| 2007-04-15 09:04:46 | ** UNSAT ** |
| | |
| | ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| | CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLANS AT THIS TIME DO NOT INDICATE ANY CODES. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SUBMIT COMPLETED PLANS FOR COMMERCIAL OFFICE |
| | BUILDING APPLICATION. AT THIS TIME THERE ARE MANY ITEMS |
| | ON PLANS WHICH ARE UNDER RESIDENTIAL DESIGN. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETE PLANS WHICH ARE CLEAR |
| | AND VISIBLE FOR ALL ELECTRICAL CIRCUITS, DESIGNATIONS |
| | ETC ON PLANS. PLEASE SEE FBC 106.1.3 WHICH REQUIRES |
| | PLANS TO BE A MINIMUM OF QUALITY. |
| | THERE ARE SEVERAL ITEMS, CIRCUITS ON PLANS WHICH ARE |
| | NOT CLEAR. |
| | PLEASE SEE THERE ARE SOME CIRCUITS WHICH ARE INDICATED |
| | WHICH ARE NOT ON PANEL SCHEDULE. |
| | PLEASE SEE 408.4 OF THE NEC, AND THE FOLLOWING TEXT |
| | BELOW WHICH IS TAKEN DIRECTLY FROM THE NEC. |
| | PLEASE KNOW THAT THE PLANS NEED TO LABEL AND PROVIDE |
| | ROOM AND AREA DESIGNATIONS ON PLANS AND CORRELATE WITH |
| | THE PANEL SCHEDULES SHOWING ALL ROOMS AND AREAS IN |
| | WHICH CIRCUITS FEED WILL BE REQUIRED FOR EACH PANEL. |
| | PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE |
| | CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT |
| | ACCEPTABLE. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 3) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL |
| | LOAD CALCULATIONS. |
| | PLEASE SEE 220.12, 220.14, 220.42, 220.44, 215.5, |
| | 230.42 ETC. |
| | PLEASE SEE THERE ARE CIRCUITS WHICH ARE OVER LOADED. |
| | PLEASE SEE NO LOADS ARE SHOWN FOR COMMERCIAL |
| | APPLICATION. |
| | |
| | 4) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH |
| | THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13. PLEASE |
| | SEE 13-413.1ABC.1, 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2. |
| | NO FIXTURE LEGEND WAS SUBMITTED, NO ENERGY |
| | CALCULATIONS, NO PERFORMANCE CALCULATIONS, ETC |
| | AS PLANS DO NOT INDICATED ANY ELECTRICAL FOR EXISTING |
| | STRUCTURE, SOME OTHER ITEMS FOR CODE COMPLIANCE WITH |
| | RESPECT TO CHAPTER 13 CAN NOT BE DETERMINED AT THIS |
| | TIME. |
| | |
| | 5) NOTE: PLEASE SEE PLANS INDICATE THIS AS AN ADDITION |
| | TO AN EXISTING STRUCTURE, HOWEVER HOW IS THIS EXISTING |
| | BEING FED FROM THE NEW ELECTRICAL SERVICE AS SHOWN. |
| | PLANS DO NOT SHOW CIRCUITING , FEEDS, OR INDICATE ANY |
| | ELECTRICAL FOR REVIEW. |
| | NO REVIEW FOR THIS CAN BE DONE AT THIS TIME. |
| | PLEASE SEE NEC 2005. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | COMPLETE PLANS. |
| | |
| | 6) NOTE: PLEASE SEE 422.13 FOR LOADS FOR WATER HEATER. |
| | |
| | 7) NOTE: PLEASE SEE BATH ROOMS WHICH ONLY INDICATE TWO |
| | FANS, NO CONTROL FOR THESE FANS AND NO LIGHTING IN |
| | THESE TWO BATH ROOMS?? |
| | PLEASE COMPLETE PLANS. |
| | FBC 106.3.5.1.2 |
| | LS 101 7.8 |
| | |
| | 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT PER 110.9. |
| | |
| | 9) NOTE: PLEASE SEE MISSING CWP AS PART OF THE GE |
| | SYSTEM PER 250.50 |
| | |
| | 10) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EMERGENCY AND EXIT LIGHTS. |
| | |
| | 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR HWH. |
| | 422.31 |
| | |
| | 12) NOTE: PLEASE SEE MISSING DISCONNECTS FOR AHU/ CU |
| | PER 440.11. |
| | |
| | 13) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON |
| | TITLE BLOCK FOR THE ARCHITECT OF RECORD PER FAC |
| | 61G1-16.004. |
| | |
| | 14) NOTE: ** ARCHITECT OF RECORD NEEDS TO SEE FS |
| | 481.221. |
| | ONE COPY OF PLANS IS BEING RETAINED. |
| | |
| | ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED TO |
| | SHOW CODE COMPLIANCE AND PLANS ARE NOT COMPLETE AT THIS |
| | TIME, THERE MAY BE NEW COMMENTS WHEN PLANS ARE |
| | RESUBMITTED DUE TO CHANGES AND INFORMATION BEING |
| | SUBMITTED FOR THE FIRST TIME FOR REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-15 08:02:10 | 2007-04-15 08:02:10 |
| | REVIEW IN PROGRESS |