| Plan Review Notes For Permit 07030368 |
| Permit Number |
07030368 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-26 19:28:27 | *****DENIED***** | | | | | | | | | 1.THE ADDRESS LISTED IN THE TITLE BLOCK OF THE | | | SUBMITTED MECHANICAL PLAN SHEETS IS INCORRECT.SEE | | | STRUCTURAL SHEETS. | | | | | | 2.IF THE REPLACEMENT OF THE EXISTING DUCT SMOKE | | | DETECTORS ARE WARRANTED AS INDICATED IN MECHANICAL NOTE | | | 15 ON SHEET M0.1,IN ADDITION TO SHUTTING DOWN | | | EQUIPMENT, DUCT DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM AS PER LOCAL REQUIREMENTS. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|