| Date |
Text |
| 2007-04-09 14:51:20 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET 2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN AND IS NOT CODE COMPLIANT, PER |
| | FBC-2004 CHAPTER 1, SECTION 106.1.1. |
| | INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| | LOCATIONS. |
| | NOTE: NOT ALL WASTE ,TRAPS AND SIZES WITH CLEANOT |
| | LOCATIONS ARE INDICATED ON SHEET 2 SANITARY ISOMETRIC |
| | RISER DIAGRAM. PLEASE REFERENCE THE ATTACHED SANITARY |
| | ISOMETRIC RISER DIAGRAM TO THE PLUMBING COMMENTS THAT |
| | REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE. |
| | NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE |
| | INCH (3"). |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED |
| | FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). |
| | |
| | (E) 917 AIR ADMITTANCE VALVE (A.A.V.) REQUIRED FOR THE |
| | KITCHEN SINK DUE TO THE FACT A KNEE WALL IS LOCATED |
| | WHERE A VENT THROUGH ROOF IS LOCATED ON SHEET 2. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |