Plan Review Notes
Plan Review Notes For Permit 07030457
Permit Number 07030457
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-14 09:40:06*** PROVISO **
 *PLANS REDLINED*
  
 1) NOTE: THE DEVICES IN STAIRS MUST MEET NFPA-101 AS
 STATED ON PREVIOUS REVIEW.
 PLEASE SEE THAT EACH LEVEL MUST CONTAIN A MINIMUM OF
 TWO CONTROL DEVICES. THE FAILURE OF A SINGLE CONTROL
 DEVICE MAY NOT LEAVE ANY ONE EGRESS AREA IN TOTAL
 DARKNESS. PLEASE SEE 7.9.2.2
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1 AS THE MAXIMUM
 TIMES FOR(PC) OCCUPANCY TYPE DEVICES SHALL BE 30MINS
 MAX.
  
 ** PLANS TO BE REVISED BEFORE FINAL SHOWING TWO DEVICES
 ON EACH LEVEL. ALONG WIHT ANY OTHER REVISIONS DURING
 CONSTRUCTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  