| 2007-03-14 16:45:23 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE STAIR AND EGRESS PATHS MUST |
| | CONTAIN THE EMERGENCY BACK UP LIGHTING TO THE RIGHT OF |
| | WAY; THIS WOULD INCLUDE ANY "VESTIBULE/LANDING" AREAS |
| | DIRECTLY OUTSIDE THE DOORWAY. |
| | PLEASE SEE THAT THE PLANS SHOW SWITCHING ON THE STAIR |
| | AND EGRESS LIGHTING. PLEASE SEE 7.8 AND 7.9 OF THE 2003 |
| | NFPA-101. PLEASE KNOW THAT THE SWITCHING OF A SINGLE |
| | DEVICE SHALL NOT LEAVE ANY ONE AREA IN TOTAL DARKNESS. |
| | IF AN OCCUPANT IN ALREADY IN THE DIRECTION OF TRAVEL IN |
| | AN EMERGENCY OR EVEN UNDER NORMAL CONDITIONS AND A |
| | SWITCH IS TURNED OFF, THIS WOULD CREATE A LIFE SAFETY |
| | ISSUE AND LEAVE AN OCCUPANT IN THE AREA IN DARKNESS. |
| | PLEASE KNOW THAT AUTOMATED SWITCHING BY THE USE OF MORE |
| | THAN ONE OCCUPANCY SENSOR IS PERMITTED HOWEVER |
| | SWITCHING AS SHOWN IS NOT. |
| | PLEASE ADJUST PLANS. |
| | * PLEASE ALSO CLARIFY IF THESE FIXTURES CONTAIN A THIRD |
| | WIRE TO BE CONNECTED AHEAD OF ANY SWITCHING DEVICES SO |
| | THAT THE TURNING OFF OF A SWITCH AS SHOWN OR AN |
| | OCCUPANCY SENSOR TYPE DEVICE DOES NOT CREATE THE |
| | TURNING "ON" OF A FIXTURE ON THE SWITCH LEG. 700.12E |
| | NEC. |
| | |
| | 2) NOTE: PLEASE SEE MISSING PHOTO-METRIC LEVELS AT ALL |
| | EGRESS AREAS INCLUDING WHAT ARE TO BE HALLWAYS AND |
| | OTHER AREAS OF EXIT EGRESS. |
| | NFPA-101 7.8, 7.9 |
| | PLEASE SEE THERE SEEMS TO BE S DIFFERENCE OF THE NUMBER |
| | OF LIGHTING FIXTURES SHOWN ON THE PHOTO-METRIC SHEETS |
| | COMPARED TO THE NUMBER OF LIGHTING FIXTURES ON THE |
| | LIGHTING PLANS. PLEASE VERIFY THIS. (SEE WHAT APPEARS |
| | TO BE A AND D FIXTURES TOGETHER). |
| | |
| | 3) NOTE: PLEASE SEE ANY FIXTURES LOCATED OUTSIDE SHALL |
| | BE LISTED FOR LOCATIONS AS EITHER WET OR DAMP |
| | LOCATIONS. |
| | 110.3 |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT THE ELECTRICAL SHEETS/PLANS. |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |