| 2008-07-08 14:52:02 | 1. THE FIRE DEPARTMENT CONNECTIONS (FDC'S) ON THE SITE |
| | SHALL BE EQUIPPED WITH KNOX-BOX LOCKING CAPS. |
| | |
| | 2. THE USE OF PROPANE AND CHARCOAL GRILLS IN |
| | MULTI-FAMILY BUILDINGS ARE NOT PERMITTED. ONLY LISTED |
| | ELECTRIC TYPE EQUIPMENT IS ALLOWED. |
| | |
| | 3. ON PAGE A601 EXIT DIRECTION MARKINGS LEAD TO |
| | OPENINGS. THESE LARGE OPENINGS CANNOT CONTAIN GATES OT |
| | OTHER DEVICES WHICH WILL NOT ALLOW FOR EXITING. |
| | |
| | 4. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON PAGE |
| | E-8. |
| | |
| | 5. THE PROPOSED FIRE STANDPIPE SYSTEM FOR THE DOCKS |
| | SHALL COMPLY WITH NFPA 303. SEPARATE PLANS AND PERMITS, |
| | AND FDC ARE REQUIRED. |
| | |
| | 6. ON PAGE SP-1.1 THE TYPICAL FIRE CABINET SHALL BE |
| | EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS. ALL STANDPIPE |
| | CONNECTIONS SHALL ALSO BE EQUIPPED WITH THESE DEVICES. |
| | |
| | 7. ON PAGE AC-15 SMOKE CONTROL SYSTEM SEQUENCE OF |
| | OPERATIONS INDICATES THAT SMOKE DETECTORS WILL ACTIVATE |
| | A SUPERVIOSRY SIGNAL. DUCT SMOKE DETECTORS SHALL |
| | ACTIVATE A GENERAL ALARM AND NOT A SUPERVISORY SIGNAL. |
| | |
| | 8. ALL ASSOCIATED DAMPERS SHALL BE DROP TESTED TO |
| | ENSURE PROPER OPERATION AFTER INSTALLATION. |
| | |
| | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER AND FIRE ALARM EQUIPMENT PLANNED FOR |
| | BUILDINGS 1 & 2. |
| | |
| | 10. PLEASE CORRECT BUILDING CODE AND FIRE DEFICIENCIES |
| | AS IDENTIFIED BY THE CONSTRUCTION SERVICES PLAN |
| | REVIEWER. |
| | |
| | 11. ALL CONSTRUCTION METHODS AND INSTALLATION METHODS |
| | ARE SUBJECT TO FIELD INSPECTION AND APPROVAL. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |