| Plan Review Notes For Permit 07030437 |
| Permit Number |
07030437 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-14 12:38:26 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 2} CIRCUIT #19 DOES NOT COMPLY WITH210.52(B)(1) FOR | | | KITCHEN (SMALL APPLIANCE) CIRCUITS. | | | | | | 3} IF CIRCUIT #27 IS MEANT FOR THE DINNING ROOM | | | RECEPTALES, IT ALSO VIOLATES 210.52(B)(1). SEPERATE THE | | | LIGHTING FROM THE RECEPTACLES IN THIS AREA. SEE 408.4, | | | 2005 NEC FOR CLARIFICATION. | | | | | | 4} INDICATE IF THE PROPOSED SERVICE IS OVERHEAD OR | | | UNDERGROUND. 215.5. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|