCATIONS FOR ALL OVER RIDES |
| | DEVICES SHALL BE LOCATED SO THAT THE OCCUPANT CAN |
| | VISUALLY SEE THE LIGHTING WHICH IS BEING CONTROLLED. |
| | PLEASE PROVIDE MORE INFORMATION. |
| | PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. |
| | PLEASE SEE 13-415.1.AB.1; PLEASE SEE ENERGY |
| | CALCULATIONS FOR BUILD OUT OF SPACE WHICH WAS NOT |
| | SUBMITTED. |
| | PLEASE SEE13-415.2.ABC.1.2 (3) FOR TRACK LIGHTING AND |
| | HOW LOAD IS SHOWN. |
| | PLEASE PROVIDE INFORMATION ON TRANSFORMERS IF LOW |
| | VOLTAGE AS SHOWN. |
| | PLEASE SEE NO LIGHTING FIXTURE LEGEND WAS SUBMITTED AND |
| | NOT INFORMATION FOR MAXIMUM LIGHTING POWER DENSITIES |
| | WAS SHOWN. PLEASE SEE THE QUOTING OF THE CODE IN LIEU |
| | OF THE TECHNICAL INFORMATION REQUIRED IN DESIGN IS NOT |
| | PERMITTED. |
| | PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT |
| | INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE |
| | THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE |
| | SUBMITTED. |
| | * PLEASE SEE ALL OF CHAPTER 13. |
| | PLEASE BE SURE ALL TO SEE 13-103.1.1.1 |
| | |
| | 6) NOTE: PLEASE SEE THE NEW ELECTRICAL SERVICE WHICH IS |
| | BEING PROPOSED WILL NOT BE PERMITTED PER 230.2E. PLEASE |
| | SEE THAT THIS BUILDING ALREADY CONTAINS AN ELECTRICAL |
| | SERVICE AND NEW FEED TO THIS TENANT BUILD OUT SHALL |
| | ORIGINATE FROM THIS EXISTING SERVICE FOR TENANT SPACE. |
| | PLEASE ALSO INCLUDE COMPLETE LOAD SUMMARY OF THE |
| | EXISTING SERVICE WITH NEW ELECTRICAL LOAD BEING ADDED. |
| | NEC 220.12, 220.14, 220.42, 220.43 A AND B, 220.44 |
| | ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 7) NOTE: PLEASE PROVIDE INFORMATION ON THAT SERVICE AND |
| | THE NEW CONNECTIONS. |
| | PLEASE KNOW THAT A FLOATING NEUTRAL WILL BE REQUIRED TO |
| | BE NOTED ON PLANS AS THE EQUIPMENT GROUNDING WILL |
| | ALREADY BE BONDED AT THIS FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6 AND 250.24 |
| | |
| | 8) NOTE: PLEASE SEE THE LOADS FOR THE SHOW WINDOWS |
| | SHALL COMPLY WITH 220.43A FOR FEEDER CALCULATIONS. THE |
| | CALCULATION OF 200 VOLT-AMPERES FOR EACH LINEAR FOOT OF |
| | A SHOW WINDOW IS REQUIRED TO DETERMINE THE FEEDER LOAD. |
| | SEE THE COMMENTARY FOLLOWING 220.14(G) FOR LOAD |
| | CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS. |
| | AS NO LOAD CALCULATIONS WERE SUBMITTED, REVIEW OF THIS |
| | FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | |
| | 9) NOTE: PLEASE SEE MISSING SIGN CIRCUIT ON PLANS. THIS |
| | CIRCUIT IS BEING SHOWN ON PANEL SCHEDULE HOWEVER NOT ON |
| | PLANS AT THE LOCATION OF THE FRONT ENTRANCE AS REQUIRED |
| | PER 600.5. |
| | |
| | 10) NOTE: PLEASE CORRELATE ALL THE CIRCUITING AS SHOWN |
| | ON PLANS. PLEASE SEE THE CIRCUITS SEEM TO BE SHOWN |
| | HOWEVER ALSO INDICATES SOME NOTATIONS AS *S*-# ON EACH |
| | ONE?? PLEASE SEE THAT THIS DOES NOT SEEM TO CORRELATE |
| | TO ANY INFORMATION ON PLANS? PLEASE SEE THERE IS NO |
| | SWITCH LEGEND? |
| | PLEASE ALSO SEE THAT NOT ALL DEVICES CONTAIN CIRCUITING |
