| Plan Review Notes For Permit 07030452 |
| Permit Number |
07030452 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-13 14:33:40 | DENIED BY BUILDING | | | | | | 1) RAS 150 IS NOT ACCEPTED IN THIS JURISDICTION. ALSO, | | | THE CITY OF WEST PALM BEACH IS NOT LOCATED IN THE HIGH | | | VELOCITY HURRICANE ZONE. | | | | | | 2) THE SYSTEM SPECIFIED IN THE NOA IS FOR A WOOD | | | NON-INSULATED DECK. ON SOME OF THE PAPER WORK THAT WAS | | | SUBMITTED 3/4" PERLITE INSULATION IS SPECIFIED. IF THE | | | DECK WILL BE INSULATED,SELECT A SYSTEM FOR AN | | | INSULATED WOOD DECK FROM THE NOA. | | | | | | 3) THE MAXIMUM DESIGN PRESSURE SPECIFIED FOR THE | | | ROOFING MATERIAL, ON PAGE 28 OF THE NOA, IS TOO LOW FOR | | | ROOF ZONE 3 (- 89 PSF) . SEE 2004 FBC TABLE | | | 1609.6.2.1(2). GENERAL LIMITATION #7 ON PAGE 32 OF THE | | | NOA ALLOWS THE PRESSURE TO BE INCREASED BASED ON | | | ENHANCED FASTENER SPACING CALCULATED USING RAS 117. | | | SUBMIT RAS 117 CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|