Plan Review Notes
Plan Review Notes For Permit 07030410
Permit Number 07030410
Review Stop E
Sequence Number 2
Notes
Date Text
2007-05-24 09:23:18 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 ALL PLANS.
  
 2} CRCUITS 24,26 & 28 ON THE PANEL SCHEDULE HAVE #14
 CONDUCTORS ON 20 AMP BREAKERS, IN VIOLATION OF 310.16.
 PLEASE VERIFY AND CORRECT. NOTE 210.11(C)(3) REGARDING
 20 AMP BATHROOM REQUIREMENTS.
  
 3} A RECEPTACLE IS REQUIRED WITHIN 2' OF THE SINK
 (ABOVE THE DISHWASHER) PER 210.52(C)(1). NEC. ALSO SEE
 210.8 FOR GFCI REQUIREMENTS.
  
 4} A SMOKE ALARM IS REQUIRED OUTSIDE THE "GREAT ROOM"
 AS IT MEETS THE DEFINITION OF BEDROOM IN THE FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718