| 2007-04-17 16:54:51 | |
| | |
| | DENIED |
| | |
| | 1)PLANS SHALL REFLECT THE CURRENT 2004 FBC WITH 2006 |
| | REVISIONS AND THE CORRECT CONSTRUCTION TYPE. PLEASE SEE |
| | THAT GENERAL NOTE #1 REFLECTS THE 2001 FBC AND TYPE VI |
| | UNPROTECTED AS CONSTRUCTION TYPE. |
| | |
| | 2)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SETS OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561) 233-5025 FOR MOREINFORMATION. |
| | |
| | 3)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION |
| | ON THE WALL SECTIONS PER R403.1.4 FBC RES. |
| | |
| | 4)RESIDENTIAL BUILDINGS SHALL COMPLY WITHR311.4.1 |
| | FBC RES. PROVIDE AT MINIMUM NOT LESS THAN ONE DOOR THAT |
| | MEET THE REQUIREMENTS OF R311.4.2 DOOR SHALL BE 3"-0" |
| | WIDE AND 6"-8" IN HEIGHT |
| | |
| | 5)THE SH24 ( 37"X 49") WINDOWS DO NOT MEET THE MIN |
| | FOR EMERGENCY EGRESS FROM THE BEDROOMS. KINCO WINDOWS |
| | HAVE DESIGNATIONS THAT DIFFER FROM PGT AND OTHER |
| | MANUFACTURERS IF USING THEIR WINDOW PLEASE USE THEIR |
| | DESIGNATION. MOST SH UNITS REQUIRE 5-6" SUBTRACTED FROM |
| | THE HEIGHT THEN DIVIDE IN HALF TO GET CLEAR OPENING |
| | HEIGHT. |
| | |
| | 6)WINDOWS ARE NOT IMPACT RESISTANT THEREFORE PRODUCT |
| | APPROVALS ARE REQUIRED FOR OPENING |
| | PROTECTIVES/SHUTTERS |
| | |
| | 7)PROVIDE ROOF PITCH AND MEAN ROOF HEIGHT ON THE |
| | ELEVATIONS AS REQUIRED FOR ROOF PRODUCT APPROVAL DESIGN |
| | PRESSURE CALCULATIONS. |
| | |
| | 8)SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 9)PLAN NOTE # 10 ON SHEET 3 OF 4 IS INCORRECT. PER |
| | 1609.1.4 FBC PROTECTION OF OPENINGS IS REQUIRED TO MEET |
| | LARGE MISSILE IMPACT TESTS WHEN WITHIN 30 FEET OF |
| | GRADE |
| | |
| | 10)PROVIDE MINIMUM ROOF SHEATHING ATTACHMENT NOTE OR |
| | DETAIL ON DRAWINGS |
| | |
| | 11)SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL. PLEASE SEE MECHANICAL PLAN REVIEW NOTES |
| | AS TO CORRECT FORM TO BE USED |
| | |
| | 12)THE FLORIDA COVER SHEET FOR THE JELD-WEN EXTERIOR |
| | DOOR IS INCORRECT, PLEASE SEE THE NOA'S THAT ARE |
| | COVERED BY FL #498-R1 ARE NOT THE MIAMI-DADE NOA THAT |
| | YOU ARE SUBMITTING. THE CORRECT FL# FOR THIS NOA IS FL# |
| | 539-R1 |
| | |
| | 13)THE FLORIDA COVER SHEET FOR THE ENTERGRA "S" ROOF |
| | TILES IS INCORRECT FL# 7804 USES A TEST LAB REPORT NOT |
| | A MIAMI-DADE NOA. IT REQUIRES FL# 282-R1 |
| | |
| | 14)THE KINCO WINDOWS THAT WERE SUBMITTED ON YOUR NOA |
| | ARE NOT IN THE FLORIDA PRODUCT APPROVAL SYSTEM BUT ARE |
| | IN OUR LOCAL PRODUCT APPROVAL LISTINGS AND THE |
| | MIAMI-DADE NOA IS ALL THAT IS REQUIRED. PLEASE SEE NOTE |
| | 5 TO CONFIRM THEIR USE. |
| | |
| | 15)PROVIDE PRODUCT APPROVALS FOR THE CAST-CRETE |
| | LINTELS OR SUPPLY THERE FL# ON THE LINTEL SCHEDULE AS |
| | WITH THE TRUSS ANCHORS. (CAN BE FOUND UNDER FL# 158 AND |
| | CLICK LINK NOA03-0605.05 FOR 8" WIDE LINTELS) |
| | |
| | 16)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC*. ( ALL SHOP |
| | DRAWINGS AND PRODUCT APPROVALS ARE TO BE REVIEWED AND |
| | APPROVED BY ARCHITECT) |
| | |
| | 17)PROVIDE CORRECTED SURVEY PLEASE SEE THE RIGHT SIDE |
| | OF BUILDING HAS A 2'-0" OFFSET YET BOTH ENDS OF THE |
| | BUILDING STATE 5'-0" FROM PROPERTY LINE |
| | |
| | 18)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF R401.3 FBC RES. |
| | SITE SHALL NOT DRAIN ON ADJACENT PROPERTY |
| | |
| | 19)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS |
| | OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES |
| | ONLY FOR REFERENCE |
| | |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH ADMINISTRATIVE |
| | AMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | |