| 2008-06-20 14:04:35 | |
| | FLAGLER BEACH CLUB BUILDING# 3TOWER (15 STORY)& |
| | PARKING STRUCTURES |
| | |
| | BUILDING PLAN REVIEW |
| | |
| | PERMIT: 07030460 |
| | ADD: 5818 N FLAGLER DR(HIGH RISE BUILDING# 3) CONT: |
| | SCOTT GROUP |
| | TEL: (561)346-9888 |
| | CONTACT NAT HEALY635-6935 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | ARCHITECT: DAVID LAWRENCE |
| | T: (561)805-5793 |
| | F: (561)805-5795 |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2-4) COMPLIED. |
| | |
| | 5) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF |
| | WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS |
| | LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. MINIMUM BASE FLOOD |
| | ELEVATION IS 7'-6". |
| | |
| | 6) COMPLIED. |
| | |
| | 7) 2ND REQUEST, .FL S S 713.13NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT.NOTE: |
| | 713.24(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 8) 2ND REQUEST,THRESHOLD INSPECTOR:WPB AMENDMENT |
| | 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN |
| | CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT |
| | (561)805-6711 FOR FURTHER INFORMATION BEFORE THE PERMIT |
| | MAY BE ISSUED. |
| | |
| | 9-15A) COMPLIED. |
| | |
| | 15B) INFORMATIONALONLY, NO COMMENT REQUIRED. 15B) |
| | PLANS INDICATE POOL, DECKS, FENCES, GATES AND OTHER |
| | SITE AMENITIES THAT WOULD BE COVERED UNDER SEPARATE |
| | PERMITS ALTHOUGH THERE ARE FEATURES IN THESE PLANS, |
| | OTHER TRADES MAY NOT COMMENT ON THESE ISSUES SINCE |
| | THERE ARE NO PERMITS APPLIED FOR AT THIS TIME FOR THESE |
| | ITEMS. |
| | |
| | 16-17) COMPLIED. |
| | |
| | 18A) SHEET A101A, THE SKYLIGHT DRIVE THROUGH PROVIDE |
| | PRODUCT APPROVAL FOR WIND AND PROVIDE WHAT TYPE SAFETY |
| | GLAZING WILL BE USED. 2405.2 ALLOWABLE GLAZING |
| | MATERIALS AND LIMITATIONS. THE RESPONCE INDICATED THIS |
| | WAS DELETED BUT ON SHEET A101 IS STILL INDICATED ON |
| | PLANS, PLEASE ADVISE, 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 18B-D) COMPLIED. |
| | |
| | 18E) SEMI-COMPLIED, RESPONCE INDICATED THAT IN THE DOOR |
| | SCHEDULE FOUND ON A400 DOOR NUMBERS 9, 13,16,17,18 & 19 |
| | WERE 90 MINUTE DOORS AND FRAMES, THE DOOR SCHEDULE ALSO |
| | INDICATES THESE DOOR FRAMES ARE TO BE ALUMINUM, PLEASE |
| | PROVIDE UL OR OTHER RECONIZED AGENCY REPORT. 715.3.1 |
| | NFPA 252 OR UL 10C. |
| | |
| | 19) SHEET A102 |
| | |
| | 19A)(1) 2ND REQUEST, SEE DETAIL B-3 SHEET A-402, THE |
| | SLIDING GLASS DOOR TRACK ASSEMBLY AS SHOWN DOES NOT |
| | MEET FAIR HOUSING GUIDELINES,FOR SECONDARY DOORS |
| | (SLIDING GLASS DOORS) THE GUIDELINE SPECIFY THAT THE |
| | THRESHOLDS AT THESE DOORS SHALL BE NO HIGHER THAN ? ?. |
| | THE GUIDELINES FURTHER STATE THAT CHANGES IN LEVEL AT |
| | THESE LOCATIONS MUST BE BEVELED WITH A SLOPE NO GREATER |
| | THAN 1:2. |
| | 19A)(2) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE |
| | MAXIMUM ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING |
