| Plan Review Notes For Permit 07030489 |
| Permit Number |
07030489 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-04-18 16:15:02 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)THE SHUTTER PRODUCT APPROVALS ARE ILLEGIBLE. | | | | | | 2.)I WAS UNABLE TO REVIEW THE SHUTTER INSTALLATION | | | SCHEDULE AS I COULD NOT READ THE INFORMATION ON THE | | | PRODUCT APPROVAL. | | | | | | 3.)INDICATE WHICH MULLION PRODUCT YOU ARE USING | | | (MULLION LOAD CHART). | | | | | | 4.)YOUR APPLICATION STATES THAT YOU ARE GOING TO | | | STUCCO THE EXTERIOR.WHAT IS THE SUBSTRATE?PROVIDE A | | | DETAIL IF NECESSARY. | | | | | | THE RESPONSE LETTER ADDRESSES THE QUESTION.ALL | | | RESPONSES SHOULD BE INCORPORATED INTO THE PLAN. PROVIDE | | | A DETAIL OR SPECIFICATION, INCLUDING SHEATHING | | | NAILING. | | | | | | 5.)THE PLANS STATE THAT DESIGN CRITERIA IS FBC 1605, | | | PLEASE CLARIFY WHAT LOAD COMBINATIONS ARE USED IN THIS | | | PROJECT.ALSO REFERS TO 1606, INCORRECT CODE | | | REFERENCE. | | | | | | 6.)IT IS NOT CLEAR WHY AN ENGINEER HAS STAMPED THE | | | PRODUCT APPROVALS BUT DID NOT DRAW THE PLAN. | | | |
|