| Plan Review Notes For Permit 07030371 |
| Permit Number |
07030371 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-26 16:25:18 | *** DENIED *** | | | 1) THE PLANS NEED THE JOB ADDRESS ON THEM. | | | | | | 2) THE PLANS NEED AN A/C EQUIPMENT LISTING ON THEM | | | SHOWING THE A/C EQUIPMENT MANUF., MODEL NUMBER, TOTAL | | | BTU'S, SENSIBLE BTU'S, SEER, AND ALL OTHER PERTINENT | | | INFORMATION, PLEASE ALSO STATE IF NEW OR EXISTING | | | EQUIPMENT. | | | | | | 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 4) SEE PLANS THE TWO YELLOW HIGH LIGHTED SUPPLY AIR | | | DUCTS NEED TO BE SIZED. | | | | | | 5) SEE PLANS THE ROOM NEXT TO HER CLOSET IN THE MASTER | | | SUITE IS NOT LABELED AND MAY NEED RETURN AIR PROVIDED | | | FOR. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|