| | GLASS DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO |
| | WILL BE 4 INCHES TO THE FINISH DECK. |
| | NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK |
| | INTO THE DESIGN CRITERIA. |
| | 19A)(3) THE STRUCTURAL PLANS WILL ALSO NEED TO |
| | CORRELATE THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS |
| | STATED ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS |
| | DOORS. |
| | 19A)(4) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK |
| | IS TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS |
| | WILL REQUIRE MECHANICAL FASTENING OF TRACK. |
| | THE RESPONCE INDICATED HOW THEY WOULD MEET THE |
| | ALTERNATIVE METHODS UNDER THE FAIR HOUSING GUIDELINES, |
| | WHICH WILL NEED TO BE FILED WITH THE CLERK OF THE COURT |
| | BEFORE ISSUANCE OF THIS PERMIT. |
| | |
| | 19B-19C) COMPLIED. |
| | |
| | 19D) 2ND REQUEST, PLANS FAIL TO IDENTIFY THE WALL TYPES |
| | THAT SURROUND THE REFUSE SHOOT.707.13.3 REFUSE AND |
| | LAUNDRY CHUTE ACCESS ROOMS. ACCESS OPENINGS FOR REFUSE |
| | AND LAUNDRY CHUTES SHALL BE LOCATED IN ROOMS OR |
| | COMPARTMENTS COMPLETELY ENCLOSED BY CONSTRUCTION THAT |
| | HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR |
| | AND OPENINGS INTO THE ACCESS ROOMS SHALL BE PROTECTED |
| | BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING |
| | OF NOT LESS THAN ? HOUR AND SHALL BE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE. |
| | |
| | A506.2 THE GROUND FLOOR DETAIL (A) WALL TYPE 9/ 800 |
| | PLEASE REVISE TYPO TO 9/801. |
| | |
| | 19E-19G) COMPLIED. |
| | |
| | |
| | 19H) 2ND REQUEST, PLANS INDICATE BETWEEN UNITS 2 |
| | SEPARATE WALLS ONE WITH SOUND PROOFING THE OTHER IS A |
| | TWO HR RATED WALL. PLEASE PROVIDE AN ASSEMBLY HOW THE |
| | TWO WALLS WILL BE BUILT? |
| | A203 & A206 BOTH INDICATE A WALL TYPE 8 BUT THERE IS NO |
| | WALL DISIGNATION FOR THE SECOND WALL INDICATED ON THE |
| | PLAN. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | |
| | 19I) PROVIDE COMPLIANCE WITH:1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 19J) NO, 2ND REQUEST, PROVIDE COMPLIANCE WITH: 1207.3 |
| | STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. NO STC RATING PROVIDED FOR DETAIL 9/A.801. |
| | THE COMMON AREAS WILL NEED TO SHOW COMPLIANCE, THE |
| | INDIVIDUAL UNITS WILL BE REVIEWED UNDER THE TENANT |
| | BUILDOUT, PERMITS WILL BE REQUIRED FOR FLOOR FINISHES |
| | OF UNITS. |
| | |
| | 20-24A) COMPLIED. |
| | |
| | 24B) SEMI-COMPLIED, PLANS STILL INDICATE GRILLS TO BE |
| | INSTALLED SEE A108, PROVIDE MANUFACTURERS SPEC. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 24C) PROVISO; SHOP DRAWINGS FOR CATWALKS TO BE REVIEWED |
| | BY DESIGN PROFESSIONAL BEFORE SUBMITION TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | 24D-24F) COMPLIED. |
| | |
| | 24G) A107 THE PENTHOUSE UNITS DO HAVE THEIR OWN MEANS |
| | OF EGRESS USING THE SPIRAL STAIRS (1009.9.3) THEY ARE |
| | NOT ALLOWED TO USE THE DOORS BETWEEN UNITS FOR MEANS OF |
| | EGRESS, 1013.2 EGRESS THROUGH INTERVENING ROOMS. |
| | |
| | 24H-26B)COMPLIED. |
| | |
| | 26C) SEMI-COMPLIED) SHEET A201 EGRESS WINDOWS THE |
| | MINIMUM HEIGHT IS 24 INCHES, THE WORDING IS STILL |
| | TWENTY-TWO INCHES PLEASE MAKE CORRECTION, 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 26D) COMPLIED. |
| | |
| | 27) SHEET A201; |
| | |
| | 27A) 2ND REQUEST , PLANS INDICATE A 3'-4" MINIMUM ENTRY |
| | BETWWEN THE CABINETRY INTO THE KITCHEN, BUT THE FAIR |
| | HOUSING NOTES ON SHEET A700 NOTE 5 USABLE KITCHENS |
| | INDICATES THE MEASUREMENT IS TAKEN FROM THE EDGE OF |
| | COUNTER TOPSTO THE HANDLES OF APPLIANCES, |
| | REFRIGARATORS DEPHT MINIMUM IS 30 1/2 INCHES, RANGES 27 |
| | INCHES. PLEASE ADJUST THE PLANS TO HAVE A CLEAR NET |
| | OPENING OF |
| | 3'-4". |
| | 27B) COMPLIED. |
| | |
| | 27C) SEMI-COMPLIED, SEE 19A. |
| | |
| | 28-32A) COMPLIED. |
| | |
| | 32B) 2ND REQUEST, THE KITCHEN INDICATES A MINIMUM OF |
| | 40" CLEAR BUT THE MEASUREMENT IS TO BE TAKEN FROM THE |
| | EDGE OF THE COUNTER TOP TO THE HANDLE OF THE 27" DEEP |
| | RANGE, SEE FAAIR HOUSING NOTE 5 LOCATED ON SHEET A700. |
| | |
| | 33-41A) COMPLIED. |
| | |
| | 41B) SEMI-COMPLIED, ATACHMENT DETAIL OF CURBING AS |
| | SHOWN ON S7.2 INDICATES THE USE OF RFB, PLANS DO NOT |
| | INDICATE WHO MAKES THIS ITEM? 106.1.2 ADDITIONAL |
| | INFORMATION. |
| | |
| | 41C) 2ND REQUESTSHEET A804 PLANS MAKE REFERENCE TO |
| | THE SFBC, PLEASE MAKE CORRECTION. |
| | |
| | 41-42) COMPLIED. |
| | |
| | 43A) SEMI-COMPLIED. PILING, SHEET S-3.02 NOTE 4 |
| | REFERENCES THE 2001 FBC |
| | 43B) S-3.02 NOTE# 10 INDICATES THE USE OF 16 INCH PILE |
| | WHEREAS S-3.01 & S-3.02 BOTH INDICATE THE USE OF 18 |
| | INCH PILE PLEASE CORRELATE PLANS, 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 44) COMPLIED. |
| | |
| | 45) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| | M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF |
| | PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | ROOFING REPORT SUBMITTED IS FOR A WOOD DECK SEE A-306 |
| | |
| | 46) COMPLIED. |
| | |
| | 47) COMPLIED. |
| | |
| | 8) PLANS ARE TO SHOWCOMPLIANCE WITH: |
| | 403.8 FIRE COMMAND . |
| | A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL |
| | BE PROVIDED IN A LOCATION APPROVED BY THE FIRE |
| | DEPARTMENT. |
| | |
| | |
| | |
| | 403.10 STANDBY POWER. |
| | A STANDBY POWER SYSTEM COMPLYING WITH SECTION 2702 |
| | SHALL BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN |
| | SECTION 403.10.2 . |
| | |
| | 403.10.1 SPECIAL REQUIREMENTS FOR STANDBY POWER |
| | SYSTEMS. |
| | IF THE STANDBY SYSTEM IS A GENERATOR SET INSIDE A |
| | BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE |
| | ROOM ENCLOSED WITH 2-HOUR FIRE-RESISTANCE-RATED FIRE |
| | BARRIER ASSEMBLIES. SYSTEM SUPERVISION WITH MANUAL |
| | START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE |
| | FIRE COMMAND CENTER. |
| | |
