Plan Review Notes For Permit 07030448
Permit Number 07030448
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-13 11:04:05DENIED BY BUILDING
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE
 PERMIT APPLICATION.
  
 2) INDICATE WHICH ONE OF THE FASTENING OPTIONS AND
 MAXIMUM DESIGN PRESSURE LISTED ON PAGES 9 AND 10 OF THE
 NOA WILL BE USED. CIRCLE THE APPROPRIATE ONE.
  
 3) SEE 2004 FBC TABLE 1609.6.2.1(2) FOR THE REQUIRED
 PRESSURES. ENHANCED FASTENER SPACING WILL BE REQUIRED
 IN ORDER TO MEET THE UPLIFT REQUIREMENTS OF THE CORNER
 AND POSSIBLY THE PERIMETER AREAS. SEE LIMIATION NUMBER
 7 ON THE PAGE 32 OF THE NOA AND SUBMIT RAS 117
 CALCULATIONS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714