2007-04-23 11:17:18*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS OF WHERE THE SCOPE OF WORK IS
 CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE
 DETECTORS SHALL INTIATE A GENERAL FIRE ALARM.PLEASE
 SEE SHEET FA-14, FIRE ALARM SYSTEM-SEQUENCE OF
 OPERATION, UNDER DUCT DETECTORS NOTE C3.
  
 3.UL CERTIFICATE FOR CENTRAL STATION SERVICE TO BE AT
 THE FACP AND A COPY SUBMITTED TO WPB FIRE PREVENTION BY
 FINAL FIRE ALARM INSPECTION.
  
 4.WATERFLOW TO ACTIVATE A GENERAL FIRE ALARM WITHIN
 45 TO 60 SECONDS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED.
  
  