| | 403.10.2 STANDBY POWER LOADS. |
| | THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 1. |
| | POWER AND LIGHTING FOR THE FIRE COMMAND CENTER REQUIRED |
| | BY SECTION 403.8 ; |
| | 2.ELECTRICALLY POWERED FIRE PUMPS; |
| | 3.VENTILATION AND AUTOMATIC FIRE DETECTION |
| | EQUIPMENT FOR SMOKEPROOF ENCLOSURES. |
| | STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN |
| | ACCORDANCE WITH SECTION 3003 . |
| | |
| | 403.11 EMERGENCY POWER SYSTEMS. |
| | AN EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702 |
| | SHALL BE PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED |
| | IN SECTION 403.11.1 . |
| | |
| | 403.11.1 EMERGENCY POWER LOADS. |
| | THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS: |
| | |
| | 1.EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION |
| | REQUIRED BY CHAPTER 10 ; |
| | 2.ELEVATOR CAR LIGHTING; |
| | 3.EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; 4. |
| | AUTOMATIC FIRE DETECTION SYSTEMS; AND |
| | 5.FIRE ALARM SYSTEMS. |
| | |
| | 403.12 STAIRWAY DOOR OPERATION. |
| | STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS |
| | SHALL BE PERMITTED TO BE LOCKED FROM |
| | STAIRWAY SIDE. STAIRWAY DOORS THAT ARE LOCKED FROM THE |
| | STAIRWAY SIDE SHALL BE CAPABLE OF BEING UNLOCKED |
| | SIMULTANEOUSLY WITHOUT UNLATCHING UPON A SIGNAL FROM |
| | THE FIRE COMMAND CENTER. |
| | |
| | 403.12.1 STAIRWAY COMMUNICATIONS SYSTEM. |
| | A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM |
| | CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION |
| | SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN |
| | EACH REQUIRED STAIRWAY WHERE THE DOORS TO THE STAIRWAY |
| | ARE LOCKED. |
| | |
| | 403.13 SMOKEPROOF EXIT ENCLOSURES. |
| | EVERY REQUIRED STAIRWAY SERVING FLOORS MORE THAN 75 |
| | FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE |
| | DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH SECTIONS |
| | 909.20 AND 1019.1.8 . |
| | |
| | 403.14 RESERVED. |
| | |
| | **403.15 SMOKE CONTROL SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTION 909.** |
| | 909.16 FIRE-FIGHTER?S SMOKE CONTROL PANEL. |
| | A FIRE-FIGHTER?S SMOKE CONTROL PANEL FOR FIRE |
| | DEPARTMENT EMERGENCY RESPONSE PURPOSES ONLY SHALL BE |
| | PROVIDED AND SHALL INCLUDE MANUAL CONTROL OR OVERRIDE |
| | OF AUTOMATIC CONTROL FOR MECHANICAL SMOKE CONTROL |
| | SYSTEMS. THE PANEL SHALL BE LOCATED IN A FIRE COMMAND |
| | CENTER COMPLYING WITH SECTION 911 IN HIGH-RISE |
| | BUILDINGS OR BUILDINGS WITH SMOKE PROTECTED ASSEMBLY |
| | SEATING. IN OTHER BUILDINGS, THE FIRE-FIGHTER?S SMOKE |
| | CONTROL PANEL SHALL BE INSTALLED IN AN APPROVED |
| | LOCATION ADJACENT TO THE FIRE ALARM CONTROL PANEL. THE |
| | FIRE-FIGHTER?S SMOKE CONTROL PANEL SHALL COMPLY WITH |
| | SECTIONS 909.16.1 THROUGH 909.16.3 . |
| | |
| | 909.16.1 SMOKE CONTROL SYSTEMS. |
| | FANS WITHIN THE BUILDING SHALL BE SHOWN ON THE |
| | FIRE-FIGHTER?S CONTROL PANEL. A CLEAR INDICATION OF THE |
| | DIRECTION OF AIRFLOW AND THE RELATIONSHIP OF COMPONENTS |
| | SHALL BE DISPLAYED. STATUS INDICATORS SHALL BE PROVIDED |
| | FOR ALL SMOKE CONTROL EQUIPMENT, ANNUNCIATED BY FAN AND |
| | ZONE, AND BY PILOT-LAMP-TYPE INDICATORS AS FOLLOWS: |
| | 1.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN |
| | THEIR NORMAL STATUS?WHITE. |
| | 2.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN |
| | THEIR OFF OR CLOSED STATUS?RED. |
| | 3.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN |
| | THEIR ON OR OPEN STATUS?GREEN. |
| | 4.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN A |
| | FAULT STATUS?YELLOW/AMBER. |
| | |
| | 909.16.2 SMOKE CONTROL PANEL. |
| | THE FIRE-FIGHTER?S CONTROL PANEL SHALL PROVIDE CONTROL |
| | CAPABILITY OVER THE COMPLETE SMOKE-CONTROL SYSTEM |
| | EQUIPMENT WITHIN THE BUILDING AS FOLLOWS: |
| | 1.ON-AUTO-OFF CONTROL OVER EACH INDIVIDUAL PIECE |
| | OF OPERATING SMOKE CONTROL EQUIPMENT THAT CAN ALSO BE |
| | CONTROLLED FROM OTHER SOURCES WITHIN THE BUILDING. THIS |
| | INCLUDES STAIRWAY PRESSURIZATION FANS; SMOKE EXHAUST |
| | FANS; SUPPLY, RETURN AND EXHAUST FANS; ELEVATOR SHAFT |
| | FANS AND OTHER OPERATING EQUIPMENT USED OR INTENDED FOR |
| | SMOKE CONTROL PURPOSES. |
| | 2.OPEN-AUTO-CLOSE CONTROL OVER INDIVIDUAL DAMPERS |
| | RELATING TO SMOKE CONTROL AND THAT ARE ALSO CONTROLLED |
| | FROM OTHER SOURCES WITHIN THE BUILDING. |
| | 3.ON-OFF OR OPEN-CLOSE CONTROL OVER SMOKE CONTROL |
| | AND OTHER CRITICAL EQUIPMENT ASSOCIATED WITH A FIRE OR |
| | SMOKE EMERGENCY AND THAT CAN ONLY BE CONTROLLED FROM |
| | THE FIRE-FIGHTER?S CONTROL PANEL. |
| | |
| | |
| | 49)COMPLIED. |
| | |
| | 50) NEW,PROVIDE INFORMATION ON THE VENTILATION OF THE |
| | ENCLOSED PARKING GARAGE. 406.4.2 VENTILATION. A |
| | MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL . |
| | NOTEFLORIDA ADMINISTRATIVE CODE RULE 9B-3.0472 EVERY |
| | BUILDING WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED |
| | ON OR AFTER 7-1-08 AND HAVING A FOSSIL -FUEL- BURNING |
| | HEATER OR APPLIANCE OR AN ATTACHED GARAGE SHALL HAVE AN |
| | OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 |
| | FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. IN |
| | CONSTRUCTION ALARMS SHALL RECEIVE THEIR PRIMARY POWER |
| | FROM |
| | THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FROM THE |
| | LOCAL POWER UTUILIY SUCH ALARMS SHALL HAVE BATTERY BACK |
| | UP. BOMBINATION SMOKE/ CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | |
| | 51)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST |
| | BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | THIS REVIEW IS MAY HAVE ADDITIONAL COMMENTS AS A RESULT |
| | OF THE DESIGNERS ANSWERS TO THE PLAN REVIEW OR NEW |
| | INFORMATION BEING ADDED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | FLAGLER BEACH CLUB TOWER 1ST REVIEW.DOC |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |