| Plan Review Notes For Permit 07030457 |
| Permit Number |
07030457 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-27 10:34:11 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.DOOR(S) LEADING DIRECTLY TO A CORRIDOR SHALL BE AN | | | APPROVED, LISTED, AND LABELED FIRE DOOR AND ASSEMBLY IN | | | ACCORDANCE WITH NFPA 80. | | | | | | 3.PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT | | | ENCLOSURE ASSEMBLY SHALL BE LIMITED AS PER NFPA 101 - | | | 7.1.3.2.1 (6) | | | | | | 4.PROVIDE EMERGENCY LIGHTING FOR THE EXIT STAIR | | | ENCLOSURES. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESSWHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | COMMENT WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|