| | ON PLANS. PLEASE COMPLETE. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT |
| | LIGHTING. (ONLY SOME NOT SHOWN). |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | FBC 106.1.2. |
| | NEC 408.4 |
| | |
| | 11) NOTE: PLEASE SEE MISSING OVER CURRENT PROTECTION ON |
| | THE SECONDARY SIDE OF THE TRANSFORMER. PLEASE SEE |
| | 408.36 AND 240.21 |
| | ** REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | 12) NOTE: PLEASE SEE THE RISER AND PLANS ARE MISSING |
| | ANY CONDUCTORS ON THE SECONDARY SIDE OF THE |
| | TRANSFORMER? |
| | PLEASE SEE 240.4, 310.16, 240.21 ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 13) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS NOTE: *FOR |
| | DEFINITION OF ELECTRICAL SYMBOLS REFER TO PANEL |
| | SCHEDULE*??? PLEASE SEE THIS IS VERY CONFUSING AS A |
| | PANEL SCHEDULE WOULD NOT CONTAIN DEFINITIONS FOR ANY |
| | ELECTRICAL SYMBOLS AND ALTHOUGH THIS IS STATED ON |
| | PLANS, THE PANEL SCHEDULE AS SUBMITTED DOES NOT CONTAIN |
| | ANY SYMBOLS OR DEFINITIONS. |
| | PLEASE SUBMIT A SYMBOL LEGEND AND CORRELATE DEFINITIONS |
| | FOR PLANS AND DESIGN. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 14) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH |
| | INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE PLEASE |
| | SUBMIT A SIGNED, DATED AND SEALED NOTARIZED LETTER. FS |
| | 471.025 |
| | THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY |
| | FUTURE REFERENCE. |
| | PLEASE ALSO BE SURE THE LETTER IS ORIGINAL AND IS |
| | PROPERLY NOTARIZED PER FS 117.05. |
| | |
| | 15) NOTE: PLEASE SEE FS 471.02(2). |
| | |
| | 16) NOTE: PLEASE PROVIDE GROUNDING DETAIL FOR ALL |
| | TRANSFORMERS PER 250.20, 250.30, 250.66. |
| | PLEASE SHOW SIZE AND ATTACHMENT LOCATIONS. |
| | |
| | 17) NOTE: PLEASE SEE THAT PLANS MENTIONS ALARM SYSTEM, |
| | IS THIS SECURITY ALARM SYSTEM OR FIRE ALARM SYSTEM? |
| | PLEASE KNOW BASED ON THIS BUILDING AND IT BEING |
| | SPRINKLED AND FIRE ALARM PROTECTED, PLEASE SEE FIRE |
| | REVIEW COMMENTS WHICH WILL REQUIRED FIRE SPRINKLER |
| | LAYOUT AND PLEASE SHOW FA DEVICES ON BASED BUILDING |
| | PLANS. PLEASE KNOW THAT EVEN THOUGH ANY FIRE ALARM AND |
| | FIRE SPRINKLER WORK WILL BE DONE UNDER A SEPARATE |
| | PERMIT, THE BASE PLANS ARE REQUIRED TO SHOW |
| | PROTECTION. |
| | PLEASE BE SURE ALL DEVICES AS REQUIRED IN FBC |
| | 11-4.28.1, .2 AND .3(4) AS SHOWN WITH MINIMUM LEVELS |
| | FOR ADA COMPLIANCE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 18) NOTE: PLEASE INDICATE ALL AIC RATINGS FOR ALL NEW |
| | SERVICE EQUIPMENT. PLEASE SEE THAT ANY PANELS AND |
| | DISCONNECTS SHALL BE SHOWN. |
| | 110.9 NEC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | |
| | ** PLEASE KNOW BASED ON THE PLANS SUBMITTED AND |
| | INFORMATION NOT YET SUBMITTED FOR REVIEW AND ELECTRICAL |
| | WHICH WILL BE REQUIRED TO BE CHANGED. PLEASE KNOW THERE |
| | MAY BE COMMENTS ON THE FOLLOWING REVIEW NOT YET MADE ON |
| | THIS REVIEW. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |