Plan Review Notes
Plan Review Notes For Permit 07030384
Permit Number 07030384
Review Stop M
Sequence Number 1
Notes
Date Text
2007-03-12 08:41:36** FOR PLAN REVIEW ONLY **
 *** DENIED ***
 1) SEE MECHANICAL PLANS PAGE M2.01 MECHANICAL NOTES 1.
 PLEASE SHOW AS 2004 FLORIDA BUILDING CODE RESIDENTIAL.
  
 2) SEE MECHANICAL PLANS MECHANICAL NOTE 3. PLEASE UP
 DATE EQUIPMENT INFORMATION AS 10 SEER EQUIPMENT IS NO
 LONGER PERMITTED NEED TO GO TO 13 SEER, ALSO SHOW AIR
 HANDLER AND CONDENSER UNIT MODEL NUMBERS. SEE 2004 FBC
 13-407.1.ABC.3.2.1 (12-8-06 REVISION).
  
 3) PLEASE SUBMIT REVISED ENERGY CALCULATIONS ON FORM
 600A-04-R, SEE 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 4) HAVE REVISED ENERGY CALCULATIONS SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.