Notes
Date Text
2007-03-23 07:29:36 
  
 ****** UNSAT ******
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN
 SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-33
 2003 NFPA-86
 ** SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THIS NOTE.
  
 2) NOTE: PLEASE SEE PLANS ARE MISSING TITLE BLOCKS AS
 REQUIRED PER FAC 61G15-23.002. PLEASE ALSO SEE FS
 471.023 AND INCLUDE INFORMATION WHERE APPLICABLE.
  
 3) NOTE: PLEASE SEE THAT ALL CLEARANCES ARE REQUIRED TO
 BE SHOWN AND LAYOUT OF UNIT AND SURROUNDING CLASS
 LOCATIONS ON PLANS.
 PLEASE SEE NFPA-70 516
  
 4) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER
 SHOWING HOW ALL NEW ELECTRICAL IS BEING FED, FROM WHERE
 AND HOW.
 PLEASE INCLUDE COMPLETE LOAD CALCULATIONS FOR NEW LOADS
 ON EXISTING EQUIPMENT ALONG WITH THE LOAD ON THE
 EQUIPMENT SERVICE EQUIPMENT.
 PLEASE SEE THAT NO INFORMATION WAS SUBMITTED EXCEPT FOR
 WHAT THE NEW ELECTRICAL ITEMS WILL BE. PLEASE KNOW THAT
 A REVIEW FOR MANY ITEMS OF CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME.
 NEC 220, 215.5, 240.4, 310.16, ETC
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AS THE
 SCOPE OF CONSTRUCTION/BUILDING WHICH SEEMS TO FALL
 UNDER A GC MAY REQUIRE A GC TO APPLY FOR PERMIT.
 PLEASE SEE THAT THE PERMIT APPLICATION WAS SUBMITTED
 UNDER A MECHANICAL CONTRACTOR'S LICENSE.
 THE STRUCTURAL SCOPE OF WORK AS SHOWN IS NOT INCIDENTAL
 TO THE SCOPE APPLIED.
 PLEASE ALSO SEE BUIDLING REVIEW NOTES AS STATING THE
 EQUIPMENT WILL MEET WIND LOADS IN LIEU OF SHOWING
 SPECIFIC DETAILS IS NOT PERMITTED.
 FS 489, CILB, AND PBCLB.
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT
 SHEETS FOR ANY LISTED EQUIPMENT WHICH IS PART OF THIS
 LISTED ASSEMBLY.
 110.3, 90.7.
 FBC 106.1.2
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-22 20:02:472007-03-22 20:02:47
 NOTES TO FOLLOW ONCE REVIEW IS COMPLETE.