Plan Review Notes
Plan Review Notes For Permit 07030457
Permit Number 07030457
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-14 16:45:23** UNSAT **
  
  
 1) NOTE: PLEASE SEE THE STAIR AND EGRESS PATHS MUST
 CONTAIN THE EMERGENCY BACK UP LIGHTING TO THE RIGHT OF
 WAY; THIS WOULD INCLUDE ANY "VESTIBULE/LANDING" AREAS
 DIRECTLY OUTSIDE THE DOORWAY.
 PLEASE SEE THAT THE PLANS SHOW SWITCHING ON THE STAIR
 AND EGRESS LIGHTING. PLEASE SEE 7.8 AND 7.9 OF THE 2003
 NFPA-101. PLEASE KNOW THAT THE SWITCHING OF A SINGLE
 DEVICE SHALL NOT LEAVE ANY ONE AREA IN TOTAL DARKNESS.
 IF AN OCCUPANT IN ALREADY IN THE DIRECTION OF TRAVEL IN
 AN EMERGENCY OR EVEN UNDER NORMAL CONDITIONS AND A
 SWITCH IS TURNED OFF, THIS WOULD CREATE A LIFE SAFETY
 ISSUE AND LEAVE AN OCCUPANT IN THE AREA IN DARKNESS.
 PLEASE KNOW THAT AUTOMATED SWITCHING BY THE USE OF MORE
 THAN ONE OCCUPANCY SENSOR IS PERMITTED HOWEVER
 SWITCHING AS SHOWN IS NOT.
 PLEASE ADJUST PLANS.
 * PLEASE ALSO CLARIFY IF THESE FIXTURES CONTAIN A THIRD
 WIRE TO BE CONNECTED AHEAD OF ANY SWITCHING DEVICES SO
 THAT THE TURNING OFF OF A SWITCH AS SHOWN OR AN
 OCCUPANCY SENSOR TYPE DEVICE DOES NOT CREATE THE
 TURNING "ON" OF A FIXTURE ON THE SWITCH LEG. 700.12E
 NEC.
  
 2) NOTE: PLEASE SEE MISSING PHOTO-METRIC LEVELS AT ALL
 EGRESS AREAS INCLUDING WHAT ARE TO BE HALLWAYS AND
 OTHER AREAS OF EXIT EGRESS.
 NFPA-101 7.8, 7.9
 PLEASE SEE THERE SEEMS TO BE S DIFFERENCE OF THE NUMBER
 OF LIGHTING FIXTURES SHOWN ON THE PHOTO-METRIC SHEETS
 COMPARED TO THE NUMBER OF LIGHTING FIXTURES ON THE
 LIGHTING PLANS. PLEASE VERIFY THIS. (SEE WHAT APPEARS
 TO BE A AND D FIXTURES TOGETHER).
  
 3) NOTE: PLEASE SEE ANY FIXTURES LOCATED OUTSIDE SHALL
 BE LISTED FOR LOCATIONS AS EITHER WET OR DAMP
 LOCATIONS.
 110.3
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL SHEETS/PLANS.
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  