| 2007-03-27 12:16:50 | *****UNSAT***** | | | | | | | | | PLEASE BE ADVISED,AS PER THE FLORIDA BOARD OF | | | ENGINEERS, CONTRACTORS CANNOT MAKE CHANGES TO THE | | | ENGINEER'S SIGNED AND SEALED PLANS. | | | | | | | | | | | | 1.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE DONE | | | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | | SHEET. | | | | | | 2.AS PER WPB FIRE PREVENTION BUREAU, DUCT SMOKE | | | DETECTORS SHALL INITIATE A GENERAL FIRE ALARM. | | | THEREFORE IN REFERENCE TO FIRE ALARM NOTE #3, DELETE | | | "SUPERVISORY SIGNAL" AND INSERT "GENERAL FIRE ALARM". | | | | | | NEW COMMENT: | | | | | | A.RECTIFY FIRE ALARM NOTES TO INDICATE THAT NFPA 72 - | | | 2002 EDITION IS REFERENCED INSTEAD OF THE 1999 | | | EDITION. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|