| Date |
Text |
| 2007-06-04 11:00:12 | DENIED REVISION |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW ON THE REVISION TO MEET CODE |
| | COMPLIANCE: |
| | NOTE: THE PLAN REVISION FORM ADDRESS OF JOB WAS |
| | INCORRECTLY INDICATED AS THE ADDRESS OF CONTRACTOR, |
| | PLEASE SEE RED LINE CORRECTIONS OF THIS AND PLEASE |
| | SUBMIT THE CORRECT ADDRESS OF JOB ON FUTURE REVISIONS. |
| | ALSO NOTE THAT REVISION FEES ARE OWED FOR THIS REVISION |
| | OF $60.00 AND REVISION FEES WILL BE REQUIRED FOR THE |
| | CORRECTED REVISION SUBMITTAL. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE SUBMITTED REVISION IS NOT INDICATING ALL |
| | CORRESPONING LENGTHS ON ALL CUT SECTIONS OF PIPE TO |
| | VERIFY THE NEW INDICATED LONGEST RUN OF 75'. PLEASE |
| | CLEARLY INDICATE THE GAS METER ON THE NEXT RESUBMITTED |
| | REVISION. PLEASE CORRECT. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: THE SUBMITTED REVISION IS NOT INDICATING ALL |
| | PIPING MATERIALS BEING USED ON ALL CUT SECTIONS. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THIS GOES ALONG WITH COMMENT NUMBER ONE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS REVIEWER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |