| Date |
Text |
| 2007-04-23 19:03:51 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | MUNICIPAL CODE WPB |
| | |
| | 1. SHT 2 OF 6A BACKFLOWS FOR THE DOMESTIC WATER SERVICE |
| | SHALL BE AT LEAST THE SAME SIZE AS THE LINE IN WHICH |
| | THER ARE INSTALLED.4" BACKFLOWS ARE REQUIRED. 4" |
| | WATER SERVICE SHOWN. TABLE 603.1(D). |
| | |
| | 2. SHT 358-9 ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF |
| | PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING |
| | BUSINESS, THEY SHALL ALSO INDICATE THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET.FAC |
| | 61G15-23.002(1)(2) & FS 471.025. |
| | |
| | 3. SHT A01.2 SUBMIT THE MANUF. SPECIFICATION SHEETS FOR |
| | THE LIFT STATION. SECTIONS 106.1.2 & 303.2 303.4. |
| | |
| | 4. SHT A01.3 SECONDARY ROOF DRAINS REQUIRED FOR THE |
| | AREA NEAR STAIR G1, PUMP ROOM, LAWN EQUIP. ETC. |
| | SECTIONS 1107.1 & 1107.2. |
| | |
| | 5. SHT A01.3 THERE IS NO PRIMARY OR SECONDARY ROOF |
| | DRAINS INDICATED IN THE AREA OF STAIR G2, EMERGENCY |
| | GENERATOR ROOM AND LIFT AS REQUIRED IN SECTIONS 1101.2, |
| | 1107.1 & 1107.2. |
| | |
| | 6. SHT A01.3 ROOF DRAINS LOCATED AT THE WALLS STATES 4" |
| | RD (TYP) SEE PLUMBING DRAWINGS & DETAIL. PLEASE |
| | INDICATE WHERE IN THE PLUMBING PLANS THESE CAN BE |
| | FOUND. SECTION 106.1.1. |
| | |
| | 7. SHT A01.3ROOF DRAINS ARE SHOWN IN AREAS INDICATED |
| | AS MULCH AREAS.MORE INFORMATION IS REQUIRED. PLEASE |
| | INDICATE HOW THE MULCH WILL BE KEPT FROM DRAINING INTO |
| | THE ROOF DRAINS AND OR CLOGING THE ROOF DRAINS AND |
| | PREVENTING THEM FROM DRAINING PROPERLY.PLEASE SUBMIT |
| | A DETAIL FOR THE DRAINS IN THESE AREAS. SECTION 104.6. |
| | |
| | 8. SHT A01.3ROOF DRAINAGE INDICATES DETAILS A/A803 & |
| | D/A803. SECTION 1105.1 STATES ROOF DRAINS SHALL HAVE |
| | STRAINERS EXTENDING NOT LESS THAN 4 INCHES ABOVE THE |
| | SURFACE OF THE ROOF IMMEDIATELY ADJACENT TO THE ROOF |
| | DRAINS. STRAINER SHALL HAVE AN AVAILABLE INLET AREA, |
| | ABOVE THE ROOF, OF NOT LESS THAN ONE AND ONE-HALF TIMES |
| | THE AREA OF THE CONDUCTOR OR LEADER TO WHICH THE DRAIN |
| | IS CONNECTED. PLEASE INDICATE HOW THIS AND THE FACT |
| | THAT THE ROOF DRAIN WILL BE COVERED WITH ROCKS WILL |
| | MEET THIS CODE REQUIREMENT. THERE IS A CONCERN THAT THE |
| | GRASS CLIPPINGS, DIRT, MOSS BUILD UP ETC WILL |
| | EVENTUALLY KEEP THE DRAIN FROM DRAINING AS INTENDED. |
| | PLEASE SUBMIT INFORMATION ON HOW THIS WILL BE |
| | ADDRESSED. SECTION 104.6. |
| | |
| | 9. SHT A01.3 OVERFLOW DRAINS DETAILS B/A803 & C/A803 DO |
| | NOT MEET THE INTENT OF THE CODE TO BE USED ONLY IN CASE |
| | OF BLOCKAGE OF THE PRIMARY ROOF DRAINS. THESE DETAILS |
| | INDICATE THAT THE DRAINS ARE FLUSH WITH THE ROOF AND |
| | WILL DRAIN WHEN THE PRIMARY ROOF DRAINS DRAIN AND NOT |
| | AFTER THE BUILDUP OF A BLOCKED PRIMARY DRAIN. DRAINS |
| | INDICATED IN DETAIL C/A803 ARE SHOWN TO BE NEXT TO AN |
| | AREA THAT HAS MULCH IN IT. PLEASE CLARIFY AND INDICATE |
| | HOW THE MULCH WILL NOT BLOCK THE DRAINS. SECTION |
| | 1107.1 |
| | |
| | 10. SHT A01.3 SHOWS 4" RD'S IN PLANTERS. PLEASE |
| | CLARIFY. PLEASE SUBMIT A DETAIL. SECTION 106.1.1. |
| | |
| | 11. SHT A01.3 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH |
| | DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT |
| | CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM |
| | ROOF AREAS ABOVE. |
| | |
| | 12. SHT A01.3 UPPER ROOF PLANS. PER SECTION 1107.1 |
| | SECONDARY ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED |
| | WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE |
| | ROOF. PER SECTION 1107.2 SEPARATE SYSTEMS ARE REQUIRED. |
| | PLEASE SHOW THE SECONDARY ROOF DRAINS/SCUPPERS. |
| | |
| | 13. SHT A01.3 INDICATE IF THE WATERFALL WILL HAVE A |
| | SEPARATE WATER SUPPLY. IF SO INDICATE THE REQUIRED |
| | METHOD OF BACKFLOW PREVENTION. SECTION 608. ALSO |
| | INDICATE IF THERE WILL BE A DRAIN FOR THE WATERFALL. |
| | SECTION 106.1.1. |
| | |
| | 14. SHT A101 SHOW THE CLEAR FLOOR SPACE FOR ALL |
| | ACCESSIBLE FIXTURES IN ALL TOILET ROOMS. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.17, 11-4.18, 11-4.19 AND 11-4.22 WITH ALL |
| | SUBSECTIONS. |
| | |
| | 15. SHT A104 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH |
| | DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT |
| | CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM |
| | ROOF AREAS ABOVE. |
| | |
| | 16. SHT A107 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH |
| | DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT |
| | CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM |
| | ROOF AREAS ABOVE.--NO SECONDARY ROOF DRAINS ARE |
| | INDICATED FOR THE INTERIOR ROOF DRAIN AREAS AS REQUIRED |
| | IN SECTIONS 11-7.1 & 1107.2. PLEASE SHOW THE LOCATION |
| | OF THE REQUIRED SECONDARY DRAINS.--SCUPPERS |
| | INDICATED AS 4"X8"ALUM. TRANSFER SCUPPERS AS |
| | REFERENCED AS DETAIL C/802 ARE NOT APPROVED. PER |
| | SECTION 1503.4.3. OVERFLOW SCUPPERS SHALL BE PLACED IN |
| | THE WALL NOT LESS THAN 2" NOR MORE THAN 4" ABOVE THE |
| | ROOF. |
| | |
| | 17. SHTS A201, A203, A205, A207 & A209. INDICATE |
| | SPECIFICATION "A" OR "B" FOR ALL UNITS AS REQUIRED PER |
| | PAGES 7.34 & 7.35. |
| | |
| | 18. SHT A201 UNITS A & A REV. INDICATE THE BACKING FOR |
| | THE TUB IN THE MASTER BATH PER PAGE 6.10.--THE WING |
| | WALL NEXT TO THE W/C IN THE MASTER BATH TO BE A MAXIMUM |
| | 2'0" PER PAGE 7.44.--LAVS SHALL BE CENTERED ON THE |
| | 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR |
| | FORWARD APPROACH WITH REMOVABLE BASE CABINET SHALL BE |
| | INDICATED.--SHOW THE CLEAR FLOOR SPACE FOR THE |
| | W/C'S. PAGE 7.43.--RANGE SHALL BE CENTERED ON THE |
| | 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGES 7.4 & |
| | 7.9. --THE OPENING FOR THE W/C'S IN BATH 2 SHALL BE |
| | 33" AND MUST SHOW 18" OFF THE TUB OR LAV TO THE CENTER |
| | OF THE FIXTURE AND 15" MIN. OFF THE OTHER FIXTURE. |
| | PAGES 7.43, 7.44 & 7.45.--MINIMUM CLEARANCES |
| | BETWEEN ALL COUNTERS, APPLIANCES, BASE CABINETS AND |
| | WALLS SHALL BE 40". PAGES 7.8, 7.11, 7.22 & 7.23. 36" |
| | IS SHOWN. PLEASE SHOW COMPLIANCE. |
| | |
| | 19. SHT A203 UNITS B & B REV. INDICATE THE BACKING FOR |
| | THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE |
| | CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH PER |
| | PAGE 7.43.--THE W/C IN THE MASTER BATH SHALL BE 18" |
| | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE PER PAGE |
| | 6.5.--LAVS SHALL BE CENTERED ON THE 48" DIMENSION |
| | OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR FORWARD |
| | APPROACH WITH REMOVABLE BASE CABINET SHALL BE |
| | INDICATED.--BATH #2 OPENING FOR THE W/C SHALL BE |
| | MINIMUM 33". INDICATE MEASURMENT FROM THE CENTERLINE OF |
| | THE W/C TO THE SIDE OF THE VANITY PER PAGES 7.43, 7.44 |
| | & 7.45.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS, |
| | APPLIANCES, BASE CABINETS AND WALLS SHALL BE 40". |
| | (SHOWN AS 36"). PAGES 7.8, 7.11, 7.22 & 7.23. 36". |
| | PLEASE SHOW COMPLIANCE. |
| | |
| | 20. SHT A205 UNIT C. INDICATE THE BACKING FOR THE TUB |
| | IN THE MASTER BATH PER PAGE 6.10.-- SHOW THE CLEAR |
| | FLOOR SPACE FOR THEUSABLE W/C PER PAGE 7.43.-- SHOW |
| | THE CLEAR FLOOR SPACE FOR THE TUBS OR SHOWERS PER PAGES |
| | 7.53 THRU 7.56.--W/C'S SHALL BE 1'6" OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE PER PAGE 6.5. -- |
| | |
| | 21. SHT A207 UNITS D & D REV.INDICATE THE BACKING FOR |
| | THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE |
| | CLEAR FLOOR SPACE FOR THE USABLE W/C PER PAGE 7.43.-- |
| | SHOW THE OPENING FOR THE W/C IN BATH #2 TO BE A MINIMUM |
| | OF 33". THE W/C SHALL BE 1'6" OFF ONE FIXTURE TO THE |
| | CENTERLINE OF THE FIXTURE AND 15" MINIMUM OFF THE OTHER |
| | FIXTURE OR VANITY CABINET PER PAGES 7.43 THRU 7.45.-- |
| | MINIMUM CLEARANCES BETWEEN ALL COUNTERS, APPLIANCES, |
| | BASE CABINETS & WALLS SHALL BE 40". PAGES 7.8, 7.11, |
| | 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW COMPLIANCE. |
| | |
| | 22. SHT A209 UNITS PHA & PHA REV. INDICATE THE BACKING |
| | FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW |
| | THE CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH |
| | PER PAGE 7.43.--THE WING WALL NEXT TO THE W/C IN |
| | THE MASTER BATH SHALL BE A MAXIMUM OF 2'0" PER PAGE |
| | 7.44.--THE LAVS SHALL BE CENTERED ON THE 48" |
| | DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR |
| | FORWARD APPROACH.--A MINIMUM 33" OPENING IS |
| | REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE |
| | 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE, |
| | AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY |
| | CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS, |
| | APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES |
| | 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW |
| | COMPLIANCE. |
| | |
| | 23. SHT A212 UNITS PHB & PHB REV. INDICATE THE BACKING |
| | FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW |
| | THE CLEAR FLOOR SPACE FOR THE USABLE W/C IN THE MASTER |
| | BATH PER PAGE 7.43.--THE W/C IN THE MASTER BATH |
| | SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE |
| | FIXTURE PER PAGE 6.5.--THE LAVS SHALL BE CENTERED |
| | ON THE 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE |
| | 7.48 OR FORWARD APPROACH.--A MINIMUM 33" OPENING IS |
| | REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE |
| | 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE, |
| | AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY |
| | CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS, |
| | APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES |
| | 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW |
| | COMPLIANCE. |
| | |
| | 24. SHT A214 INDICATES DETAIL B/A802 BUT NO SCUPPER IS |
| | SHOWN. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 25. SHT A215 INDICATE THE BACKING FOR THE TUB IN BOTH |
| | BATHS PER PAGE 6.10.--SHOW THE CLEAR FLOOR SPACE |
| | FOR THE W/C IN BOTH BATHS PER PAGE 7.43.--THE W/C |
| | IN BOTH BATHS SHALL BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE PER PAGE 6.5.--THE LAVS |
| | IN THE MASTER BATH SHALL BE CENTERED ON THE 48" |
| | DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR |
| | FORWARD APPROACH. PLEASE SHOW COMPLIANCE. |
| | |
| | 26. SHT A400 GROUND FLOOR AND COMMON AREA FINISH |
| | SCHEDULE. ROOMS 106, 107 & 108 SHOW WALLBOARD FOR THE |
| | FINISH. PER SECTION 1210.2 WALLS WITHIN 2 FEET OF A W/C |
| | OR URINAL SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE TO A HEIGHT OF 4' ABOVE THE FLOOR. WALLBOARD |
| | DOES NOT COMPLY WITH THIS REQUIREMENT. PLEASE INDICATE |
| | METHOD OF COMPLIANCE. |
| | |
| | 27. SHT A404 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR |
| | W/C'S: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | B. 11-4.16.6 DISPENSERS |
| | __FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 28. SHT A405 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR |
| | W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.4 GRAB BARS (1-1/2" BETWEEN THE WALL & |
| | GB) |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | __STALLS: |
| | A. SEE FIG. 30E |
| | __LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.5 FAUCETS |
| | __FOR THE SHOWER: |
| | A. 11-4.21.3 SEAT HEIGHT |
| | B. 11-4.21.5 CONTROL HEIGHT |
| | |
| | 29. SHT A700 INDICATES PALM BEACH COUNTY ACCESSIBILITY |
| | NOTES. THE CODE REFERENCE SHALL BE FBC-2004 CHAPTER 11 |
| | AND/OR FHA-98 DESIGN MANUAL. PLEASE CHANGE REFERENCE. |
| | |
| | 30. SHT A7.00 NOTE 04) D) INDICATESLAVATORIES TO BE |
| | 15"FROM THE WALL TO THE CENTERLINE OF THE FIXTURE. |
| | PER PAGE 7.48 THE LAV SHALL BE A MINIMUM OF 24" TO THE |
| | CENTERLINE OF THE FIXTURE OFF THE WALL OR CENTERED ON |
| | THE 48" DIMENSION OF THE CLEAR FLOOR SPACE, OR IF |
| | FORWARD APPROACH INDICATE REMOVABLE BASE CABINETS. |
| | |
| | 31. SHT A700 NOTE AFTER 16) REFERENCES PALM BEACH |
| | COUNTY AND MOST OF THE NOTE IS NOT LEGIBLE. PLEASE |
| | CORRECT THE JURISDICATION OF AUTHORITY AND MAKE SURE |
| | THE NOTE IS OF SUFFICIENT CLARITY TO INDICATE |
| | INFORMATION SUBMITTED. SECTION 106.1.1. |
| | |
| | 32. SHT A700 THE FINAL NOTE IN THE NOTE SECTION (04) |
| | SHALL BE DELETED. PER FHA-98 DESIGN MANUAL, THE |
| | RESPONSIBILITY FOR COMPLYING WITH THE LAW RESTS WITH |
| | ANY AND ALL PERSONS INVOLVED IN THE DESIGN AND |
| | CONSTRUCTION OF COVERED MULTIFAMILY DWELLINGS. THIS |
| | DOES NOT INCLUDE LOCAL OR STATE GOVERNMENTS, AND TO TRY |
| | TO RELIEVE ONE SELF FROM LIBILITY WITH A NOTE WILL NOT |
| | BE APPROVED. PAGE 22 FHA-98 DESIGN MANUAL. |
| | |
| | 33.SHT A805 DETAIL A INDICATES A TRENCH DRAIN. PLEASE |
| | INDICATE WHERE THIS CAN BE FOUND ON THE FLOOR PLAN. |
| | SECTION 106.1.1. |
| | |
| | 34. SHT A806 THE SQUARE FOOTAGE FOR ALL EXTERIOR |
| | PLANTERS SHALL INDICATE 1/2 THE AREA OF ALL VERTICAL |
| | WALLS. IN THE CASE OF PLANTERS AGAINST THE BUILDING |
| | THIS WILL INCLUDE THE 1/2 THE AREA OF THE BUILDING UP |
| | TO THE PARAPETS OF THE ROOF. PLEASE SUBMIT THE |
| | CALCULATIONS FOR THESE PLANTER DRAINS PER TABLE |
| | 1106.3. |
| | |
| | 35. SHTS LP-1, LP-2, MP-1 & IR-1. THE LICENSE FOR THE |
| | LANDSCAPE ARCHITECT IS NULL & VOID AS OF 11-30-1995. -- |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER, (BUSINESS |
| | LICENSE), IS NOT ISSUED AS THE STATUS IS FOR AN |
| | APPLICANT.--THE ADDRESS FOR MAJESTIC VIEWS |
| | LANDSCAPE ARCHITECTS INC SHOWN ON THE TITLE BLOCK DOES |
| | NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE |
| | DBPR WEBSITE. (SEE ATTACHED SHEETS). THIS INFORMATION |
| | SHALL BE REQUIRED AND APPROVED PRIOR TO ISSUING THE |
| | PERMIT. |
| | |
| | 36. SHT P-1A 4" 2050SF NOT APPROVED. MINIMUM 5" |
| | REQUIRED OR INDICATE SLOPE OF PIPE PER TABLE 1106.3. |
| | |
| | 37. SHT P-1A 4" SECONDARY DRAIN BY THE FPL VAULT |
| | REQUIRED TO BE 5" MINIMUM OR INDICATE THE SLOPE OF PIPE |
| | PER TABLE 1106.3. |
| | |
| | 38. SHT P-1A INDICATE THE SQUARE FOOTAGE BEING DRAIN |
| | FOR EACH SECONDARY ROOF DRAIN. TABLE 1106.3. |
| | |
| | 39. SHT P-1A 4" DD 400SF NOT ADDED TO HORIZONTAL |
| | UNDERGROUND TOTAL SQUARE FOOTAGE. |
| | |
| | 40. SHT P-1B PLAN INDICATED ON SHEET INDEX HAS NOT BEEN |
| | SUBMITTED. SUBMIT A 2ND FLOOR/ROOF PLAN FOR THE GARAGE. |
| | SHOW ALL ROOF DRAINS, SECONDARY ROOF DRAINS, WATER |
| | SUPPLY & BACKFLOW FOR THE WATERFALL ETC. SECTION |
| | 106.1.2. |
| | |
| | 41. SHT P-1C THE GENERATOR & GENERATOR FUEL INFORMATION |
| | IS FOR MECHANICAL PLAN REVIEW. PLEASE MOVE THE |
| | INFORMATION TO THE MECHANICAL SHEETS. |
| | |
| | 42. SHT P-2 THE W/C & LAV BY COL. LINE H/6 DOES NOT |
| | CONNECT TO THE BRANCH LINE. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 43. SHT P-2 SHOWS 2 3" SPK DRAIN LINES CONNECTING TO |
| | THE STORM SYSTEM. THIS IS NOT APPROVED PER CITY CODE |
| | SECTION 90-203(A). CONNECT THE DRAIN LINES TO THE |
| | SANITARY SYSTEM. |
| | |
| | 44. SHT P-2 RELIEF VENTS ARE REQUIRED FOR THE AAV'S |
| | SERVING THE FLOOR DRAINS IN THE PUMP ROOMS. SECTION |
| | 917.3.2. |
| | |
| | 45. SHT P-2 THE HOSE BIBB IN THE TRASH ROOM DOES NOT |
| | CONNECT TO THE WATER SUPPLY MAIN. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 46. SHT P-2 THE FITTING CONNECTING THE HORIZONTAL |
| | BRANCH LINE FOR THE RWL IN "CART" ROOM GUIDES THE STORM |
| | WATER AGAINST THE FLOW. SECTIONS 706.3 & 1101.6. |
| | |
| | 47. SHT P-3 SHOW THE PIPING TO EACH FIXTURE IN EACH |
| | UNIT AT THE BASE OF EACH STACK ON THE FLOOR PLAN. |
| | SECTION 106.1.2. |
| | |
| | 48. SHT P-3 SHOWS 4 PLANTER DRAINS BUT ONLY SHOWS |
| | PIPING AND SQUARE FOOTAGE TO 2 PLANTER DRAINS. PLEASE |
| | SHOW THE PIPING & SF TO ALL PLANTER DRAINS. SECTION |
| | 1101.2. |
| | |
| | 49. SHT P-3 RWL SHOWS 1730SF, BUT SAME RWL IS INDICATED |
| | AS DRAINING 2010SF ON THE LEVELS ABOVE AND BELOW. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 50. SHTS P-4 & P-5 THE RISER DESIGNATION FORRISER |
| | S/14 IS NOT INDICATED. PLEASE SHOW RISER DESIGNATION. |
| | SECTION 106.1.2. |
| | |
| | 51. SHT P-5 THE TYPICAL FLOOR PLAN (4-14) SHOWS AREAS 1 |
| | & 2 WITH ROOF DRAINS. IS THIS TYPICAL FOR ALL FLOORS |
| | (4-14)? PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 52. SHT P-7 SINKS FOR 3 UNITS ARE NOT SHOWN DRAINING TO |
| | ANY RISER DIAGRAMS. PLEASE INDICATE WHERE THESE SINKS |
| | ARE DRAINING TO AND SHOW THE CONNECTION ON THE RISER |
| | DIAGRAM WHEN INDICATING WHERE THE SINKS ARE DRAINING |
| | TO. SECTION 106.1.1. INDICATE TOTAL FIXTURE UNITS FOR |
| | STACK WHEN ADDING THE SINK. TABLE710.1(2). |
| | |
| | 53. SHT P-7 THE COOLING TOWER OVERLFOW SHALL BE |
| | INDIRECTLY DRAINED TO THE STORM SYSTEM, AND THE COOLING |
| | TOWER DRAIN SHALL BE INDIRECTLY DRAINED TO THE SANITARY |
| | SYSTEM.PLEASE INDICATE ON THE PLANS AND SHOW ON THE |
| | RISER DIAGRAMS. SECTION 106.1.1. |
| | |
| | 54. SHT P-7 THE VENT THRU THE ROOF FOR STACK S-7 IS NOT |
| | INDICATED ON THE ROOF PLAN. PLEASE SHOW VTR ON PLANS. |
| | SECTION 903.3. |
| | |
| | 55. SHT P-8 UNIT "A" WATER RISER DIAGRAM. A FULL OPEN |
| | VALVE IS REQUIRED ON THE SUPPLY LINE TO THE WATER |
| | HEATER. SECTION 606.1(7). |
| | |
| | 56. SHT P-8 UNIT "B" WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE REF. & AT THE PDR ROOM. |
| | --THE SHOWER IS INDICATED AS A TUB IN THE M/B BY THE |
| | W/C.-- THE WATER SUPPLY TO THE REF. IS NOT INDICATED |
| | ON THE FLOOR PLAN.PLEASE CORRECT THE WATER RISER |
| | DIAGRAM & FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 57. SHT P-9 UNIT "D"FLOOR PLAN DOES NOT SHOW THE |
| | WATER SUPPLY CONNECTION FROM THE REF. TO THE WATER |
| | MAIN.--THE WATER RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLANAT THE REF. PLEASE SHOW PIPING ON THE |
| | FLOOR PLAN AND SHOW PIPING ON THE RISER DIAGRAM THAT |
| | REFLECT THE FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 58. SHT P-9 UNIT "C"THE WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE SINK, D/W, W/M & AT THE |
| | CONNECTION FROM THE W/H TO THE WATER MAIN OVERHEAD. |
| | PLEASE CORRELATE INFORMATION. SECTION 106.1.1. |
| | |
| | 59. SHT P-10 PH UNIT "A" FLOOR PLAN. INDICATE WHERE THE |
| | REF. WATER SUPPLY CONNECTS TO THE WATER MAIN. SECTION |
| | 106.1.1.--SUBMIT A UNIT "A" WATER RISER DIAGRAM |
| | THAT REFLECTS THE FLOOR PLAN. SECTION |
| | 106.3.5.1.3(3)(10)(13). |
| | |
| | 60. SHT P-11 PH UNIT "B" FLOOR PLAN. INDICATE WHERE THE |
| | REF. WATER SUPPLY CONNECTS TO THE WATER MAIN. SECTION |
| | 106.1.1.--SUBMIT A UNIT "A" WATER RISER DIAGRAM |
| | THAT REFLECTS THE FLOOR PLAN. SECTION |
| | 106.3.5.1.3(3)(10)(13). |
| | |
| | 61. SHT P-12 PH UNIT "C" & PH UNIT "B" SUBMIT WATER |
