| Plan Review Notes For Permit 07030457 |
| Permit Number |
07030457 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-14 09:40:06 | *** PROVISO ** | | | *PLANS REDLINED* | | | | | | 1) NOTE: THE DEVICES IN STAIRS MUST MEET NFPA-101 AS | | | STATED ON PREVIOUS REVIEW. | | | PLEASE SEE THAT EACH LEVEL MUST CONTAIN A MINIMUM OF | | | TWO CONTROL DEVICES. THE FAILURE OF A SINGLE CONTROL | | | DEVICE MAY NOT LEAVE ANY ONE EGRESS AREA IN TOTAL | | | DARKNESS. PLEASE SEE 7.9.2.2 | | | | | | 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1 AS THE MAXIMUM | | | TIMES FOR(PC) OCCUPANCY TYPE DEVICES SHALL BE 30MINS | | | MAX. | | | | | | ** PLANS TO BE REVISED BEFORE FINAL SHOWING TWO DEVICES | | | ON EACH LEVEL. ALONG WIHT ANY OTHER REVISIONS DURING | | | CONSTRUCTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | |
|