| 2007-03-12 18:36:48 | BUILDING REVIEW CHECKLIST: |
| | 1-RECOVER ROOFING PERMITSREQUIRES PRE-INSPECTION BY |
| | BUILDING INSPECTOR.APPLICATION SENT TO KEN CONRAD, |
| | CHIEF BUILDING INSPECTOR, FOR PRE-INSPECTION. |
| | |
| | 2- NOA #05-0613.05 FILE IS CLOSED. SEE ATTACHED COPY |
| | FROM MIAMI DADE COUNTY WEBSITE. NEED TO PROVIDE CURRENT |
| | PRODUCT APPROVAL. |
| | |
| | 3- ENGINEER CALCULATIONS: |
| | A) FASTENER SPACING OF 2.67 AT CORNER AREAS IS NOT |
| | ALLOWED. FASTENER SPACING CAN'T BE LESS THAN 4"O.C.. |
| | SEE RAS 117SEC. 8.1. |
| | |
| | B) ENGINEER TO PROVIDE RAS 117 CALCULATIONSTO |
| | DETERMINE FASTENER SPACING AS REQUIRED BY GENERAL |
| | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. |
| | |
| | B) ENGINEER TO HAVE THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER ON ALL SHEETS AS REQUIRED BY SEC. 61G15-23.002 |
| | OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 4- WITHDRAWAL RESISTANCE TEST: |
| | A) ARCHITECT NEEDS TO PROVIDE ALL HIS INFORMATION IN |
| | THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF |
| | FLORIDA ADMINISTRATIVE CODE AND SEC. 481 FLORIDA |
| | STATUTE. |
| | |
| | B) ARCHITECT TO PROVIDE ORIGINAL SIGNATURE, NOT |
| | RUBBER STAMP AS REQUIRED BY SEC. 61G1-16.003 FLORIDA |
| | ADMINISTRATIVE CODE AND SEC. 481 FLORIDA STATUTE. |
| | |
| | C) TEST WAS DONE ON FEBRUARY OF 2006 OR 2007.IF |
| | TYPO, THEN REVISE AS REQUIRED. |
| | |
| | D) THERE ARE NOT TESTS DONE IN CORNER AREAS. NEED TO |
| | DO TESTSAT CORNER AREAS AS REQUIRED BY SEC. 8.1 AND |
| | 8.2 OF TAS 105-98. |
| | |
| | |
| | 5- ROOF MOISTURE TEST: |
| | A) ARCHITECT TO PROVIDE ALL HIS INFORMATION AND |
| | ORIGINAL SIGNATURE. SEE COMMENTS ON ITEM 4 A AND B |
| | ABOVE. |
| | |
| | B) ACCORDING TO THE ROOF MOISTURE TESTS HIGH |
| | MOISTURE LEVELS ARE FOUND IN THE BOTTOM LAYER OF BUILT |
| | UP ROOF MATERIAL. PERCENT OF MOISTURE EXCEEDS THE MAX. |
| | PERCENTAGE ALLOWED BY SEC. 1521.12 FBC 2004. SPECIFY |
| | HOW IS THIS ISSUED ADDRESSED TO COMPLYWITH THIS |
| | SECTION. |
| | |
| | C) PROVIDE ALL INFORMATION REQUESTED BY SEC. 14 OF |
| | TAS 126-95. |
| | |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |