Plan Review Notes
Plan Review Notes For Permit 07030384
Permit Number 07030384
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-10 15:54:29** UNSAT **
  
 ** PLAN REVIEW ONLY*
 COLEMAN PARK PROJECT
 PLANS SUBMITTED FOR A NEW MASTER PLAN.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT ANY REFERENCES TO THE 2002 NEC
 SHOULD BE CHANGED TO THE 2005 NEC.
  
 2) NOTE: PLEASE KNOW THAT THE PLANS NEED TO CORRELATE
 WITH ALL CIRCUIT DESIGNATIONS ON PLANS FOR ROOMS AND
 AREAS. PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY
 IN THE CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE. (CIRCUITS 1-5)
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2
  
 3) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULES INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS ALONG WITH NOTES ON PLANS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 4) NOTE: PLEASE SEE THE PLANS SHOULD INDICATE THE
 DEVICE FOR THE DISHWASHER DISPOSAL. ? SWITCHED ETC?
 PLEASE ALSO SEE 210.4B AS A 2-POLE BREAKER IS REQUIRED
 IF THESE ARE BEING FED FROM THE SAME DEVICE/YOKE.
 PLEASE REVISE PANEL SCHEDULE.
 PLEASE ALSO CLARIFY LOCATION OF THE SWITCH FOR THE
 DISPOSAL, THIS IS NOT A CODE ISSUE, ONLY SEEMS THE
 SWITCH BEING LOCATED ON THE OTHER SIDE OF THE ROOM MAY
 BE PLACED CLOSER TO THE SINK/UNIT AREA?
  
 5) NOTE: PLEASE CLARIFY THE DINING ROOM/AREA BEING ON
 ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS AS REQUIRED
 PER 210.52B1, 210.11C1, 220.52.
 * PLEASE REVISE PANEL SCHEDULE TO INDICATE.
  
 6) NOTE: PLEASE INDICATE THE 3FOR THE 3WAY SWITCHES IN
 HALLWAY BY BEDROOM #1.
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE INDICATE HOW CONDUIT FROM METER TO MAIN
 BREAKER PANEL IS BEING ROUTED. PLEASE KNOW THAT AS PER
 230.70 NO MORE THAN 8FT OF UNPROTECTED CONDUCTORS IS
 PERMITTED INSIDE DWELLING. PLEASE KNOW THIS INCLUDES
 ROUTING OVERHEAD, OR IN WALLS. THIS IS BASED ON TOTAL
 LENGTH. IS THIS IN THE SLAB OR NOTE/CLARIFY THE 8FT.
  
 8) NOTE: PLEASE PLACE TYPE OF RECESSED LIGHTING FIXTURE
 ON PLANS/FIXTURE LEGEND AS REQUIRED UNDER FBC CHAPTER
 13, 13-606.1.ABC.1.2.4.
  
 9) NOTE: PLEASE SEE BUILDING REVIEW NOTES ALSO, AS EACH
 PERMIT WILL REQUIRE ENERGY CALCULATIONS PER 2004 FBC W/
 2006 REVISIONS AND SHALL BE SIGNED, DATED AND SEALED BY
 THE DESIGNER OF RECORD AS REQUIRED IN 13-103.1.1.1
  
 10) NOTE: PLEASE SEE THE WATER HEATER IS BEING SHOWN
 WITH A 220V OUTLET. THIS IS REQUIRED TO BE HARDWIRED.
 PLEASE SHOW J-BOX IF THE BREAKER IN PANEL WILL BE USED
 FOR DISCONNECTING MEANS, OR SHOW DISCONNECT AS REQUIRED
 PER 422.30, 422.31.
 PLEASE KNOW THIS CAN BE A 2-POLE/240V RATED TOGGLE
 SWITCH.
  
 11) NOTE: PLEASE INDICATE THE DISCONNECTING MEANS FOR
 THE AHU. PLEASE SEE THIS IS ALSO SHOWN AS A 220V OUTLET
 WHERE DISCONNECT IS REQUIRED. 440.11
 PLEASE KNOW THIS MUST ALSO BE HARDWIRED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]