| Date |
Text |
| 2007-05-08 17:03:15 | 1. SITE PLAN DOES NOT ILLUSTRATE ANY FIRE HYDRANTS. |
| | |
| | 2. BUILDING 1 AND BUILDING 2 SHALL BE BE FIRE SPRINKLER |
| | PROTECTED IN ACCORDANCE WITH FS 553.895 (2). |
| | |
| | 3. THE DEPICTED ENTRY CONFIGURATION SHALL BE DESIGNED |
| | SO AS TO BE UTILIZED BY FIRE RESCUE. |
| | |
| | 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 5. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| | |
| | 6. SUITABLE ROADS THAT CAN SUPPORT FIRE APPARATUS SHALL |
| | BE PROVIDED DURING CONSTRUCTION ACTIVITIES. |
| | |
| | 7. TEMPORARY STANDPIPE SYSTEMS ARE REQUIRED WHEN THE |
| | BUILDING REACHES THREE STORIES OR THIRTY FEET IN |
| | HEIGHT. |
| | |
| | 8. STANDPIPE SYSTEM FOR FUTURE DOCK MUST BE PERMITTED. |
| | |
| | 9. DEBRIS SHALL BE REMOVED FROM THE SITE AND BUILDING |
| | DAILY. |
| | |
| | 10. PLEASE INDICATE WHAT SAFETY PRACTICES WILL BE |
| | EMPLOYED WHEN THE TORCH APPLIED ROOFING MATERIALS ARE |
| | INSTALLED. |
| | |
| | 11. PLEASE EXPLAIN STAIRS THAT ARE ABSENT OF DOORS. |
| | |
| | 12. PLEASE INDICATE ON THE PLANS THAT VOID SPACES WILL |
| | NOT BE USED FOR ANY PURPOSE. |
| | |
| | 13. ANY SECURITY FEATURES PLANNED SHALL NOT INTERFERE |
| | WITH ANY EXITING FROM THE BUILDING. |
| | |
| | 14. PLEASE ILLUSTRATE ON THE PLANS THAT ALL EXTERIOR |
| | STAIRS AND RAMPS WILL BE SLIP RESISTANT. |
| | |
| | 15. PLEASE EXPLAIN WHY THE PARKING AREA ON THE GROUND |
| | FLOOR OF BUILDING THREE ONLY HAS A ONE HOUR FIRE |
| | RATING. |
| | |
| | 16. ELEVATOR WARNING SIGNS ARE REQUIRED. |
| | |
| | 17. KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING. |
| | |
| | 18. ARCHITECTURAL FEATURES SUCH AS SOFFITS SHALL NOT |
| | INTERFERE WITH WITH THE OPERATION OF ANY FIRE SPRINKLER |
| | HEADS. |
| | |
| | 19. SINCE BUILDING THREE WILL BE CONSIDERED A HIGH-RISE |
| | BUILDING, ALL OF THE REQUIREMENTS SHALL BE MET OF THE |
| | FLORIDA FIRE AND BUILDING CODE. |
| | |
| | 20. THE LOBBY APPEARS TO BE AN ATRIUM AND THE REQUIRED |
| | PROTECTION FOR AN ATRIUM SHALL BE PROVIDED. |
| | |
| | 21. THE NOTE FOR EGRESS WINDOWS ON PAGE A201 DOES NOT |
| | INDICATE A MAXIMUM SILL HEIGHT. |
| | |
| | 22. ELEVATION DRAWING DOES NOT DISPLAY BUILDING |
| | ADDRESS. A MINIMUM OF AT LEAST 6" HIGH NUMBERS WITH 1" |
| | IN WIDTH SHALL BE PROVIDED. |
| | |
| | 23. SERVICE ELEVATOR DOORS LOCATED NEAR STAIR # 2 SHALL |
| | BE MARKED "NO EXIT" SINCE IT IS IN CLOSE PROXIMITY TO |
| | THE STAIR # 2 EXIT DOOR. |
| | |
| | 24. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR |
| | LOCATIONS. |
| | |
| | 25. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE |
| | SIGNS SHALL IDENTIFY THE STAIR IDENTITY, FLOOR LEVEL, |
| | AND TERMINUS TOP AND BOTTOM. |
| | |
| | 26. ALL FIRE AND SMOKE DAMPERS SHALL BE DROP TESTED |
| | AFTER INSTALLATION TO ENSURE PROPER OPERATION. |
| | |
| | 27. THE CARBON MONOXIDE DETECTORS SHOWN ON PAGE AC-01 |
| | SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS |
| | INSTRUCTIONS. SPACING AND AREA TO BE COVERED SHALL NOT |
| | EXCEED THESE REQUIREMENTS. |
| | |
| | 28. MORE DETAILS NEEDED ON THE RECIRCULATION |
| | RESIDENTIAL EXHAUST HOOD DISPLAYED ON PAGE AC-07. |
| | |
| | 29. PLEASE PROVIDE AN ELEVATION DRAWING OF THE |
| | GENERATOR EXHAUST AND STAIR DISPLAYED ON PAGE AC-12. |
| | |
| | 30. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | COMPLETE INSTALLATION OF THE AUTOMATIC FIRE SPRINKLER |
| | SYSTEMS. |
| | |
| | 31. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | INSTALLATION OF THE FIRE ALARM SYSTEM. |
| | |
| | 32. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL |
| | LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | 33. PLEASE INDICATE WHAT THE VOICE EVACUATION MESSAGE |
| | WILL SAY WHEN THE REQUIRED FIRE ALARM SYSTEM IS |
| | ACTIVATED. |
| | |
| | 34. PLEASE INDICATE ON THE PLANS WHAT UL LISTINGS THAT |
| | THE 500 GALLON FUEL TANK WILL HAVE. |
| | |
| | 35. PLEASE DECLARE ON PAGE P-15 THAT THE GAS |
| | INSTALLATION WILL COMPLY WITH NFPA 54. |
| | |
| | 36. THE FDC SHOWN ON PAGE SP-1.1 SHOULD BE ROTATED TO |
| | FACE SOUTH. HOSE MAY KINK THE WAY IS IS POSITIONED. |
| | |
| | 37. WHY ARE BUILDINGS 1 & 2 SHARING A FD CONNECTION. |
| | |
| | 38. FIRE SPRINKLER HEADS THAT ARE LOCATED OUTSIDE SHALL |
| | BE WAX OR CORROSION RESISTANT. |
| | |
| | 39. SOME DRAWINGS ILLUSTRATE THAT CLOSETS ARE FIRE |
| | SPRINKLER PROTECTED AND SOME ARE NOT. PLEASE PROVIDE |
| | DETAILS ON THE PLANS. |
| | |
| | 40. PLEASE PROVIDE MORE DETAILS ON THE PRESSURE |
| | RESTRICTING AND PRESSURE REGULATING DEVICES PLANNED FOR |
| | USE. WILL THESE DEVICES BE FACTORYOR FIELD ADJUSTED. |
| | |
| | 41. THE BACKFLOW DEVICE SHOWN ON PAGE SP-14 SHALL BE |
| | EQUIPPED WITH A CHAIN AND LOCK. |
| | |
| | 42. PLEASE VERIFY ALL DOORS THAT NEED TO BE RATED AS TO |
| | THE RATING AND TYPES THAT CAN BE USED. |
| | |
| | 43. ELECTRIC POWERED SMOKE DETECTORS SHALL BE PROVIDED |
| | ON EVERY LEVEL OF THE RESIDENTIAL UNITS. |
| | |
| | 44. WET FIRE HYDRANTS ARE REQUIRED PRIOR, TO DURING, |
| | AND AFTER CONSTRUCTION. |
| | |
| | 45. THE FLORIDA FIRE PREVENTION CODE REQUIRES THAT |
| | EMERGENCY INSTRUCTIONS BE PROVIDED TO THE RESIDENTS. |
| | PLEASE ADVISE HOW THIS WILL BE ACCOMPLISHED AND ENSURE |
| | THAT THIS REQUIREMENT IS PLACED ON THE PLANS. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4774 FAX |