| 2007-06-29 11:31:16 | DENIED 2ND TIME | | | REFERENCE: | | | ** FBC-2004 PLUMBING. | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | 1. THE MANUFACTURER'S RECOMMENDED SETBACK IN THE | | | INSTALLATIOM MANUAL ON PAGE #5, 1.3 GENERATOR LOCATION, | | | STATES "A GOOD RULE IS TO ALLOW FIVE FEET OF SPACE ON | | | ALL SIDES". THERE IS NOT THE RECOMMENDED CLEARANCE | | | BETWEEN THE GENERATOR AND THE RESIDENCE. | | | | | | NOTE: NO FUTHER ACTION CAN BE TAKEN REGARDING ISSUING | | | THIS PERMIT AS LONG AS THERE IS A PREVIOUS APPLICATION | | | OPEN (#06060449) FOR THIS INSTALLATION. THE OWNER MUST | | | CONTACT ADRIANNA MCKENZIE, SUPERVISER, LICENSE/PERMITS, | | | CONTRUCTION SERVICES DEPARTMENT(561-805-6681) TO CLEAR | | | THIS MATTER UP. | | | | | | 2.NOTE: THE RESUBMITTED DRAWING IS INDICATING THE | | | EXISTING AS WELL AS THE PROPOSED GENERATOR BTU LOAD. | | | BUT IT IS FAILING TO INDICATE THE LONGEST LENGTH OF THE | | | SYSTEM OR THE LOCATION OF THE MP REGULATORS TO THE | | | EXISTING APPLIANCES. PLEASE CLARIFY THIS AND PLEASE | | | KNOW THAT THE GENERATOR LOCATION MAY CHANGE DUE TO | | | CLEARENCES. (SEE COMMENT #1). | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|