| Plan Review Notes For Permit 07030468 |
| Permit Number |
07030468 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-30 10:51:23 | NEED LOAD CALCULATION FOR THE SERVICE.215.5 | | | | | | NEED TO SHOW THE LOCATIONS OF THE PANELS ON DRAWINGS | | | 215.5 | | | | | | OUTLET SPACING IS NOT TO CODE210.50 | | | | | | NEED ARCFAULTS IN BEDROOMS ON ALL.210.12 | | | | | | NEED SMOKE ALARMS PER FLA BLDG COCE | | | | | | NEED TO SHOW GARAGE AND WIRING. |
|