| 2007-03-15 14:36:06 | |
| | |
| | DENIED/INCOMPLETE INFORMATION |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | THE SCOPE OF ELECTRICAL WORK IN THE DESCRIPTION ON THE |
| | APPLICATION IS NOT CLEAR, NOR DOES THE PLAN INDICATE IF |
| | THE SERVICE IS NEW OR EXISTING. |
| | |
| | 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| | SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS, |
| | PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS |
| | PER 106.3.5.4 FBC. THE NOTE ON THE RISER INDICAES #2 |
| | AWG CONDUCTORS, TOO SMALL FOR 200 AMPS PER |
| | 310.15(B)(6), THE GROUNDING ELECTRODE DOES NOT INDICATE |
| | THE CONNECTIONS TO COMPLETE THE SYSTEM PER 250.50, THE |
| | CONDUTORS IN THE RISER CONDUIT ARE NOT SIZED. |
| | |
| | 2} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE |
| | AND AMPERE RATING, MAIN LUG OR MAIN BREAKER. INDICATE |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC |
| | AS AMENDED. |
| | |
| | 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW |
| | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS." |
| | |
| | 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 5} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR |
| | REVIEW PER 106.1 FBC AS AMENDED. |
| | |
| | 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |