| Plan Review Notes For Permit 07030453 |
| Permit Number |
07030453 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-17 16:41:31 | *****DENIED***** | | | | | | | | | 1.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS | | | EAST TAMARIND AVENUE, DISPLAY THE NUMERICAL ADDRESS OF | | | THE BUILDING.AS PER WEST PALM BEACH CODE, ADDRESS | | | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS | | | THAN 1" IN WIDTH. | | | | | | 2.NFPA 101 - 2003 EDITION SHALL BE REFERENCED. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | | PROPERTY OR VICINITY THEREOF (INCLUDING ROADS, STREETS, | | | FIRE LANES). | | | | | | 5.IT IS INDICATED ON SHEET 7 THAT THERE WILL BE PULL | | | STATIONS AND SMOKE DETECTORS.WILL THESE DEVICES BE | | | TIED INTO A LOCAL OR A MONITORED FIRE ALARM SYSTEM? | | | | | | 6.PLEASE DECLARE INTERIOR WALL AND CEILING FINISH | | | MATERIAL IN EXITS, EXIT ACCESS CORRIDORS, AND ALL OTHER | | | AREAS AS CLASS A, CLASS B, OR CLASS C.BE SPECIFIC | | | | | | 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL | | | DISTANCE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|