| Plan Review Notes For Permit 07030319 |
| Permit Number |
07030319 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-12 17:18:32 | *****DENIED***** | | | | | | | | | 1.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE DONE | | | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | | SHEET. | | | | | | 2.AS PER WPB FIRE PREVENTION BUREAU, DUCT SMOKE | | | DETECTORS SHALL INITIATE A GENERAL FIRE ALARM. | | | THEREFORE IN REFERENCE TO FIRE ALARM NOTE #3, DELETE | | | "SUPERVISORY SIGNAL" AND INSERT "GENERAL FIRE ALARM". | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|