| | RISER DIAGRAMS. SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 62. SHT P-13 RISERS 1 & 18 DO NOT REFLECT THE FLOOR |
| | PLAN. 1ST & 2ND FLOORS INDICATE SHOWERS, BUT THE FLOOR |
| | PLAN INDICATES TUBS.-- THE PIPING FOR THE SECOND |
| | FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. PLEASE |
| | CORRELATE INFORMATION. SECTION 106.1.1. |
| | |
| | 63. SHT P-13 RISERS 2, 10, 14, 20 & 27 DO NOT REFLECT |
| | THE FLOOR PLAN. ALL RISERS SHOW OFFSETS, BUT OFFSETS |
| | FOR RISERS 2 & 20 ARE DIFFERENT FROM THE OTHER RISERS. |
| | PLEASE CLARIFY & CORRELATE THE INFORMATION FROM THE |
| | RISERS & FLOOR PLANS. SECTION 106.1.1. |
| | |
| | 64. SHT P-13 RISERS 3 & 21 THE PIPING FOR THE SECOND |
| | FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.-- THE |
| | VENT DOES NOT SHOW THE OFFSET INDICATED ON THE FLOOR |
| | PLAN. SECTION 106.1.1. |
| | |
| | 65. SHT P-13 RISERS 4 & 19 THE PIPING FOR THE SECOND |
| | FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.-- |
| | RECHECK THE TOTAL FU COUNT. ADDS UP TO 110FU.-- SHOW |
| | THE SIZE OF THE PIPING TO THE W/M'S AT THE 2ND & 3RD |
| | FLOORS. SECTIONS 106.1.1 & 406.3 & TABLE 709.1. |
| | |
| | 66. SHT P-13 RISERS 5 & 22 THE PIPING FOR THE SECOND |
| | FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION |
| | 106.1.1. |
| | |
| | 67. SHT P-13 RISERS 6 & 23 SHOW ALL PIPE SIZES FROM THE |
| | STACK THRU TO THE LAVS.--RECHECK THE TOTAL FU |
| | COUNT. ADDS UP TO 112FU. TABLES 709.1 & 710.1(2). |
| | |
| | 68. SHT P-13 RISERS 8 & 25THE PIPING FOR THE SECOND |
| | FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.-- VENT |
| | OFFSETS ARE NOT SHOWN. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 69. SHT P-13 RISER 9 THE PIPING FOR THE SECOND FLOOR |
| | FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--VENT |
| | OFFSET IS NOT SHOWN. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 70. SHT P-13 RISER 11 THE PIPING FOR THE SECOND FLOOR |
| | FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION |
| | 106.1.1. |
| | |
| | 71. SHT P-13 RISER 12 THE PIPING FOR THE SECOND FLOOR |
| | FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--SHOW ALL |
| | PIPE SIZES ON RISER. SECTION 106.1.1 & TABLE 710.1(2). |
| | |
| | 72. SHT P-13 RISER 13 THE PIPING FOR THE SECOND FLOOR |
| | FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION |
| | 106.1.1. |
| | |
| | 73. SHT P-13 RISER 15 THE PIPING FOR THE SECOND FLOOR |
| | FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--VENT |
| | OFFSET IS NOT SHOWN. SHOW THE CONNECTION FROM RISER |
| | S/14. SECTION 106.1.1. |
| | |
| | 74. SHT P-13 RISER 16 THE PIPING FOR THE SECOND FLOOR |
| | FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--VENT |
| | OFFSET IS NOT SHOWN.--SINK CONNECTION FROM THE |
| | ROOF NOT SHOWN.--RECHECK THE TOTAL FIXTURE COUNT. |
| | ADDS UP TO 56. SECTION 106.1.1 & TABLE 710.1(2). |
| | |
| | 75. SHT P-13 RISER 17 SHOW ALL PIPE SIZES.--THE |
| | VENT OFFSET IS NOT SHOWN.--RECHECK THE TOTAL |
| | FIXTURE COUNT. ADDS UP TO 98. SECTION 106.1.1 & TABLE |
| | 710.1(2). |
