2007-03-15 14:36:06 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE SCOPE OF ELECTRICAL WORK IN THE DESCRIPTION ON THE
 APPLICATION IS NOT CLEAR, NOR DOES THE PLAN INDICATE IF
 THE SERVICE IS NEW OR EXISTING.
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC. THE NOTE ON THE RISER INDICAES #2
 AWG CONDUCTORS, TOO SMALL FOR 200 AMPS PER
 310.15(B)(6), THE GROUNDING ELECTRODE DOES NOT INDICATE
 THE CONNECTIONS TO COMPLETE THE SYSTEM PER 250.50, THE
 CONDUTORS IN THE RISER CONDUIT ARE NOT SIZED.
  
 2} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE
 AND AMPERE RATING, MAIN LUG OR MAIN BREAKER. INDICATE
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED.
  
 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 5} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  