| | |
| | 76. SHT P-14 BACKFLOW PROTECTION IS REQUIRED FOR THE |
| | SUPPLY LINE TO THE TRASH CHUTE FLUSH RING. PLEASE |
| | INDICATE THE METHOD TO BE USED. (AN N-36 VACUUM BREAKER |
| | AT THE TOP OF THE SUPPLY LINE IS AN ACCEPTABLE METHOD). |
| | SECTION 608.--THE PAN DRAIN LINE IS MISLABELED AS |
| | "CD" RISER DIAGRAM. SECTION 106.1.1. |
| | |
| | 77. SHT P-15GAS PIPING RISER DIAGRAM. PLEASE SUBMIT |
| | THE CALCULATION FOR EQUATION 4-2.--SUBMIT |
| | MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | 78. SHT P-15HORIZONTAL WATER ISOMETRIC RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN. OFFSETS IN 1" WATER |
| | MAIN PRIOR TO THE W/H AND TOILET ROOMS IS NOT SHOWN. -- |
| | NO TRAPPED SECTIONS ALLOWED IN THE T/P DISCHARGE LINE. |
| | --MANUF. SPECIFICATION SHEET REQUIRED FOR THE IN-LINE |
| | EXPANSION TANK. SHOW MODEL NUMBER. SECTIONS 106.1.1, |
| | 303.2, 303.4 & 504.6.1. |
| | |
| | 79. SUBMIT A WATER RISER DIAGRAM FOR THE COOLING TOWER |
| | WATER. SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 80. SHT P-16 HORIZONTAL SANITARY ISOMETRIC DIAGRAM. |
| | RECHECK THE DFU'S FOR THE RISERS AND TOTAL AS IT |
| | ACCUMULATES IN THE SYSTEM.--PIPING DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE W/C'S, LAV ETC BY THE SHOWERS & |
| | RISER 27.--THE NOTE FOR REVENT INDICATES CONNTECION |
| | TO RISER #25. RISER #25 DOES NOT SHOW THE VENT |
| | CONECTION.--RELIEF VENTS ARE REQUIRED FOR THE AAV'S |
| | FOR THE FLOOR DRAINS IN THE PUMP ROOMS.TABLE |
| | 710.1(2), SECTIONS 106.1.1 & 917.3.2. |
| | |
| | 81. SHT P-17 RISER DOES NOT REFLECT THE FLOOR PLAN. THE |
| | PIPING FOR THE 4" GD'S, 3" SPA DRAINS, PIPING AROUND 6" |
| | 3106SF, 3" RWL BRANCH LINE ARE NOT SHOWN.SECTION |
| | 106.1.1. |
| | |
| | 82. SHT P-17 THE SIZE OF THE DRAINAGE PIPE SHALL NOT BE |
| | REDUCED IN SIZE IN THE DIRECTION OF FLOW. (6" RWL |
| | REDUCES TO 4"). SECTION 704.2. |
| | |
| | 83. SHT P-17 OFFSETS ARE NOT SHOWN ON THE RISERS TO |
| | REFLECT THOSE SHOWN ON THE FLOOR PLAN FOR THREE RISERS. |
| | CORRELATE INFORMATION . SECTION 106.1.1. |
| | |
| | 84. SHT P-17 4" RWL 1480SF IS INDICATED AS 1340SF AT |
| | THE ROOF DRAIN. PLEASE CORRELATE INFORMATION. SECTION |
| | 106.1.1. |
| | |
| | 85. SHT P-18 HORIZONTAL CONDENSATE ISOMETRIC DIAGRAM. |
| | SHOW ALL PIPE SIZES ON RISER DIAGRAM. SECTION 106.1.1. |
| | |
| | 86. SHT P-19. GARAGE ROOF STORM DRAINAGE ISOMETRIC |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN AT DD 400SF. -- |
| | SHOW THE PIPING & PIPE SIZE OF PIPE BETWEEN THE |
| | STRUCTURES.--2 SECONDARY DRAIN SHOWN AS 4" ARE |
| | REQUIRED TO BE A MINIMUM OF 5". INDICATE PIPE SIZE OR |
| | SLOPE OF PIPE. TABLE 1106.3 & SECTION 106.1.1. |
| | |
| | 87. SHT P-20 FIXTURE CONNECTION SCHEDULE. INDICATE THE |
| | HOT & COLD WATER CONNECTION SIZES TO REFLECT THOSE |
| | SHOWN ON THE WATER RISER DIAGRAM FOR THE WATER HEATER. |
| | SECTION 106.1.1 & TABLE 604.5. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND, |
| | AS WELL AS THE RETURN OF THE RED LINED SET OF PLANS |
| | FROM THE FIRST REVIEW, WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |